Plan Review Details - Permit 13110240
Plan Review Stops For Permit 13110240
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-13 Cont ID  
Sent By jgomez Date 2014-01-13 Time 10:27 Rev Time 0.00
Received By jgomez Date 2014-01-13 Time 10:27 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-10 Cont ID  
Sent By jgomez Date 2013-12-10 Time 10:49 Rev Time 0.00
Received By jgomez Date 2013-12-10 Time 10:40 Sent To  
Notes
2013-12-10 11:13:28RESIDENTIAL (R3) ADDITION/ALTERATION, BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL NEW WINDOWS AND WINDOWS TO BE REPLACED AS SHOWN
 ON PLANS. (SINGLE HUNG WINDOWS AND FIXED WINDOWS)
  
 B) ALL NEW DOORS AND DOORS TO BE REPLACED AS SHOWN ON
 PLANS.
  
 C) CEMENT BOARD SOFFIT AS SHOWN ON PLANS AND SECTIONS.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAIL/SECTIONS. ***NOTE: PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR.
  
 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS TO FBC.
  
 3- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC.
 101.4.3 OF 2010 FBC-ENERGY CONSERVATION. AND,
 COORDINATE WITH INFORMATION SHOWN ON PLANS.
  
 4- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.
  
 5- PROVIDE MANUFACTURER SPECIFICATIONS FOR THE THE
 SPRAYED INSULATION TO BE USED. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION AND SEC. R316 OF 2010
 FBC-RESIDENTIAL.
  
 6- DOORS AND WINDOWS DESIGN PRESSURES SHOWN ON SHEET A2
 DON'T MATCH DESIGN PRESSURES SHOWN ON THE WIND LOAD
 FACTORS ON SHEET S1. REVISE AS REQUIRED TO MATCH.
 ***NOTE: ACCORDING TO SEC. R301.2.1.4.3 OF 2010
 FBC-RESIDENTIAL, THIS BUILDING IS LOCATED ON EXPOSURE
 "C" NOT "B". REVISE AS REQUIRED ALSO.
  
 7- SHEET A4: R19 BATT INSULATION DOESN'T FIT ON A 2 X 4
 WOOD FRAMED WALLS. REVISE AS REQUIRED AND COORDINATE
 WITH THE ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-13 Cont ID  
Sent By skennedy Date 2014-01-13 Time 14:45 Rev Time 0.00
Received By skennedy Date 2014-01-13 Time 14:43 Sent To  
Notes
2014-01-13 13:49:55NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-13 Cont ID  
Sent By skennedy Date 2013-12-13 Time 11:51 Rev Time 0.00
Received By skennedy Date 2013-12-13 Time 11:51 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-31 Cont ID  
Sent By skennedy Date 2014-01-31 Time 16:39 Rev Time 0.00
Received By skennedy Date 2013-12-31 Time 16:02 Sent To  
Notes
2013-12-31 16:02:03INCOMING SENT TO R15 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-13 Cont ID  
Sent By skennedy Date 2013-12-13 Time 11:50 Rev Time 0.00
Received By skennedy Date 2013-11-07 Time 15:31 Sent To  
Notes
2013-11-12 15:31:28SENT TO R4 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-01-13 Cont ID  
Sent By jgomez Date 2014-01-13 Time 11:28 Rev Time 0.00
Received By jgomez Date 2014-01-13 Time 11:28 Sent To  
Notes
2014-01-13 11:28:59PAID $176.46. MU-2013-026799. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-12-12 Cont ID  
Sent By jgomez Date 2013-12-12 Time 15:06 Rev Time 0.00
Received By jgomez Date 2013-12-12 Time 15:06 Sent To  
Notes
2013-12-12 15:08:161- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD.)
 TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK COUNTY
 STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES ARE DUE.
 REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF THE
 UNIFIED LAND DEVELOPMENT CODE.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-01-13 Cont ID  
Sent By jgomez Date 2014-01-13 Time 11:34 Rev Time 0.00
Received By jgomez Date 2014-01-13 Time 11:34 Sent To  
Notes
2014-01-13 13:37:36MECHANICAL REVIEW APPROVED WITH PROVISO:
  
 1- REVISE SIZE OF TRANSFER GRILL FOR ALL BEDROOMS AND
 OFFICE. SIZE TO COMPLY WITH EXCEPTION #2 OF SEC.
 M1602.4
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-13 Cont ID  
Sent By jgomez Date 2013-12-12 Time 17:05 Rev Time 0.00
Received By jgomez Date 2013-12-12 Time 17:05 Sent To  
Notes
2013-12-12 17:06:06RESIDENTIAL (R3) ADDITION/ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS AS
 REQUIRED BY SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- HVAC PLAN TO SHOW COMPLIANCE WITH THE BALANCED
 RETURN AIR REQUIRED FOR THE HABITABLE ROOMS (OFFICE AND
 ALL BEDROOMS). SEC. M1602.4 OF 2010 FBC-RESIDENTIAL.
  
