Plan Review Details - Permit 13101143
Plan Review Stops For Permit 13101143
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-18 Cont ID  
Sent By albarran Date 2013-11-18 Time 18:31 Rev Time 0.00
Received By albarran Date 2013-11-18 Time 18:30 Sent To I
Notes
2013-11-18 18:34:18THE SCOPE OF THIS WORK IS THE TEMPORARY INSTALLATION OF
 A PORTABLE GENERATOR FOR EMERGENCY BACK UP WHILE THE
 PERMANENT UNIT IS BEING SERVICED.
 ALL WORK WILL BE SUBJECT TO THE FIELD INSPECTORS
 APPROVAL.
  
 SENT TO SH DESK
2013-11-18 18:31:46RECEIVED VIA EMAIL AN EXPLANATION OF THE SCOPE AND THE
 MATERIALS CUT SHEET.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-13 Cont ID  
Sent By albarran Date 2013-11-13 Time 12:09 Rev Time 0.00
Received By albarran Date 2013-11-13 Time 11:55 Sent To I
Notes
2013-11-13 13:25:51THE FOLLOWING CORRECTIONS TO THE SUBMITTED DRAWING
 SHALL BE MADE TO COMPLY WITH MINIMUM CODE REQUIREMENTS.
 !. NOT ENOUGH DETAIL ON SUBMITTED DRAWINGS. NEED TO
 SHOW LOCATION OF ATS
 2. THE CONDUIT AS INDICATED ON THE DRAWINGS EXCEEDS THE
 MAXIMUM ALLOWABLE BENDS. REROUTE THE THE RACEWAY OR
 INSTALL A PULL BOX TO BREAK THE CONTINUOUS PATH.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-14 Cont ID  
Sent By shill Date 2013-11-14 Time 11:06 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
2013-11-01 10:08:44ELECTRIC $5000 & UNDER