Plan Review Details - Permit 13101148
Plan Review Stops For Permit 13101148
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-03-07 Cont ID  
Sent By jgomez Date 2014-03-07 Time 19:04 Rev Time 0.00
Received By jgomez Date 2014-03-07 Time 19:04 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-01-24 Cont ID  
Sent By jgomez Date 2014-01-24 Time 13:26 Rev Time 0.00
Received By jgomez Date 2014-01-24 Time 13:26 Sent To  
Notes
2014-01-24 13:26:29THIRD BUILDING REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- ORIGINAL COMMENT:
 SUMMER KITCHEN: PROVIDE COMPLETE MANUFACTURER'S SPECS
 FOR "BULL ANGUS GRILL" THAT IS DESIGNED TO BE INSTALLED
 IN A COVERED PORCH AS SHOWN ON PLANS. SEC. M1302.1,
 M1901.2 AND G2408.1 OF 2010 FBC-RESIDENTIAL.
  
 RESPONSE TO SUBMITTAL:
 SHEET A-2A SUBMITTED IS SHOWING A VENT OPENING IN THE
 WALL FOR OPTIONAL SUMMER KITCHEN:
 A) OPENINGS ARE NOT ALLOWED ON THIS WALL. THIS IS A
 ZERO LOT LINE. SEC. R302.1 OF 2010 FBC-RESIDENTIAL.
 REVISE PLANS AS REQUIRED.
  
 B) PROVIDE BBQ MANUFACTURER'S SPECS AS REQUESTED ON
 ORIGINAL COMMENT ABOVE OR PROVIDE COMPLETE INFORMATION
 FOR ALTERNATIVE MATERIALS, DESIGN AND METHODS OF
 CONSTRUCTION AND EQUIPMENT (SEC. 104.11 OF CITY
 AMENDMENTS TO FBC) FOR THE BUILDING OFFICIAL REVIEW AND
 APPROVAL. PLEASE CONTACT ROBERT BROWN (BUILDING
 OFFICIAL) AT (561)805-6652 FOR REQUIRED INFORMATION TO
 BE SUBMITTED FOR REVIEW.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-12-31 Cont ID  
Sent By jgomez Date 2013-12-31 Time 13:37 Rev Time 0.00
Received By jgomez Date 2013-12-31 Time 13:31 Sent To  
Notes
2013-12-31 13:32:16BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR :
 *A) 18' WIDE GARAGE DOOR. NOA 12-0228.04 SUBMITTED WAS
 SUPERSEDED BY MIAMID-DADE. VISIT THE MIAMI-DADE WEBSITE
 AND DOWNLOAD CURRENT NOA.
  
 2- DESIGNER OF RECORD TO APPROVED ABOVE PRODUCT
 APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS.
  
 3- SUMMER KITCHEN: PROVIDE COMPLETE MANUFACTURER'S
 SPECS FOR "BULL ANGUS GRILL" THAT IS DESIGNED TO BE
 INSTALLED IN A COVERED PATIO AS SHOWN ON PLANS. SEC.
 M1302.1, M1901.2 AND G2408.1 OF 2010 FBC-RESIDENTIAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-12-03 Cont ID  
Sent By jgomez Date 2013-12-03 Time 09:33 Rev Time 0.00
Received By jgomez Date 2013-12-03 Time 09:33 Sent To  
Notes
2013-12-03 09:51:20NEW SINGLE FAMILY RESIDENCE, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- SHEET S-2: REVISE ROOF LOADS. NEED 20PSF ATTIC LIVE
 LOAD. REQUIRED BY TABLE R301.5. SEE FOOTNOTES "B" AND
 "G".
  
 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR :
 A) 18' WIDE GARAGE DOOR.
  
 B) WINDOW MULLION. NOA 11-0922.01 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE.
  
 C) FIXED WINDOWS. NOA 11-1110.15 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE.
  
 3- DESIGNER OF RECORD TO APPROVED PRODUCT APPROVALS.
 SEC. 107.3.4.1 CITY AMENDMENTS.
  
