Plan Review Details - Permit 13110257
Plan Review Stops For Permit 13110257
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-01-27 Cont ID  
Sent By rmcdouga Date 2014-01-27 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2014-01-27 Time 06:53 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 08:15 Rev Time 0.00
Received By rmcdouga Date 2014-01-08 Time 06:56 Sent To  
Notes
2014-01-08 09:41:182010 FBC
  
 DENIED BY BUILDING
  
 1) THE ARCHITECT THAT SEALED THE PLANS HAS HAD HIS
 LICENSE REVOKED AND CAN NO LONGER PERFORM DESIGN WORK.
 THE PLANS ARE REQUIRED TO HAVE THE ORIGINAL HAND
 WRITTEN SIGNATURE OF THE ARCHITECT THAT IS SIGNING AND
 SEALING THE PLANS. FACIMILIES, COPIES OR SIGNATURE
 STAMPS ARE NOT ACCEPTABLE. FBC 61G1-16.003
  
 2) PROVIDE A STRUCTURAL DETAIL SHOWING HOW THE WINDOW
 OPENING AT THE REAR ROOM WILL BE ENCLOSED. CITY
 AMENDMENTS 107.2.1 AND FBC R301.1
  
 3) REVISE THE PLANS AND THE WINDOW SCHEDULE TO SHOW THE
 LOCATIONS AND SIZES OF THE HORIZONTAL SLIDING WINDOWS
 REFERENCED IN YOUR LETTER. CITY AMENDMENTS 107.2.1 AND
 FBC R310
  
 4) SPECIFY THE WIND DESIGN DATA ( 170 MPH VULT,
 EXPOSURE CATEGORY D) AND SPECIFY THE REQUIRED OPENING
 PRESSURES ON THE PLANS. FBCR 301.2.1
  
 5) PROVIDE THE FLORIDA PRODUCT APPROVAL NUMBER FOR THE
 JELD-WEN EXTERIOR DOOR THAT WAS SUBMITTED. DCA RULE
 9N-3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 07:55 Rev Time 0.00
Received By rmcdouga Date 2013-12-11 Time 06:37 Sent To  
Notes
2013-12-11 06:52:482010 FBC
  
 DENIED BY BUILDING
  
 1) THE PLANS THAT WERE SUBMITTED ARE TOO SMALL.
 BUILDING PLANS ARE REQUIRED TO BE DRAWN TO A MINIMUM
 1/8 INCH SCALE PER CITY AMENDMENTS 107.2.1.4
  
 2) PLANS SUBMITTED FOR PUBLIC RECORD FROM AN ARCHITECT
 ARE REQUIRED TO BE DATED, SIGNED AND SEALED BY HIM. THE
 ARCHITECT HAND WRITTEN SIGNATURE IS REQUIRED. COPIES,
 STAMPS OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FS 481
 AND FAC 61G1-16.003
  
 3) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE ES
 FIXED WINDOWS ARE EXPIRED. SUBMIT TWO CURRENT COPIES OF
 THE PRODUCT APPROVALS AS REQUIRED BY DCA RULE 9N-3.
  
 4) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR
 THE EXTERIOR DOORS AS REQUIRED BY DCA RULE 9N-3.
  
 5) PRODUCT APPROVALS WERE SUBMITTED FOR CASEMENT
 WINDOWS, HOWEVER, NONE WERE SPECIFIED IN THE WINDOW
 SCHEDULE. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 6) SUBMIT TWO CURRENT COPIES OF PRODUCT APPROVALS FOR
 STRUCTURAL MULLIONS USED TO CONNECT THE DOUBLE WINDOWS
 AS REQUIRED BY DCA RULE 9N-3.
  
 7) THE BEDROOM WINDOWS NEED TO COMPLY WITH FBC R310 FOR
 EMERGENCY ESCAPE AND RESCUE OPENINGS AND THE REQUIRED
 NET CLEAR OPENING AREA, OPENING HEIGHT AND OPENING
 WIDTH. THIS MAY REQUIRE INSTALLING CASEMENT WINDOWS OR
 SINGLE HUNG COMPACT EGRESS WINDOWS THAT CAN SWING OPEN.
  
 8) THE SCOPE OF WORK ON THE APPLICATION SPECIFIES THE
 REPLACEMENT OF 17 WINDOWS AND 3 EXTERIOR DOORS. CLEARLY
 INDICATE THE SPECIFIC DOORS AND WINDOWS THAT ARE TO BE
 REPLACED ON THE PLANS. CITY AMENDMENTS 107.2.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-01-27 Cont ID  
Sent By rmcdouga Date 2014-01-27 Time 07:33 Rev Time 0.00
Received By rmcdouga Date 2014-01-27 Time 06:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 09:09 Rev Time 0.00
Received By rmcdouga Date 2014-01-08 Time 06:56 Sent To  
Notes
2014-01-08 09:26:302008 NEC
  
 DENIED BY ELECTRIC
  
 1) SPECIFY THE SCOPE OF THE ELECTRICAL WORK ON THE
 PLANS. IF NEW CIRCUITS ARE TO BE ADDED TO SERVICE NEW
 MECHANICAL OR OTHER EQUIPMENT, SHOW THAT THE EXISTING
 SERVICE AND PANEL ARE CAPABLE OF HANDLING THE
 ADDITIONAL LOADS, SPECIFY THE SIZE OF THE EXISTING
 SERVICE AND PROVIDE A PANEL SCHEDULE. CITY AMENDMENTS
 107.2.1 AND 107.3.5.3
  
