| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-11-14 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-11-14 |
Time |
18:05 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-11-14 |
Time |
16:41 |
Sent To |
|
|
| Notes |
| 2013-11-14 18:06:23 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ONE STORY STRUCTURE IS LOCATED IN EXPOSURE | | | CATEGORY C, PER FBC R301.2.1.4.3. THE W-32 SYSTEM THAT | | | WAS SELECTED FROM THE FLAT ROOF PRODUCT APPROVAL (FL | | | 1654) HAS A MAXIMUM DESIGN PRESSURE OF -90 PSF. THIS IS | | | TOO LOW FOR ROOF ZONE 3 (THE CORNER AREAS). THIS IS A | | | FULLY BONDED ASSEMBLY AND CAN NOT BE INCREASED BY | | | RATIONAL ANALYSIS PER NOTE #9 ON PAGE 2 OF THE PRODUCT | | | APPROVAL. ANOTHER SYSTEM WILL BE REQUIRED. | | | | | | 2) SPECIFY THE MEAN ROOF HEIGHT AND ROOF SLOPE FOR THE | | | METAL ROOF. CITY AMENDMENTS 107.2.1 | | | | | | 3) SPECIFY THE SQFT OF SLOPED ROOF AND THE SQFT OF THE | | | FLAT ROOF. CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
|