 3- HVAC PLAN TO SHOW THE SUPPLY AIR (CFM'S) FOR EACH
 ROOM. SEC. M1601.1 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-01-13 Cont ID  
Sent By jgomez Date 2014-01-13 Time 13:42 Rev Time 0.00
Received By jgomez Date 2014-01-13 Time 13:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-12-13 Cont ID  
Sent By jgomez Date 2013-12-12 Time 17:05 Rev Time 0.00
Received By jgomez Date 2013-12-12 Time 17:05 Sent To  
Notes
2013-12-12 17:05:43RESIDENTIAL (R3) ADDITION/ALTERATION, PLUMBING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM:
 A) ONLY THE FIXTURES WITHIN THE "BATHROOM GROUPS" SHALL
 CONNECT TO THE WET VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 HORIZONTAL WET VENT. SEC. P3108.1 OF 2010
 FBC-RESIDENTIAL.
 BATHROOM GROUPS WET VENT IS NOT SHOWN CORRECTLY.
 SEPARATE THE BATHROOM GROUPS HORIZONTAL WET VENTS FROM
 THE MAIN DRAIN LINE.
  
 B) NO MORE THAN ONE WET-VENTED FIXTURE DRAIN SHALL
 DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 CONNECTION. SEC. P3108.2.1 OF 2010 FBC-RESIDENTIAL. TUB
 AND TOILET FROM BATHROOM #2 ARE NOT PROPERLY VENTED.
  
 C) WASHER DRAIN NEEDS TO DISCHARGE DOWNSTREAM OF THE
 BATHROOM GROUP HORIZONTAL WET VENT. SEC. P3108.1
  
 D) CLARIFY HOW ARE THE KITCHEN SINK AND LIVING ROOM BAR
 SINK VENTED. STUDOR VENT OR DRY VENT. RISER DIAGRAM
 SHOWS BOTH. HOW TO INSTALL DRY VENT ON KITCHEN ISLAND
 SINK?. SEC. 1072.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status N Date 2013-12-12 Cont ID  
Sent By jgomez Date 2013-12-12 Time 16:48 Rev Time 0.00
Received By jgomez Date 2013-12-12 Time 16:48 Sent To  
Notes
2013-12-12 16:49:29NO ROOF WORK SHOWN ON PLANS. AND, NO ROOF PRODUCT
 APPROVAL SUBMITTED EITHER. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2014-01-30 Cont ID  
Sent By jroach Date 2014-01-30 Time 16:27 Rev Time 0.00
Received By jroach Date 2014-01-30 Time 16:27 Sent To  
Notes
2014-01-30 16:28:06 PROVISO
  
 1. PRIOR TO FINAL INSPECTION, SEPARATE LANDSCAPE AND
 IRRIGATION PERMIT APPLICATIONS SHALL BE SUBMITTED AND
 APPROVED. LANDSCAPING SHALL CONFORM TO THE MINIMUM
 REQUIREMENTS OF ARTICLE XIV OF THE CITY?S ZONING AND
 LAND DEVELOPMENT REGULATIONS.
  
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, PRINCIPAL
 PLANNER, AT [email protected] OR (561) 822-1448.
  
2014-01-02 12:13:521/2/14

Review Stop Z ZONING
Rev No 1 Status F Date 2013-11-25 Cont ID  
Sent By jroach Date 2013-11-25 Time 16:03 Rev Time 0.00
Received By jroach Date 2013-11-25 Time 16:03 Sent To  
Notes
2013-11-25 16:05:14ZONING PLAN REVIEW
 ___________________________________________
  
 DATE OF REVIEW: 11.25.2013
 PERMIT NO.: 13110240
 ADDRESS: 301 PALMETTO STREET
 CONTRACTOR/CONTACT: LUKAS VARNAVICIUS
 TELEPHONE NO.: 561.639.9090
 SCOPE OF REVIEW: INTERIOR/EXTERIOR ALTERATIONS TO
 EXISTING RESIDENTIAL STRUCTURE
 ___________________________________________
  