 4- SUMMER KITCHEN: PROVIDE COMPLETE MANUFACTURER'S
 SPECS FOR "BULL ANGUS GRILL" THAT IS DESIGNED TO BE
 INSTALLED IN A COVERED PATIO AS SHOWN ON PLANS. SEC.
 M1302.1 OF 2010 FBC-RESIDENTIAL. (THIS APPLIES IF
 SUMMER KITCHEN OPTION IS INSTALLED).
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-03-10 Cont ID  
Sent By rmcdouga Date 2014-03-10 Time 15:03 Rev Time 0.00
Received By rmcdouga Date 2014-03-10 Time 15:03 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-31 Cont ID  
Sent By skennedy Date 2013-12-31 Time 15:56 Rev Time 0.00
Received By skennedy Date 2013-12-31 Time 15:56 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-25 Cont ID  
Sent By albarran Date 2013-11-25 Time 18:14 Rev Time 0.00
Received By albarran Date 2013-11-25 Time 17:55 Sent To B
Notes
2013-11-25 18:19:55THE FOLLOWING COMMENTS DO NOT ADDRESS THE ENTIRETY OF
 THE ELECTRICAL PLAN REVIEW.
 BOTH SETS OF ELECTRICAL DRAWINGS HAVE A LARGE NUMBER OF
 LIGHTS WHICH HAVE BEEN CROSS OVER WITH BLACK MARKER,
 BUT THERE IS NO INDICATION AS TO WHAT ARE THE
 INTENTIONS OF SUCH. IF YOU PLAN TO ELIMINATE THOSE
 LIGHTING OUTLETS FROM THE PLANS/HOME, PLEASE INDICATE
 SO ON THE DRAWINGS.
 MAKE A NOTE OF COMPLIANCE WITH FBC-ENERGY CONSERVATION
 SECTION 404.1

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-03-10 Cont ID  
Sent By rmcdouga Date 2014-03-10 Time 15:58 Rev Time 0.00
Received By rmcdouga Date 2014-03-10 Time 15:58 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-12-31 Cont ID  
Sent By skennedy Date 2013-12-31 Time 15:56 Rev Time 0.00
Received By skennedy Date 2013-12-31 Time 15:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-03-10 Cont ID  
Sent By rmcdouga Date 2014-03-10 Time 15:59 Rev Time 0.00
Received By rmcdouga Date 2014-03-04 Time 17:55 Sent To  
Notes
2014-03-04 17:56:01SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-02-03 Cont ID  
Sent By jgomez Date 2014-02-03 Time 16:04 Rev Time 0.00
Received By jgomez Date 2014-01-29 Time 07:59 Sent To  
Notes
2014-02-03 16:05:30ENERGY CALCULATIONS AND EQUIPMENT LOAD CALCULATIONS
 SUBMITTED. JG.
2014-01-30 07:59:28SENT TO GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-01-24 Cont ID  
Sent By jgomez Date 2014-01-24 Time 13:26 Rev Time 0.00
Received By jgomez Date 2014-01-17 Time 13:02 Sent To  
Notes
2014-01-17 13:03:01TO JG DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-31 Cont ID  
Sent By skennedy Date 2013-12-31 Time 15:57 Rev Time 0.00
Received By skennedy Date 2013-12-12 Time 15:36 Sent To  
Notes
2013-12-19 15:00:18RESUBMITTAL SENT TO R1 SHELF FOR REVIEW. JG.
2013-12-13 14:20:40SENT TO J GOMEZ

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-03 Cont ID  
Sent By jgomez Date 2013-12-03 Time 13:36 Rev Time 0.00
Received By jgomez Date 2013-10-31 Time 17:43 Sent To  
Notes
2013-10-31 17:43:29INCOMING SENT TO R09 .JW

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status P Date 2013-12-03 Cont ID  
Sent By jgomez Date 2013-12-03 Time 11:03 Rev Time 0.00
Received By jgomez Date 2013-12-03 Time 11:03 Sent To  
Notes
2013-12-03 11:04:52$8,711.11. MU-2013-22509. JG.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2014-03-07 Cont ID  
Sent By jgomez Date 2014-03-07 Time 19:10 Rev Time 0.00
Received By jgomez Date 2014-03-07 Time 19:10 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2014-02-03 Cont ID  
Sent By jgomez Date 2014-02-03 Time 16:05 Rev Time 0.00
Received By jgomez Date 2014-02-03 Time 16:05 Sent To  
Notes
2014-02-03 16:10:55CHECKLIST:
  
 1- ENERGY CALCULATIONS AND EQUIPMENT LOAD CALCULATIONS
 SUBMITTED ARE FOR MODEL 2566. ACCORDING TO PLANS
 SUBMITTED LOT 93 IS FOR MODEL 2500. REVISE AS REQUIRED
 TO MATCH.
  
 2- SEE COMMENTS BELOW FROM THIRD REVIEW:
  
  
 THIRD MECHANICAL REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- NEW A/C PLAN SUBMITTED.
 ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL.
 REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS
 REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT
 APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO
 MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC.
 M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4"
 CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE
 LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF
 THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR
 EXACT LOCATION AND REVISE DETAIL AS REQUIRED.
  
