Plan Review Details - Permit 13101093
Plan Review Stops For Permit 13101093
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-06 Cont ID  
Sent By jwitmer Date 2014-01-06 Time 16:48 Rev Time 0.00
Received By jwitmer Date 2014-01-06 Time 16:13 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-16 Cont ID  
Sent By jwitmer Date 2013-11-16 Time 10:27 Rev Time 0.00
Received By jwitmer Date 2013-11-16 Time 09:34 Sent To  
Notes
2013-11-16 10:27:28BUILDING PLAN REVIEW
 PERMIT: 13101093
 ADD: 721 VILLAGE BLVD # 107E
 CONT: HIGHLAND CONTRACTORS
 TEL: (561)371- 9997
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 16/ 2013
  
 ACTION: DENIED
  
 1A) SHEET 1.4 A THE LIFE SAFETY SHEET PLEASE PROVIDE
 THE SQUARE FT FOR BOTH THE DINING AREA AND KITCHEN FOR
 THE CALCULATIONS. PLEASE ALSO NOTE THE CORRECT COUNT
 FOR THE KITCHEN SHOULD BE 200 SQ FT PER OCCUPANT 2010
 FBC-B TABLE 1004.1.1.
  
 1B) THE COVERSHEET LIST A HIGHER OCCUPANT LOAD THAN
 FIGURED BY TABLE 1004.1.1. PLEASE PROVIDE AN APPROVED
 AISLE, SEATING OR FIXED EQUIPMENT DIAGRAM
 SUBSTANTIATING ANY INCREASE IN OCCUPANT LOAD SHALL BE
 SUBMITTED. WHERE REQUIRED BY THE BUILDING OFFICIAL,
 SUCH DIAGRAM SHALL BE POSTED. 2010 FBC-B 1004.2.
  
 1C)2010 FBC-B 1004.3 POSTING OF OCCUPANT LOAD. EVERY
 ROOM OR SPACE THAT IS AN ASSEMBLY OCCUPANCY SHALL HAVE
 THE OCCUPANT LOAD OF THE ROOM OR SPACE POSTED IN A
 CONSPICUOUS PLACE, NEAR THE MAIN EXIT OR EXIT ACCESS
 DOORWAY FROM THE ROOM OR SPACE. POSTED SIGNS SHALL BE
 OF AN APPROVED LEGIBLE PERMANENT DESIGN AND SHALL BE
 MAINTAINED BY THE OWNER OR AUTHORIZED AGENT.
  
 2) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B SECTION
 713.6 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 3) SHEET 2.1E SHOWS (2) EXITING SIGNS, THE EXIT SIGN
 LOCATED IN THE REAR WALL OF THE REAR DINING ROOM IS NOT
 CLEAR, IF IT WILL BE VISIBLE THROUGH THE REMAINDER OF
 THE DINING ROOMS BECAUSE OF THE WALLS, DROPPED HEADERS
 & COLUMNS. PLEASE ALSO IDENIFTY ON THE 1.0A ELEVATIONS.
 THE CORRIDOR BEHIND THE REAR DINING ROOM WILL ALSO NEED
 A DIRECTIONAL SIGN DIRECTING THE OCCUPANTS TO THE SIDE
 EXIT.
 2010 FBC-B 1006.3.1 EXITS SHALL BE MARKED BY AN
 APPROVED SIGN READILY VISIBLE FROM ANY DIRECTION OF
 EXIT ACCESS. EVERY EXIT SIGN SHALL BE SUITABLY
 ILLUMINATED BY A RELIABLE LIGHT SOURCE. EXTERNALLY AND
 INTERNALLY ILLUMINATED SIGNS SHALL BE VISIBLE IN BOTH
 NORMAL AND EMERGENCY LIGHTING.
  
 4) 2010 FBC-B 1006.3.4 EXIT STAIR DOOR OR TACTILE
 SIGNAGE. TACTILE SIGNAGE STATING ?EXIT? AND COMPLYING
 WITH ICC/ANSI A117.1, AMERICAN NATIONAL STANDARD FOR
 ACCESSIBLE AND USABLE BUILDINGS AND FACILITIES, SHALL
 BE INSTALLED ADJACENT TO THE LATCH SIDE OF THE DOOR 60
 INCHES (1524 MM) ABOVE THE FINISHED FLOOR TO THE CENTER
 LINE OF THE SIGN.
  
 5) PLANS DO NOT HAVE ANY DETAILS INDICATING COMPLIANCE
 WITH THE 2010 FL ACCESSIBILITY CODE 904.4 SALES AND
 SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
 EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A
 COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A
 REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK
 STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL
 BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION
 WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH
 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR
 GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF
 THE COUNTER.
  
 FIGURE 904.4 (EXCEPTION)
 ALTERATION OF SALES AND SERVICE COUNTERS
 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915
 MM) MINIMUM LENGTH OF COUNTER.
 EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS
 THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER
 SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE
 THE FINISH FLOOR.
 904.4.2 FORWARD APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH
 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A FORWARD APPROACH TO THE COUNTER.
  