 REVIEW STATUS: FAILED
 ___________________________________________
  
 PLEASE PROVIDE A WRITTEN RESPONSE TO THE FOLLOWING PLAN
 REVIEW COMMENTS:
  
 1. PURSUANT TO SECTION 94-441 OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), BECAUSE THE
 PROPOSED SCOPE OF WORK EXCEEDS 50 PERCENT OF THE VALUE
 OF THE EXISTING STRUCTURE, THE SITE SHALL BE BROUGHT
 INTO COMPLIANCE WITH ARTICLE XIV (LANDSCAPING) OF THE
 ZLDRS. PLANS SHALL BE SUBMITTED INDICATING SUCH. IF
 EXISTING MATERIAL IS SHOWN ON THE PLANS AND ALL
 PROVISIONS OF ARTICLE XIV HAVE BEEN MET, THEN NO
 ADDITIONAL PERMIT/INSTALLATION IS REQUIRED. IF THE
 EXISTING MATERIAL ON SITE DOES NOT CONFORM TO ALL OF
 THE REQUIREMENTS OF ARTICLE XIV, THEN ADDITIONAL
 MATERIAL WILL NEED TO BE SHOWN ON THE PLANS AND
 PERMITTED UNDER A LANDSCAPE PERMIT. PLEASE NOTE THAT
 PLANS SHOULD INCLUDE, BUT NOT BE LIMITED TO, THE
 FOLLOWING:
  
  A. THE LOCATION OF ALL EXISTING AND PROPOSED
 STRUCTURES, IMPROVEMENTS, ETC.
  
  B. THE LOCATION OF ALL EXISTING AND PROPOSED TREES,
 SHRUBS, GROUND COVERS, ETC.
  
  C. THE LOCATION OF UTILITY AND DRAINAGE EASEMENTS,
 OVERHEAD LINES, WATER METERS, TRANSFORMERS, CHECK
 VALVES, CLEAN OUTS, FIRE HYDRANTS, LIGHT POLES, ETC.
 THAT MAY IMPACT LANDSCAPING.
  
  D. TABULATION TABLE INDICATING HOW THE EXISTING AND
 PROPOSED PLANT MATERIAL COMPLIES WITH ARTICLE XIV.
  
  E. SPECIES, QUANTITY, HEIGHT, SPREAD, SPACING, AND
 LOCATION OF THE EXISTING AND PROPOSED PLANT MATERIAL.
  
  F. STATEMENT THAT ALL LANDSCAPE AREAS WILL BE PROVIDED
 WITH A PERMANENT AUTOMATIC IRRIGATION SYSTEM, INCLUDING
 THE ADJACENT RIGHT-OF-WAY (PLEASE NOTE THAT ANY NEW
 IRRIGATION SHALL BE DONE UNDER A SEPARATE PERMIT).
  
 2. SHEET A1 SHOWS THAT STAIRS AND A WALKWAY ARE BEING
 ADDED TO THE FRONT OF THE HOUSE. PLEASE PROVIDE TWO (2)
 COPIES OF A CURRENT AND ACCURATE SURVEY.
  
 3. PLEASE PROVIDE A SITE PLAN SHOWING THE ADDITION OF
 THE STAIRS AND THE WALKWAY IN CONTEXT WITH THE ENTIRE
 LOT, THE SETBACK BETWEEN THE STAIRS AND ALL ADJACENT
 PROPERTY LINES.
  
 4. PLEASE PROVIDE THE SQUARE FOOTAGE OF IMPERVIOUS
 SURFACE (EXISTING DRIVEWAY PLUS THE NEW WALKWAY) WITHIN
 THE FRONT SETBACK.
  
 5. SHEET A3 INDICATES A CONDENSING UNIT, IS THIS
 EXISTING OR PROPOSED? IF PROPOSED, PLEASE NOTE THE
 DIMENSION BETWEEN THE CONDENSING UNIT AND ADJACENT
 PROPERTY LINES.
 ___________________________________________
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 ___________________________________________
  
 QUESTIONS/COMMENTS, PLEASE CONTACT THE FOLLOWING:
  
 JOHN ROACH, PRINCIPAL PLANNER
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES DEPARTMENT ? PLANNING DIVISION
 401 CLEMATIS STREET - P.O. BOX 3147
 WEST PALM BEACH, FLORIDA 33402
  
 PHONE: 561.822.1448
 FAX: 561.822.1460
  
 EMAIL: [email protected]
  
 WWW.WPB.ORG
  
2013-11-13 15:27:0011/13/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved