| Plan Review Stops For Permit 13101148 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2014-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-03-07 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-03-07 |
Time |
19:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2014-01-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-01-24 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-01-24 |
Time |
13:26 |
Sent To |
|
|
| Notes |
| 2014-01-24 13:26:29 | THIRD BUILDING REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- ORIGINAL COMMENT: | | | SUMMER KITCHEN: PROVIDE COMPLETE MANUFACTURER'S SPECS | | | FOR "BULL ANGUS GRILL" THAT IS DESIGNED TO BE INSTALLED | | | IN A COVERED PORCH AS SHOWN ON PLANS. SEC. M1302.1, | | | M1901.2 AND G2408.1 OF 2010 FBC-RESIDENTIAL. | | | | | | RESPONSE TO SUBMITTAL: | | | SHEET A-2A SUBMITTED IS SHOWING A VENT OPENING IN THE | | | WALL FOR OPTIONAL SUMMER KITCHEN: | | | A) OPENINGS ARE NOT ALLOWED ON THIS WALL. THIS IS A | | | ZERO LOT LINE. SEC. R302.1 OF 2010 FBC-RESIDENTIAL. | | | REVISE PLANS AS REQUIRED. | | | | | | B) PROVIDE BBQ MANUFACTURER'S SPECS AS REQUESTED ON | | | ORIGINAL COMMENT ABOVE OR PROVIDE COMPLETE INFORMATION | | | FOR ALTERNATIVE MATERIALS, DESIGN AND METHODS OF | | | CONSTRUCTION AND EQUIPMENT (SEC. 104.11 OF CITY | | | AMENDMENTS TO FBC) FOR THE BUILDING OFFICIAL REVIEW AND | | | APPROVAL. PLEASE CONTACT ROBERT BROWN (BUILDING | | | OFFICIAL) AT (561)805-6652 FOR REQUIRED INFORMATION TO | | | BE SUBMITTED FOR REVIEW. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2013-12-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-12-31 |
Time |
13:37 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-12-31 |
Time |
13:31 |
Sent To |
|
|
| Notes |
| 2013-12-31 13:32:16 | BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR : | | | *A) 18' WIDE GARAGE DOOR. NOA 12-0228.04 SUBMITTED WAS | | | SUPERSEDED BY MIAMID-DADE. VISIT THE MIAMI-DADE WEBSITE | | | AND DOWNLOAD CURRENT NOA. | | | | | | 2- DESIGNER OF RECORD TO APPROVED ABOVE PRODUCT | | | APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 3- SUMMER KITCHEN: PROVIDE COMPLETE MANUFACTURER'S | | | SPECS FOR "BULL ANGUS GRILL" THAT IS DESIGNED TO BE | | | INSTALLED IN A COVERED PATIO AS SHOWN ON PLANS. SEC. | | | M1302.1, M1901.2 AND G2408.1 OF 2010 FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-12-03 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-12-03 |
Time |
09:33 |
Sent To |
|
|
| Notes |
| 2013-12-03 09:51:20 | NEW SINGLE FAMILY RESIDENCE, BUILDING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- SHEET S-2: REVISE ROOF LOADS. NEED 20PSF ATTIC LIVE | | | LOAD. REQUIRED BY TABLE R301.5. SEE FOOTNOTES "B" AND | | | "G". | | | | | | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | | DCA RULE 9N-3 FOR : | | | A) 18' WIDE GARAGE DOOR. | | | | | | B) WINDOW MULLION. NOA 11-0922.01 SUBMITTED WAS | | | SUPERSEDED BY MIAMI-DADE. | | | | | | C) FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS | | | SUPERSEDED BY MIAMI-DADE. | | | | | | 3- DESIGNER OF RECORD TO APPROVED PRODUCT APPROVALS. | | | SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | 4- SUMMER KITCHEN: PROVIDE COMPLETE MANUFACTURER'S | | | SPECS FOR "BULL ANGUS GRILL" THAT IS DESIGNED TO BE | | | INSTALLED IN A COVERED PATIO AS SHOWN ON PLANS. SEC. | | | M1302.1 OF 2010 FBC-RESIDENTIAL. (THIS APPLIES IF | | | SUMMER KITCHEN OPTION IS INSTALLED). | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2014-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-10 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-10 |
Time |
15:03 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-12-31 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-31 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-12-31 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-11-25 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-11-25 |
Time |
18:14 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-11-25 |
Time |
17:55 |
Sent To |
B |
|
| Notes |
