Plan Review Details - Permit 13101059
Plan Review Stops For Permit 13101059
Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-30 Cont ID  
Sent By albarran Date 2013-10-30 Time 15:36 Rev Time 0.00
Received By albarran Date 2013-10-30 Time 14:43 Sent To PC
Notes
2013-10-30 15:40:44THOUGH NEC 550.33(B) REQUIRES THAT THE MINIMUM
 SERVICE/FEEDERS FOR THE LOTS BE A MINIMUM OF 100 AMP,
 THIS CAN BE CONSIDERED A LEVEL 1 ALTERATION AND UNDER
 THE FBC-EXISTING SECTION 608.1.1 EXISTING WIRING &
 EQUIPMENT UNDERGOING REPAIR CAN BE REPLACED WITH LIKE
 MATERIAL.
2013-10-30 14:47:01PER EC TO SUSAN, THE PREMISES ARE W/O POWER. I CALLED
 THE EC TO CONFIRM THE STATUS BUT WAS UNABLE TO MAKE
 CONTACT. I LEFT A MESSAGE FOR A RETURN PHONE CALL.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved