Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-13 Cont ID  
Sent By albarran Date 2013-11-13 Time 18:21 Rev Time 0.00
Received By albarran Date 2013-11-13 Time 17:56 Sent To I
Notes
2013-11-13 18:49:15THIS PERMIT IS APPROVED WITH THE FOLLOWING PROVISIOS:
  
 THE SERVICE FEEDERS ARE NOT ADEQUATE FOR THE
 APPLICATION.
 1. TABLE 310.15(B)(6) ALLOWS A #4 CU CONDUCTOR FOR 100
 AMP DWELLING SERVICE, THEREFORE, AS PER TABLE 310.16
 YOU SHALL PROVIDE A #3 CU CONDUCTOR FOR THIS
 APPLICATION.
 2. TABLE 310.13(A) RESTRICTS THHN INSULATED CONDUCTORS
 TO DRY OR DAMP LOCATIONS ONLY
 3. SECTION 300.5(B) CONSIDERS THE INSIDE OF AN
 UNDERGROUND RACEWAY AS A WET LOCATION, THEREFORE YOU
 SHALL USE THWN LISTED CONDUCTORS.
 4. SECTION 310.50(B) REQUIRES THAT YOU USE SCH. 80 PVC.
 5. SECTION 310.50(E) REQUIRES THAT IT BE SEALED.
 6. YOU FAIL TO ADDRESS THE GROUNDING FOR THIS SERVICE
 WHICH SHALL MEET THE REQUIREMENTS OF SECTION 250.56
  
 THE ABOVE MENTIONED CONDITIONS ARE PLACED ON THE
 COMPLETED INSTALLATION FOR INSPECTION.
  