| Plan Review Stops For Permit 13110257 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2014-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-27 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-27 |
Time |
06:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2014-01-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-08 |
Time |
08:15 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-08 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2014-01-08 09:41:18 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE ARCHITECT THAT SEALED THE PLANS HAS HAD HIS | | | LICENSE REVOKED AND CAN NO LONGER PERFORM DESIGN WORK. | | | THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL HAND | | | WRITTEN SIGNATURE OF THE ARCHITECT THAT IS SIGNING AND | | | SEALING THE PLANS. FACIMILIES, COPIES OR SIGNATURE | | | STAMPS ARE NOT ACCEPTABLE. FBC 61G1-16.003 | | | | | | 2) PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE WINDOW | | | OPENING AT THE REAR ROOM WILL BE ENCLOSED. CITY | | | AMENDMENTS 107.2.1 AND FBC R301.1 | | | | | | 3) REVISE THE PLANS AND THE WINDOW SCHEDULE TO SHOW THE | | | LOCATIONS AND SIZES OF THE HORIZONTAL SLIDING WINDOWS | | | REFERENCED IN YOUR LETTER. CITY AMENDMENTS 107.2.1 AND | | | FBC R310 | | | | | | 4) SPECIFY THE WIND DESIGN DATA ( 170 MPH VULT, | | | EXPOSURE CATEGORY D) AND SPECIFY THE REQUIRED OPENING | | | PRESSURES ON THE PLANS. FBCR 301.2.1 | | | | | | 5) PROVIDE THE FLORIDA PRODUCT APPROVAL NUMBER FOR THE | | | JELD-WEN EXTERIOR DOOR THAT WAS SUBMITTED. DCA RULE | | | 9N-3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-12-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-11 |
Time |
07:55 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-11 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2013-12-11 06:52:48 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE PLANS THAT WERE SUBMITTED ARE TOO SMALL. | | | BUILDING PLANS ARE REQUIRED TO BE DRAWN TO A MINIMUM | | | 1/8 INCH SCALE PER CITY AMENDMENTS 107.2.1.4 | | | | | | 2) PLANS SUBMITTED FOR PUBLIC RECORD FROM AN ARCHITECT | | | ARE REQUIRED TO BE DATED, SIGNED AND SEALED BY HIM. THE | | | ARCHITECT HAND WRITTEN SIGNATURE IS REQUIRED. COPIES, | | | STAMPS OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FS 481 | | | AND FAC 61G1-16.003 | | | | | | 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE ES | | | FIXED WINDOWS ARE EXPIRED. SUBMIT TWO CURRENT COPIES OF | | | THE PRODUCT APPROVALS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 4) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR | | | THE EXTERIOR DOORS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 5) PRODUCT APPROVALS WERE SUBMITTED FOR CASEMENT | | | WINDOWS, HOWEVER, NONE WERE SPECIFIED IN THE WINDOW | | | SCHEDULE. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 | | | | | | 6) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR | | | STRUCTURAL MULLIONS USED TO CONNECT THE DOUBLE WINDOWS | | | AS REQUIRED BY DCA RULE 9N-3. | | | | | | 7) THE BEDROOM WINDOWS NEED TO COMPLY WITH FBC R310 FOR | | | EMERGENCY ESCAPE AND RESCUE OPENINGS AND THE REQUIRED | | | NET CLEAR OPENING AREA, OPENING HEIGHT AND OPENING | | | WIDTH. THIS MAY REQUIRE INSTALLING CASEMENT WINDOWS OR | | | SINGLE HUNG COMPACT EGRESS WINDOWS THAT CAN SWING OPEN. | | | | | | 8) THE SCOPE OF WORK ON THE APPLICATION SPECIFIES THE | | | REPLACEMENT OF 17 WINDOWS AND 3 EXTERIOR DOORS. CLEARLY | | | INDICATE THE SPECIFIC DOORS AND WINDOWS THAT ARE TO BE | | | REPLACED ON THE PLANS. CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-27 |
Time |
07:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-27 |
Time |
06:53 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2014-01-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-08 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-08 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2014-01-08 09:26:30 | 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) SPECIFY THE SCOPE OF THE ELECTRICAL WORK ON THE | | | PLANS. IF NEW CIRCUITS ARE TO BE ADDED TO SERVICE NEW | | | MECHANICAL OR OTHER EQUIPMENT, SHOW THAT THE EXISTING | | | SERVICE AND PANEL ARE CAPABLE OF HANDLING THE | | | ADDITIONAL LOADS, SPECIFY THE SIZE OF THE EXISTING | | | SERVICE AND PROVIDE A PANEL SCHEDULE. CITY AMENDMENTS | | | 107.2.1 AND 107.3.5.3 | | | | | | 2) SHOW THE LOCATIONS OF THE SMOKE ALARMS REQUIRED BY | | | FBC R314.3.1 ON THE PLANS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-12-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-11 |
Time |
09:28 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-11 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2013-12-11 09:42:59 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) IN ADDITION TO THE REQUIRED LIGHTING OUTLET AND | | | EXHAUST FAN, PROVIDE AT LEAST ONE 20 AMP, GFCI | | | PROTECTED, TAMPER-RESISTANT RECEPTACLE WITHIN 3 FEET OF | | | THE OUTSIDE EDGE OF THE BASIN IN THE BATHROOM. NEC | | | 210.52(D) , 210.8, 406.11, 210.11(C)(3) | | | | | | 2) AN ELECTRICAL SUB-PERMIT IS REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-27 |
Time |
08:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-22 |
Time |
11:19 |
Sent To |
|
|
| Notes |
| 2014-01-22 11:19:36 | SENT TO R MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2014-01-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-08 |
Time |
14:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-31 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2013-12-31 14:32:46 | SENT TO R MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-12-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-11 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-11-07 |
Time |
12:03 |
Sent To |
|
|
| Notes |
| 2013-11-16 10:56:07 | R13 | | | | | 2013-11-07 12:04:12 | ROUTED TO MISC 1 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2014-01-22 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-22 |
Time |
11:20 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-22 |
Time |
11:20 |
Sent To |
|
|
| Notes |
| 2014-01-22 11:21:37 | A SEPARATE PERMIT APPLICATION, PLANS AND REVIEW IS | | | REQUIRED FOR THE MECHANICAL PERMIT. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2014-01-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-08 |
Time |
08:21 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-08 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2014-01-08 09:08:31 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) THE SCOPE OF MECHANICAL WORK IS NOT CLEAR. NO HVAC | | | EQUIPMENT IS SHOWN ON THE EXISTING FLOOR PLAN AND FROM | | | THE NOTES IT APPEARS THAT A NEW SYSTEM IS BEING | | | INSTALLED. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1 | | | | | | 2) IF A NEW HVAC SYSTEM IS TO BE INSTALLED, SUBMIT TWO | | | COPIES OF EQUIPMENT SIZING CALCULATIONS, TWO SETS | | | MECHANICAL PLANS SHOWING THE DUCT SIZES AND LOCATIONS, | | | GRILL SIZES LOCATIONS AND CFMS AT EACH OUTLET. SHOW | | | COMPLIANCE WITH FBCR M1602.04 FOR BALANCED RETURN AIR. | | | INCLUDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS | | | THAT CORRESPONDS WITH THE EQUIPMENT SIZING | | | CALCULATIONS. FBCR M1401.3, FBCR M1601.1 AND CITY | | | AMENDMENTS 107.3.5.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-12-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-11 |
Time |
07:16 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-11 |
Time |
07:16 |
Sent To |
|
|
| Notes |
| 2013-12-11 07:54:58 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) BECAUSE THE PROPOSED BATHROOM DOES NOT HAVE ANY | | | WINDOWS, IT IS REQUIRED BY FBC R303.3 TO HAVE A | | | MECHANICAL VENTILATION SYSTEM INSTALLED IN ACCORDANCE | | | WITH FBCR M1507. | | | | | | 2) A MECHANICAL SUB-PERMIT IS REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2014-01-27 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-27 |
Time |
07:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-27 |
Time |
06:53 |
Sent To |
|
|
| Notes |
| 2014-01-27 07:34:04 | APPROVED WITH EXCEPTION. PLANS HAVE BEEN REDLINED TO | | | COMPLY WITH CODE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2014-01-08 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-01-08 |
Time |
07:48 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-01-08 |
Time |
06:56 |
Sent To |
|
|
| Notes |
| 2014-01-08 07:49:30 | APPROVED WITH EXCEPTION. PLANS HAVE BEEN REDLINED TO | | | COMPLY WITH CODE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2013-12-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-11 |
Time |
07:02 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-11 |
Time |
06:37 |
Sent To |
|
|
| Notes |
| 2013-12-11 07:02:42 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) SUBMIT TWO COPIES OF A PLUMBING RISER DIAGRAM OF THE | | | DRAIN, WASTE AND VENT SYSTEM FOR THE NEW BATHROOM. CITY | | | AMENDMENTS 107.3.5.3 | | | | | | 2) THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF | | | THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED ON | | | THE DRAWINGS. CITY AMENDMENTS 107.2.1 | | | | | | 3) A PLUMBING SUB-PERMIT IS REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|