 6) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-12 Cont ID  
Sent By albarran Date 2013-12-12 Time 10:14 Rev Time 0.00
Received By albarran Date 2013-12-12 Time 09:21 Sent To M
Notes
2013-12-12 10:17:11RETURNED TO BIN B25

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-01-08 Cont ID  
Sent By lphilmor Date 2014-01-08 Time 11:34 Rev Time 0.00
Received By lphilmor Date 2014-01-08 Time 11:34 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-21 Cont ID  
Sent By wjolin Date 2013-11-21 Time 15:00 Rev Time 0.00
Received By wjolin Date 2013-11-21 Time 13:27 Sent To  
Notes
2013-11-21 15:00:47721 VILLAGE BOULEVARD #107E
 PERMIT #13101093
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT
 DOORS WITH EXIT SIGNS.
  
 GENERAL: TOTAL OCCUPANT LOAD DOES NOT APPEAR TO INCLUDE
 THE BOOTH SEATING CALCULATED AT 1 PER 24-INCHES.
  
 SHEET 2.1E: THERE APPEARS TO BE INSUFFICIENT EMERGENCY
 LIGHTING IN THE KITCHEN AREA AND MAIN SEATING AREA.
 EMERGENCY ILLUMINATION SHALL BE PROVIDED FOR A MINIMUM
 OF 1.5 HOURS IN THE EVENT OF FAILURE OF NORMAL
 LIGHTING. EMERGENCY LIGHTING FACILITIES SHALL BE
 ARRANGED TO PROVIDE INITIAL ILLUMINATION THAT IS NOT
 LESS THAN AN AVERAGE OF 1 FT-CANDLE AND, AT ANY POINT,
 NOT LESS THAN 0.1 FT-CANDLE, MEASURED ALONG THE PATH OF
 EGRESS AT FLOOR LEVEL.
  
 SHEET 3.0M: PROVIDE DUCT SMOKE DETECTORS FOR AIR FLOWS
 ABOVE 2,000 CFM.
  
 GENERAL: PLANS DO NOT INDICATE A FIRE ALARM OR FIRE
 SPRINKLER SCOPE OF WORK.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop G GAS REVIEW
Rev No 1 Status P Date 2013-11-12 Cont ID  
Sent By lwagner Date 2013-11-12 Time 10:49 Rev Time 0.00
Received By lwagner Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-13 Cont ID  
Sent By skennedy Date 2014-01-13 Time 08:52 Rev Time 0.00
Received By skennedy Date 2013-12-23 Time 09:28 Sent To  
Notes
2013-12-26 09:28:38B23
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-14 Cont ID  
Sent By hmoser Date 2013-12-14 Time 09:28 Rev Time 0.00
Received By hmoser Date 2013-10-30 Time 07:46 Sent To  
Notes
2013-10-31 07:47:09B25

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-01-29 Cont ID  
Sent By jwitmer Date 2014-01-29 Time 09:59 Rev Time 0.00
Received By jwitmer Date 2014-01-29 Time 09:59 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status F Date 2014-01-06 Cont ID  
Sent By jwitmer Date 2014-01-06 Time 16:39 Rev Time 0.00
Received By jwitmer Date 2014-01-06 Time 16:38 Sent To  
Notes
2014-01-06 16:39:32BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-11-16 Cont ID  
Sent By jwitmer Date 2013-11-16 Time 09:35 Rev Time 0.00
Received By jwitmer Date 2013-11-16 Time 09:35 Sent To  
Notes
2013-11-16 09:35:28BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-01-07 Cont ID  
Sent By hmoser Date 2014-01-07 Time 09:32 Rev Time 0.00
Received By hmoser Date 2014-01-07 Time 09:32 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-12-14 Cont ID  
Sent By hmoser Date 2013-12-14 Time 09:27 Rev Time 0.00
Received By hmoser Date 2013-12-14 Time 08:34 Sent To  
Notes
2013-12-14 09:27:39PLAN DENIED
 1) CFM ON THE PLAN DO NOT MATCH THE CEILING OUTLET
 SCHEDULE.
 2) PROVIDE FRESH AIR CALCULATIONS PER TABLE 403.3
 VENTILATION RATES
 2010 FBC (M)
 3) REFER TO SECTION 606.2.1 SUPPLY AIR 2010 FBC (M).
 SHOW
 DUCT DETECTORS ON PLAN.
 4) PROVIDE ENERGY CALCULATIONS WITH THE PLAN. PER
 SECTION
 603.2 DUCT SIZING 2010 FBC (M)
 5) REFER TO SECTION 503.2.4.4 SHUTOFF DAMPER CONTROLS
 2010 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676
2013-12-12 10:16:38RETURNED TO BIN B25
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-11-12 Cont ID  
Sent By lwagner Date 2013-11-12 Time 10:50 Rev Time 0.00
Received By lwagner Date 2013-11-12 Time 10:22 Sent To  
Notes
***NONE***