| 2013-11-25 18:19:55 | THE FOLLOWING COMMENTS DO NOT ADDRESS THE ENTIRETY OF | | | THE ELECTRICAL PLAN REVIEW. | | | BOTH SETS OF ELECTRICAL DRAWINGS HAVE A LARGE NUMBER OF | | | LIGHTS WHICH HAVE BEEN CROSS OVER WITH BLACK MARKER, | | | BUT THERE IS NO INDICATION AS TO WHAT ARE THE | | | INTENTIONS OF SUCH. IF YOU PLAN TO ELIMINATE THOSE | | | LIGHTING OUTLETS FROM THE PLANS/HOME, PLEASE INDICATE | | | SO ON THE DRAWINGS. | | | MAKE A NOTE OF COMPLIANCE WITH FBC-ENERGY CONSERVATION | | | SECTION 404.1 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2014-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-10 |
Time |
15:58 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-10 |
Time |
15:58 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2013-12-31 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-31 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-12-31 |
Time |
15:56 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2014-03-10 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2014-03-10 |
Time |
15:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2014-03-04 |
Time |
17:55 |
Sent To |
|
|
| Notes |
| 2014-03-04 17:56:01 | SENT TO J GOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2014-02-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-02-03 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-01-29 |
Time |
07:59 |
Sent To |
|
|
| Notes |
| 2014-02-03 16:05:30 | ENERGY CALCULATIONS AND EQUIPMENT LOAD CALCULATIONS | | | SUBMITTED. JG. | | 2014-01-30 07:59:28 | SENT TO GOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2014-01-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-01-24 |
Time |
13:26 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-01-17 |
Time |
13:02 |
Sent To |
|
|
| Notes |
| 2014-01-17 13:03:01 | TO JG DESK | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-12-31 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-31 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-12-12 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2013-12-19 15:00:18 | RESUBMITTAL SENT TO R1 SHELF FOR REVIEW. JG. | | 2013-12-13 14:20:40 | SENT TO J GOMEZ |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-12-03 |
Time |
13:36 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-10-31 |
Time |
17:43 |
Sent To |
|
|
| Notes |
| 2013-10-31 17:43:29 | INCOMING SENT TO R09 .JW |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
P |
Date |
2013-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-12-03 |
Time |
11:03 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-12-03 |
Time |
11:03 |
Sent To |
|
|
| Notes |
| 2013-12-03 11:04:52 | $8,711.11. MU-2013-22509. JG. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2014-03-07 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-03-07 |
Time |
19:10 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-03-07 |
Time |
19:10 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
F |
Date |
2014-02-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-02-03 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-02-03 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2014-02-03 16:10:55 | CHECKLIST: | | | | | | 1- ENERGY CALCULATIONS AND EQUIPMENT LOAD CALCULATIONS | | | SUBMITTED ARE FOR MODEL 2566. ACCORDING TO PLANS | | | SUBMITTED LOT 93 IS FOR MODEL 2500. REVISE AS REQUIRED | | | TO MATCH. | | | | | | 2- SEE COMMENTS BELOW FROM THIRD REVIEW: | | | | | | | | | THIRD MECHANICAL REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- NEW A/C PLAN SUBMITTED. | | | ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL. | | | REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS | | | REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT | | | APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO | | | MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC. | | | M1307.2.1 OF 2010 FBC-RESIDENTIAL. | | | | | | ***RESPONSE: | | | INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4" | | | CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE | | | LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF | | | THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR | | | EXACT LOCATION AND REVISE DETAIL AS REQUIRED. | | | | | | | | | 2- NEW COMMENT. | | | A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN FOR THIS | | | BUILDING. PROVIDE CORRECT A/C PLAN. SEC. 103.2.2 OF | | | 2010 FBC-ENERGY CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