  
 2- NEW COMMENT.
 A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN FOR THIS
 BUILDING. PROVIDE CORRECT A/C PLAN. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-01-24 Cont ID  
Sent By jgomez Date 2014-01-24 Time 13:38 Rev Time 0.00
Received By jgomez Date 2014-01-24 Time 13:38 Sent To  
Notes
2014-01-24 13:39:16THIRD MECHANICAL REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- ***ORIGINAL COMMENT:
 REVISE EQUIPMENT SIZING CALCULATIONS. THEY ARE DONE
 USING WORST CASE SCENARIO FROM THE ENERGY CALCULATIONS.
 NEED TO USE THE ACTUAL BUILDING ORIENTATION. SEC.
 403.6.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 ***RESPONSE:
 INFORMATION SUBMITTED STATED THAT CALCULATIONS WERE
 DONE FOR ALL POSSIBLE BUILDING ORIENTATIONS AT THE END
 OF THE REPORT. CALCULATIONS AND LISTED EQUIPMENT STILL
 SHOW FRONT DOOR FACING NORTHEAST, WHICH IS NOT THE
 CORRECT BUILDING ORIENTATION FOR THIS BUILDING.
 CALCULATIONS AND EQUIPMENT LISTED NEED TO SHOW SPECIFIC
 BUILDING ORIENTATION AS REQUIRED BY SEC. 403.6.1.
 IN ADDITION, CALCULATIONS SHOWING THE ROTATIONS AT THE
 END OF THE REPORT DON'T MATCH THOSE CALCULATIONS SHOWN
 AT THE BEGINNING OF THE REPORT.
  
  
  
 2- NEW A/C PLAN SUBMITTED.
 ***ORIGINAL COMMENT: REVISE THE CU MOUNTING DETAIL.
 REVISE THE NUMBER AND LOCATION OF HURRICANE CLIPS AS
 REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA PRODUCT
 APPROVAL FL14239 SPECIFIED ON THE DETAIL. REQUIRED TO
 MEET THE DESIGN PRESSURES OF SEC. R301 OF 2010 AND SEC.
 M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 ***RESPONSE:
 INFORMATION SUBMITTED STATED THAT USING ONLY ONE 2"X4"
 CLIP PER SIDE. IF USING ONLY ONE CLIP, THEN THE
 LOCATION OF THE CLIP HAS TO BE CLOSER TO THE CORNER OF
 THE UNIT NOT IN THE CENTER. SEE PRODUCT APPROVAL FOR
 EXACT LOCATION AND REVISE DETAIL AS REQUIRED.
  
  
 3- NEW COMMENT.
 A/C PLAN SUBMITTED DOESN'T MATCH FLOOR PLAN FOR THIS
 BUILDING. PROVIDE CORRECT A/C PLAN. SEC. 103.2.2 OF
 2010 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-12-31 Cont ID  
Sent By jgomez Date 2013-12-31 Time 13:55 Rev Time 0.00
Received By jgomez Date 2013-12-31 Time 13:55 Sent To  
Notes
2013-12-31 13:56:37NEW SINGLE FAMILY RESIDENCE (R3), SECOND MECHANICAL
 REVIEW CHECKLIST.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS ARE DONE USING THE
 ENERGY CALCULATIONS WORST CASE SCENARIO. FOR THE
 PURPOSE OF EQUIPMENT SIZING THE CALCULATIONS NEED TO BE
 DONE BASED ON THE "ACTUAL" BUILDING ORIENTATION AS
 REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION. REVISE EQUIPMENT SIZING CALCULATIONS
 USING THE "ACTUAL" BUILDING ORIENTATION. (REPEAT
 COMMENT).
  
 2- NEW A/C PLAN SUBMITTED. A) REVISE THE CU MOUNTING
 DETAIL. REVISE THE NUMBER AND LOCATION OF HURRICANE
 CLIPS AS REQUIRED TO MATCH PAGE ONE OF 4 OF FLORIDA
 PRODUCT APPROVAL FL14239 SPECIFIED ON THE DETAIL.
 REQUIRED TO MEET THE DESIGN PRESSURES OF SEC. R301 OF
 2010 AND SEC. M1307.2.1 OF 2010 FBC-RESIDENTIAL.
  
 3- PERSON RESPONSIBLE FOR THE DESIGN TO PROVIDE NAME
 AND SIGNATURE AS REQUIRED BY SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-03 Cont ID  
Sent By jgomez Date 2013-12-03 Time 13:28 Rev Time 0.00
Received By jgomez Date 2013-12-03 Time 13:28 Sent To  
Notes
2013-12-03 13:35:39NEW SINGLE FAMILY RESIDENCE (R3), MECHANICAL REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS ARE DONE USING THE
 ENERGY CALCULATIONS WORST CASE SCENARIO. FOR THE
 PURPOSE OF EQUIPMENT SIZING THE CALCULATIONS NEED TO BE
 DONE BASED ON THE "ACTUAL" BUILDING ORIENTATION AS
 REQUIRED BY SEC. 403.6.1 OF 2010 FBC-ENERGY
 CONSERVATION. REVISE EQUIPMENT SIZING CALCULATIONS
 USING THE "ACTUAL" BUILDING ORIENTATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-12-03 Cont ID  
Sent By jgomez Date 2013-12-03 Time 11:05 Rev Time 0.00
Received By jgomez Date 2013-12-03 Time 11:04 Sent To  
Notes
***NONE***

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2013-12-03 Cont ID  
Sent By jgomez Date 2013-12-03 Time 11:25 Rev Time 0.00
Received By jgomez Date 2013-12-03 Time 11:25 Sent To  
Notes
2013-12-03 11:26:26ROOF TILE NOA 11-0510.02 SUBMITTED. JG.

Review Stop Z ZONING
Rev No 3 Status P Date 2014-01-07 Cont ID  
Sent By dkittred Date 2014-01-07 Time 11:41 Rev Time 0.00
Received By dkittred Date 2014-01-07 Time 11:41 Sent To  
Notes
2014-01-07 11:42:331/7/14 - LANDSCAPING PERMIT (13121183) SUBMITTED AND
 APPROVED BY ZONING. DK

Review Stop Z ZONING
Rev No 2 Status F Date 2013-12-23 Cont ID  
Sent By dkittred Date 2013-12-23 Time 15:00 Rev Time 0.00
Received By dkittred Date 2013-12-23 Time 14:14 Sent To  
Notes
2014-01-07 11:40:201/7/14 - LANDSCAPING PERMIT (13121183) SUBMITTED AND
 APPROVED BY ZONING. DK
2013-12-23 14:58:09PLANNING AND ZONING COMMENTS: ***FAILED***
  
 12/23/2013
 1. LANDSCAPE PLAN REVIEWED AND NOTATIONS ADDED TO PLAN.
 PLAN IS READY FOR APPROVAL, HOWEVER, PERMIT APPLICATION
 FOR LANDSCAPING HAS NOT YET BEEN SUBMITTED. PLEASE
 SUBMIT PERMIT APPLICATION FOR LANDSCAPING IN ORDER FOR
 PLANNING AND ZONING TO ISSUE APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  

Review Stop Z ZONING
Rev No 1 Status F Date 2013-11-14 Cont ID  
Sent By dkittred Date 2013-11-14 Time 09:53 Rev Time 0.00
Received By dkittred Date 2013-11-13 Time 16:40 Sent To  
Notes
2013-11-14 09:49:06PLANNING AND ZONING COMMENTS: ***FAILED***
  
 11/14/13
  
 1. PLEASE CLARIFY ON PLANS THE HEIGHT OF THE PRIVACY
 WALL NOT UNDER ROOF. MAXIMUM HEIGHT PERMITTED IS 6
 FEET.
  
 2. VERIFY SETBACK OF MECHANICAL EQUIPMENT. MECHANICAL
 EQUIPMENT CANNOT PROTRUDE MORE THAN 4 FEET IN TO A
 REQUIRED SETBACK AND THE REQUIRED 'NON-ZERO SIDE' SIDE
 SETBACK IS 8 FEET.
  
 3. A SEPARATE LANDSCAPE PERMIT IN CONFORMANCE WITH
 ARTICLE XIV SHALL BE SUBMITTED.
 NOTE: ZLDR SEC. 94-442(B)(2)A. - FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHADE, FLOWERING, OR FRUIT
 TREE SHALL BE PLANTED FOR EACH 1,200 SQUARE FEET OF
 OPEN SPACE OR PORTION THEREOF. FOR SINGLE-FAMILY
 DWELLING UNITS, AT LEAST ONE SHRUB SHALL BE PLANTED FOR
 EACH 500 SQUARE FEET OF OPEN SPACE OR PORTION THEREOF.
 PLEASE ADJUST CALCULATIONS ON THE TABLE TO REFLECT
 REQUIREMENTS OF THE CITY OF WEST PALM BEACH RATHER THAN
 PALM BEACH COUNTY. ALSO, THE LAYOUT OF THE LANDSCAPE
 PLOT PLAN IS NOT CONSISTENT WITH THE PLOT PLAN OF THE
 HOUSE AND DRIVEWAY ON THE SURVEY. THERE DOES NOT APPEAR
 TO BE ENOUGH SPACE ON THE EAST SIDE OF THE DRIVEWAY FOR
 TREES ACCORDING TO THE SURVEY. PLEASE REVISE.
  
 4. SHOULD THERE BE ANY EXISTING TREES ON THE PROPERTY
 THAT NEED TO BE REMOVED OR RELOCATED, A TREE ALTERATION
 PERMIT THROUGH THE PLANNING DEPT. WILL BE REQUIRED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-11-13 15:13:5711/13/13