| Plan Review Stops For Permit 13110145 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
P |
Date |
2013-11-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-18 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-18 |
Time |
06:29 |
Sent To |
|
|
| Notes |
| 2013-11-18 07:00:17 | BUILDING PROVISO: | | | 1) ADDRESS CORRECTED ON PLANS TO 1741 PALM BEACH LAKES | | | BLVD # E-223 | | | | | | 2) PB OUTLET MALLS: | | | A LETTER FROM THE QUALIFIER OF BOTH THE SHELL | | | CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT | | | CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT | | | PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT | | | CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK | | | HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY | | | WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE | | | DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND | | | NOTARIZED. | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | CONSTRUCTION SERVICES HOME PAGE |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-12-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-10 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-12-10 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-11-25 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-11-25 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-11-25 |
Time |
10:25 |
Sent To |
|
|
| Notes |
| 2013-11-25 11:18:00 | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY | | | SUBMITTAL COMPLIANT WITH FBC-E 103 | | | FBC-E 505.2.2 PROVIDE AUTOMATIC LIGHTING SHUTOFF | | | | | | STEVEN KENNEDY, CBO | | | CHIEF PLANS EXAMINER | | | (561) 805-6710 | | | [email protected] | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2013-11-13 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-11-13 |
Time |
16:45 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-11-13 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2013-11-13 16:45:34 | PERMIT #13110145 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED BY EMAIL ([email protected]) | | | ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND | | | APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT | | | 500 NORTH DIXIE HIGHWAY. | | | | | | ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A | | | LOCK/UNLOCK INDICATOR. | | | | | | EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH | | | SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL | | | OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN | | | HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE | | | SPACED NOT MORE THAN 15 FEET ON CENTER. | | | | | | PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN | | | STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE | | | MAINTAINED AT ALL TIMES. | | | | | | AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY | | | EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL | | | EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED | | | WITH RESPECT TO THEIR DUTIES UNDER THE PLAN. | | | | | | EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED | | | IN THE USE OF PORTABLE FIRE EXTINGUISHERS. | | | | | | SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE | | | FIRE ALARM AND SPRINKLER SYSTEM. | | | | | | WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT | | | SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED | | | AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE | | | MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM | | | SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD | | | INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY | | | BE NEEDED. | | | | | | SUE ELLEN CALDERON | | | FIRE INSPECTOR & INVESTIGATOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-12-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-10 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-12-09 |
Time |
18:59 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-11-26 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-11-26 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-11-05 |
Time |
17:49 |
Sent To |
|
|
| Notes |
| 2013-11-25 11:18:20 | SENT TO EZ | | 2013-11-06 17:50:11 | B13 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
N |
Date |
2013-11-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-23 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-23 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2013-11-23 09:43:28 | IMPACT FEES NOT REQUIRED ON THE BASE BUILDING GROUP "J" | | | CREDIT USE AT PBC. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2013-12-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-10 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-12-10 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-11-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-23 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-23 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2013-11-23 09:56:16 | MECHANICAL PLAN REVIEW | | | PERMIT: 13110145 | | | ADD: 1741 PALM BEACH LAKES # E223 | | | CONT: TBD | | | CONTACT: KARI NEVILLE | | | TEL: (561) 373-3902 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: SAT. NOV. 23/ 2013 | | | ACTION: DENIED | | | | | | 1) PLEASE PROVIDE THE MISSING ENERGY CALCULATIONS. 2010 | | | FBC-ENEREGY 103.1 GENERAL. | | | CONSTRUCTION DOCUMENTS AND OTHER SUPPORTING DATA SHALL | | | BE SUBMITTED IN ONE OR MORE SETS WITH EACH APPLICATION | | | FOR A PERMIT. THE CONSTRUCTION DOCUMENTS SHALL BE | | | PREPARED BY A REGISTERED DESIGN PROFESSIONAL WHERE | | | REQUIRED BY FLORIDA STATUTES. WHERE SPECIAL CONDITIONS | | | EXIST, THE CODE OFFICIAL IS AUTHORIZED TO REQUIRE | | | NECESSARY CONSTRUCTION DOCUMENTS TO BE PREPARED BY A | | | REGISTERED DESIGN PROFESSIONAL. | | | 103.2 INFORMATION ON CONSTRUCTION DOCUMENTS. | | | 103.2.1 CODE DEMONSTRATION FORMS. | | | SEE TABLE 103.2.1. FORM 506 (COMMISISSION APPROVED | | | SOFTWARE PRINTOUT). | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | DEVELOPMENT SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-12-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-10 |
Time |
15:50 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-12-10 |
Time |
15:49 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2013-11-22 |
|
|
Cont ID |
|
| Sent By |
lwagner |
Date |
2013-11-22 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
lwagner |
Date |
2013-11-19 |
Time |
15:23 |
Sent To |
|
|
| Notes |
| 2013-11-22 10:24:40 | FBC 2010 ACCESSIBILITY CODE | | | FBC 2010 PLUMBING REVIEW #1 | | | DENIED: | | | | | | | | | 1. THE COMMON AREA TOILET FACILITIES ARE OVER 500' FROM | | | THE STORE ENTRANCE. PLEASE VERIFY THE PUBLIC ACCESS | | | DISTANCE WITH THE PALM BEACH OUTLET MALL. ALSO THE | | | ROUTE TO THE STORE FACILITIES APPEARS TO BE THROUGH A | | | STORAGE (STOCK) AREA. SHEET A0.01 LISTS THE NON SALES | | | AREA AS A STOCKROOM. THE RESTROOMS WILL BE REQUIRED TO | | | BE OPEN TO PUBLIC ACCESS. | | | | | | 403.3.2 LOCATION OF TOILET FACILITIES IN OCCUPANCIES | | | OTHER THAN COVERED MALLS. | | | IN OCCUPANCIES OTHER THAN COVERED MALL BUILDINGS, THE | | | REQUIRED PUBLIC AND EMPLOYEE TOILET FACILITIES SHALL BE | | | LOCATED NOT MORE THAN ONE STORY ABOVE OR BELOW THE | | | SPACE REQUIRED TO BE PROVIDED WITH TOILET FACILITIES, | | | AND THE PATH OF TRAVEL TO SUCH FACILITIES SHALL NOT | | | EXCEED A DISTANCE OF 500 FEET (152 M). | | | | | | 403.3.1 ACCESS. | | | THE ROUTE TO THE PUBLIC TOILET FACILITIES REQUIRED BY | | | SECTION 403.3 SHALL NOT PASS THROUGH KITCHENS, STORAGE | | | ROOMS OR CLOSETS. ACCESS TO THE REQUIRED FACILITIES | | | SHALL BE FROM WITHIN THE BUILDING OR FROM THE EXTERIOR | | | OF THE BUILDING. ALL ROUTES SHALL COMPLY WITH THE | | | ACCESSIBILITY REQUIREMENTS OF THE FLORIDA BUILDING | | | CODE, ACCESSIBILITY. THE PUBLIC SHALL HAVE ACCESS TO | | | THE REQUIRED TOILET FACILITIES AT ALL TIMES THAT THE | | | BUILDING IS OCCUPIED. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|
|
| Review Stop |
POLICE |
POLICE |
| Rev No |
1 |
Status |
N |
Date |
2013-12-10 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-10 |
Time |
15:49 |
Rev Time |
|
| Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-11-25 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2013-11-25 |
Time |
21:33 |
Rev Time |
0.25 |
| Received By |
eschneid |
Date |
2013-11-25 |
Time |
21:33 |
Sent To |
B |
|
| Notes |
| 2013-11-13 15:20:42 | 11/13/13 |
|
|