 2) SHOW THE LOCATIONS OF THE SMOKE ALARMS REQUIRED BY
 FBC R314.3.1 ON THE PLANS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 09:28 Rev Time 0.00
Received By rmcdouga Date 2013-12-11 Time 06:37 Sent To  
Notes
2013-12-11 09:42:592010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) IN ADDITION TO THE REQUIRED LIGHTING OUTLET AND
 EXHAUST FAN, PROVIDE AT LEAST ONE 20 AMP, GFCI
 PROTECTED, TAMPER-RESISTANT RECEPTACLE WITHIN 3 FEET OF
 THE OUTSIDE EDGE OF THE BASIN IN THE BATHROOM. NEC
 210.52(D) , 210.8, 406.11, 210.11(C)(3)
  
 2) AN ELECTRICAL SUB-PERMIT IS REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-01-27 Cont ID  
Sent By rmcdouga Date 2014-01-27 Time 08:20 Rev Time 0.00
Received By rmcdouga Date 2014-01-22 Time 11:19 Sent To  
Notes
2014-01-22 11:19:36SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 14:33 Rev Time 0.00
Received By rmcdouga Date 2013-12-31 Time 14:32 Sent To  
Notes
2013-12-31 14:32:46SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 09:43 Rev Time 0.00
Received By rmcdouga Date 2013-11-07 Time 12:03 Sent To  
Notes
2013-11-16 10:56:07R13
  
2013-11-07 12:04:12ROUTED TO MISC 1

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2014-01-22 Cont ID  
Sent By rmcdouga Date 2014-01-22 Time 11:20 Rev Time 0.00
Received By rmcdouga Date 2014-01-22 Time 11:20 Sent To  
Notes
2014-01-22 11:21:37A SEPARATE PERMIT APPLICATION, PLANS AND REVIEW IS
 REQUIRED FOR THE MECHANICAL PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 08:21 Rev Time 0.00
Received By rmcdouga Date 2014-01-08 Time 06:56 Sent To  
Notes
2014-01-08 09:08:312010 FBC
  
 DENIED BY MECHANICAL
  
 1) THE SCOPE OF MECHANICAL WORK IS NOT CLEAR. NO HVAC
 EQUIPMENT IS SHOWN ON THE EXISTING FLOOR PLAN AND FROM
 THE NOTES IT APPEARS THAT A NEW SYSTEM IS BEING
 INSTALLED. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 2) IF A NEW HVAC SYSTEM IS TO BE INSTALLED, SUBMIT TWO
 COPIES OF EQUIPMENT SIZING CALCULATIONS, TWO SETS
 MECHANICAL PLANS SHOWING THE DUCT SIZES AND LOCATIONS,
 GRILL SIZES LOCATIONS AND CFMS AT EACH OUTLET. SHOW
 COMPLIANCE WITH FBCR M1602.04 FOR BALANCED RETURN AIR.
 INCLUDE AN EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS
 THAT CORRESPONDS WITH THE EQUIPMENT SIZING
 CALCULATIONS. FBCR M1401.3, FBCR M1601.1 AND CITY
 AMENDMENTS 107.3.5.3
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 07:16 Rev Time 0.00
Received By rmcdouga Date 2013-12-11 Time 07:16 Sent To  
Notes
2013-12-11 07:54:582010 FBC
  
 DENIED BY MECHANICAL
  
 1) BECAUSE THE PROPOSED BATHROOM DOES NOT HAVE ANY
 WINDOWS, IT IS REQUIRED BY FBC R303.3 TO HAVE A
 MECHANICAL VENTILATION SYSTEM INSTALLED IN ACCORDANCE
 WITH FBCR M1507.
  
 2) A MECHANICAL SUB-PERMIT IS REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-01-27 Cont ID  
Sent By rmcdouga Date 2014-01-27 Time 07:32 Rev Time 0.00
Received By rmcdouga Date 2014-01-27 Time 06:53 Sent To  
Notes
2014-01-27 07:34:04APPROVED WITH EXCEPTION. PLANS HAVE BEEN REDLINED TO
 COMPLY WITH CODE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-01-08 Cont ID  
Sent By rmcdouga Date 2014-01-08 Time 07:48 Rev Time 0.00
Received By rmcdouga Date 2014-01-08 Time 06:56 Sent To  
Notes
2014-01-08 07:49:30APPROVED WITH EXCEPTION. PLANS HAVE BEEN REDLINED TO
 COMPLY WITH CODE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 07:02 Rev Time 0.00
Received By rmcdouga Date 2013-12-11 Time 06:37 Sent To  
Notes
2013-12-11 07:02:422010 FBC
  
 DENIED BY PLUMBING
  
 1) SUBMIT TWO COPIES OF A PLUMBING RISER DIAGRAM OF THE
 DRAIN, WASTE AND VENT SYSTEM FOR THE NEW BATHROOM. CITY
 AMENDMENTS 107.3.5.3
  
 2) THE PRINTED NAME, SIGNATURE AND LICENSE NUMBER OF
 THE PERSON RESPONSIBLE FOR THE DESIGN IS REQUIRED ON
 THE DRAWINGS. CITY AMENDMENTS 107.2.1
  
 3) A PLUMBING SUB-PERMIT IS REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]