F |
Date |
2014-01-24 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2014-01-24 |
Time |
13:38 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2014-01-24 |
Time |
13:38 |
Sent To |
|
|
| Notes |
| 2014-01-24 13:39:16 | THIRD MECHANICAL REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- ***ORIGINAL COMMENT: | | | REVISE EQUIPMENT SIZING CALCULATIONS. THEY ARE DONE | | | USING WORST CASE SCENARIO FROM THE ENERGY CALCULATIONS. | | | NEED TO USE THE ACTUAL BUILDING ORIENTATION. SEC. | | | 403.6.1 OF 2010 FBC-ENERGY CONSERVATION. | | | | | | ***RESPONSE: | | | INFORMATION SUBMITTED STATED THAT CALCULATIONS WERE | | | DONE FOR ALL POSSIBLE BUILDING ORIENTATIONS AT THE END | | | OF THE REPORT. CALCULATIONS AND LISTED EQUIPMENT STILL | | | SHOW FRONT DOOR FACING NORTHEAST, WHICH IS NOT THE | | | CORRECT BUILDING ORIENTATION FOR THIS BUILDING. | | | CALCULATIONS AND EQUIPMENT LISTED NEED TO SHOW SPECIFIC | | | BUILDING ORIENTATION AS REQUIRED BY SEC. 403.6.1. | | | IN ADDITION, CALCULATIONS SHOWING THE ROTATIONS AT THE | | | END OF THE REPORT DON'T MATCH THOSE CALCULATIONS SHOWN | | | AT THE BEGINNING OF THE REPORT. | | | | | | | | | | | | 2- NEW A/C PLAN SUBMITTED. | | | ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL. | | | REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS | | | REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT | | | APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO | | | MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC. | | | M1307.2.1 OF 2010 FBC-RESIDENTIAL. | | | | | | ***RESPONSE: | | | INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4" | | | CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE | | | LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF | | | THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR | | | EXACT LOCATION AND REVISE DETAIL AS REQUIRED. | | | | | | | | | 3- NEW COMMENT. | | | A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN FOR THIS | | | BUILDING. PROVIDE CORRECT A/C PLAN. SEC. 103.2.2 OF | | | 2010 FBC-ENERGY CONSERVATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2013-12-31 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-12-31 |
Time |
13:55 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-12-31 |
Time |
13:55 |
Sent To |
|
|
| Notes |
| 2013-12-31 13:56:37 | NEW SINGLE FAMILY RESIDENCE (R3), SECOND MECHANICAL | | | REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- EQUIPMENT SIZING CALCULATIONS ARE DONE USING THE | | | ENERGY CALCULATIONS WORST CASE SCENARIO. FOR THE | | | PURPOSE OF EQUIPMENT SIZING THE CALCULATIONS NEED TO BE | | | DONE BASED ON THE "ACTUAL" BUILDING ORIENTATION AS | | | REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY | | | CONSERVATION. REVISE EQUIPMENT SIZING CALCULATIONS | | | USING THE "ACTUAL" BUILDING ORIENTATION. (REPEAT | | | COMMENT). | | | | | | 2- NEW A/C PLAN SUBMITTED. A) REVISE THE CU MOUNTING | | | DETAIL. REVISE THE NUMBER AND LOCATION OF HURRICANE | | | CLIPS AS REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA | | | PRODUCT APPROVAL FL14239 SPECIFIED ON THE DETAIL. | | | REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF | | | 2010 AND SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- PERSON RESPONSIBLE FOR THE DESIGN TO PROVIDE NAME | | | AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY | | | AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-12-03 |
Time |
13:28 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-12-03 |
Time |
13:28 |
Sent To |
|
|
| Notes |
