| Plan Review Stops For Permit 13110464 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-11-19 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-11-19 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-11-19 |
Time |
09:06 |
Sent To |
I |
|
| Notes |
| 2013-11-19 09:21:00 | THOUGH THE ADDITIONAL LOAD IS PROPERLY REFLECTED, THE | | | DEDICATED CIRCUITS FOR EACH UNIT IS NOT REFLECTED ON | | | THE PANEL SCHEDULE. CORRECT THE PANEL SCHEDULE | | | ACCORDINGLY FOR FINAL INSPECTIONS. | | | | | | SENT TO SH DESK. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-11-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-11-19 |
Time |
16:18 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-11-14 |
Time |
08:36 |
Sent To |
|
|
| Notes |
| 2013-11-14 08:37:51 | ROUTED TO ELECTRIC $5000 & UNDER |
|
|
|