| Notes |
| 2013-11-13 18:49:15 | THIS PERMIT IS APPROVED WITH THE FOLLOWING PROVISIOS: | | | | | | THE SERVICE FEEDERS ARE NOT ADEQUATE FOR THE | | | APPLICATION. | | | 1. TABLE 310.15(B)(6) ALLOWS A #4 CU CONDUCTOR FOR 100 | | | AMP DWELLING SERVICE, THEREFORE, AS PER TABLE 310.16 | | | YOU SHALL PROVIDE A #3 CU CONDUCTOR FOR THIS | | | APPLICATION. | | | 2. TABLE 310.13(A) RESTRICTS THHN INSULATED CONDUCTORS | | | TO DRY OR DAMP LOCATIONS ONLY | | | 3. SECTION 300.5(B) CONSIDERS THE INSIDE OF AN | | | UNDERGROUND RACEWAY AS A WET LOCATION, THEREFORE YOU | | | SHALL USE THWN LISTED CONDUCTORS. | | | 4. SECTION 310.50(B) REQUIRES THAT YOU USE SCH. 80 PVC. | | | 5. SECTION 310.50(E) REQUIRES THAT IT BE SEALED. | | | 6. YOU FAIL TO ADDRESS THE GROUNDING FOR THIS SERVICE | | | WHICH SHALL MEET THE REQUIREMENTS OF SECTION 250.56 | | | | | | THE ABOVE MENTIONED CONDITIONS ARE PLACED ON THE | | | COMPLETED INSTALLATION FOR INSPECTION. | | | |
|
|