| 2013-12-03 13:35:39 | NEW SINGLE FAMILY RESIDENCE (R3), MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- EQUIPMENT SIZING CALCULATIONS ARE DONE USING THE | | | ENERGY CALCULATIONS WORST CASE SCENARIO. FOR THE | | | PURPOSE OF EQUIPMENT SIZING THE CALCULATIONS NEED TO BE | | | DONE BASED ON THE "ACTUAL" BUILDING ORIENTATION AS | | | REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY | | | CONSERVATION. REVISE EQUIPMENT SIZING CALCULATIONS | | | USING THE "ACTUAL" BUILDING ORIENTATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
P |
Date |
2013-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-12-03 |
Time |
11:05 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-12-03 |
Time |
11:04 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
R |
ROOF PLAN REVIEW |
| Rev No |
1 |
Status |
P |
Date |
2013-12-03 |
|
|
Cont ID |
|
| Sent By |
jgomez |
Date |
2013-12-03 |
Time |
11:25 |
Rev Time |
0.00 |
| Received By |
jgomez |
Date |
2013-12-03 |
Time |
11:25 |
Sent To |
|
|
| Notes |
| 2013-12-03 11:26:26 | ROOF TILE NOA 11-0510.02 SUBMITTED. JG. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2014-01-07 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2014-01-07 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2014-01-07 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2014-01-07 11:42:33 | 1/7/14 - LANDSCAPING PERMIT (13121183) SUBMITTED AND | | | APPROVED BY ZONING. DK |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2013-12-23 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2013-12-23 |
Time |
15:00 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2013-12-23 |
Time |
14:14 |
Sent To |
|
|
| Notes |
| 2014-01-07 11:40:20 | 1/7/14 - LANDSCAPING PERMIT (13121183) SUBMITTED AND | | | APPROVED BY ZONING. DK | | 2013-12-23 14:58:09 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 12/23/2013 | | | 1. LANDSCAPE PLAN REVIEWED AND NOTATIONS ADDED TO PLAN. | | | PLAN IS READY FOR APPROVAL, HOWEVER, PERMIT APPLICATION | | | FOR LANDSCAPING HAS NOT YET BEEN SUBMITTED. PLEASE | | | SUBMIT PERMIT APPLICATION FOR LANDSCAPING IN ORDER FOR | | | PLANNING AND ZONING TO ISSUE APPROVAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2013-11-14 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2013-11-14 |
Time |
09:53 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2013-11-13 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2013-11-14 09:49:06 | PLANNING AND ZONING COMMENTS: ***FAILED*** | | | | | | 11/14/13 | | | | | | 1. PLEASE CLARIFY ON PLANS THE HEIGHT OF THE PRIVACY | | | WALL NOT UNDER ROOF. MAXIMUM HEIGHT PERMITTED IS 6 | | | FEET. | | | | | | 2. VERIFY SETBACK OF MECHANICAL EQUIPMENT. MECHANICAL | | | EQUIPMENT CANNOT PROTRUDE MORE THAN 4 FEET IN TO A | | | REQUIRED SETBACK AND THE REQUIRED 'NON-ZERO SIDE' SIDE | | | SETBACK IS 8 FEET. | | | | | | 3. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH | | | ARTICLE XIV SHALL BE SUBMITTED. | | | NOTE: ZLDR SEC. 94-442(B)(2)A. - FOR SINGLE-FAMILY | | | DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING, OR FRUIT | | | TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF | | | OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY | | | DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR | | | EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF. | | | PLEASE ADJUST CALCULATIONS ON THE TABLE TO REFLECT | | | REQUIREMENTS OF THE CITY OF WEST PALM BEACH RATHER THAN | | | PALM BEACH COUNTY. ALSO, THE LAYOUT OF THE LANDSCAPE | | | PLOT PLAN IS NOT CONSISTENT WITH THE PLOT PLAN OF THE | | | HOUSE AND DRIVEWAY ON THE SURVEY. THERE DOES NOT APPEAR | | | TO BE ENOUGH SPACE ON THE EAST SIDE OF THE DRIVEWAY FOR | | | TREES ACCORDING TO THE SURVEY. PLEASE REVISE. | | | | | | 4. SHOULD THERE BE ANY EXISTING TREES ON THE PROPERTY | | | THAT NEED TO BE REMOVED OR RELOCATED, A TREE ALTERATION | | | PERMIT THROUGH THE PLANNING DEPT. WILL BE REQUIRED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT: | | | | | | DANIELLE J. KITTREDGE, AICP | | | SENIOR PLANNER | | | PLANNING & ZONING DIVISION | | | PHONE: (561)-822-1443 | | | EMAIL: [email protected] | | | | | 2013-11-13 15:13:57 | 11/13/13 |
|
|