Plan Review Details - Permit 13110419
Plan Review Stops For Permit 13110419
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-12 Cont ID  
Sent By skennedy Date 2013-12-12 Time 09:44 Rev Time 0.00
Received By skennedy Date 2013-12-12 Time 09:44 Sent To FIRE
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-30 Cont ID  
Sent By jwitmer Date 2013-11-30 Time 11:49 Rev Time 0.00
Received By jwitmer Date 2013-11-30 Time 11:43 Sent To  
Notes
2013-11-30 11:49:33BUILDING PLAN REVIEW
 PERMIT: 13110419
 ADD: 2121 OKEECHOBEE BLVD
 CONT: TO BE DETERMINED
 TEL: (314)821-1100
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 30/ 2013
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 107.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS: THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL INCLUDE THE
 FOLLOWING MINIMUM CRITERIA AND DOCUMENTS: MISSING THE
 LIFE SAFETY PLAN AS INDICATED IN THE INDEX SHEET A0.1
 LIFE SAFETY PLAN.
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-03 Cont ID  
Sent By skennedy Date 2013-12-03 Time 15:12 Rev Time 0.00
Received By skennedy Date 2013-12-03 Time 15:12 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-12-12 Cont ID  
Sent By scaldero Date 2013-12-12 Time 14:35 Rev Time 0.00
Received By scaldero Date 2013-12-12 Time 14:35 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-19 Cont ID  
Sent By scaldero Date 2013-11-19 Time 15:56 Rev Time 0.00
Received By scaldero Date 2013-11-19 Time 15:56 Sent To  
Notes
2013-11-19 16:00:43PERMIT #13110419
 FIRE DEPARTMENT - PLANS REVIEW COMMENTS
  
 ****FAIL COMMENTS****
 SHEET A0.0 INDICATES THAT A LIFE SAFETY PLAN IS
 PROVIDED UNDER SHEET A0.1. SHEET A0.1 NOT INCLUDED.
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-12 Cont ID  
Sent By scaldero Date 2013-12-13 Time 14:36 Rev Time 0.00
Received By shill Date 2013-12-09 Time 18:48 Sent To  
Notes
2013-12-09 18:49:47IN SKENNEDY OFFICE TO BE REASSEMBLED AS WAS MAILED IN.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-03 Cont ID  
Sent By skennedy Date 2013-12-03 Time 15:12 Rev Time 0.00
Received By skennedy Date 2013-11-13 Time 15:12 Sent To  
Notes
2013-11-13 15:13:58INCOMING SENT TO C-18. JW

Review Stop Z ZONING
Rev No 1 Status N Date 2013-11-19 Cont ID  
Sent By ajones Date 2013-11-19 Time 10:32 Rev Time 0.00
Received By ajones Date 2013-11-19 Time 10:32 Sent To  
Notes
***NONE***