Plan Review Details - Permit 13101054
Plan Review Stops For Permit 13101054
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-11-12 Cont ID  
Sent By jwitmer Date 2013-11-12 Time 08:26 Rev Time 0.00
Received By jwitmer Date 2013-11-12 Time 07:32 Sent To  
Notes
2013-11-12 08:26:50BUILDING PLAN REVIEW
 PERMIT: 13101054
 ADD: 1781 PALM BEACH LAKES BLVD # W243
 CONT: TO BE DETERMINED
 TEL: (561) 373-3902 CONTACT KARI NEVILLE
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 DATE: TUESDAY NOV 12/ 2013
 ACTION: DENIED
  
 BUILDING PROVISO:
 A REVISION IS REQUIRED!!!
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
 1) PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) A REVISION IS REQUIRED, SHEET A3.1 THE ACCESSIBLE
 DRESSING ROOM NEEDS TO COMPLY WITH THE 2010 FL
 ACCESSIBILITY CODE SECTION 803.3 DOOR SWING. DOORS
 SHALL NOT SWING INTO THE ROOM UNLESS A CLEAR FLOOR OR
 GROUND SPACE COMPLYING WITH 305.3 IS PROVIDED BEYOND
 THE ARC OF THE DOOR SWING.
  
 3) A REVISION IS REQUIRED, SHEET A3.1 THE ACCESSIBLE
 DRESSING ROOM NEEDS TO COMPLY WITH THE 2010 FL
 ACCESSIBILITY CODE SECTION 803.4 BENCHES. A BENCH
 COMPLYING WITH 903 SHALL BE PROVIDED WITHIN THE ROOM.
 903.4 BACK SUPPORT.
 THE BENCH SHALL PROVIDE FOR BACK SUPPORT OR SHALL BE
 AFFIXED TO A WALL. BACK SUPPORT SHALL BE 42 INCHES
 (1065 MM) LONG MINIMUM AND SHALL EXTEND FROM A POINT 2
 INCHES (51 MM) MAXIMUM ABOVE THE SEAT SURFACE TO A
 POINT 18 INCHES (455 MM) MINIMUM ABOVE THE SEAT
 SURFACE. BACK SUPPORT SHALL BE 21/2 INCHES (64 MM)
 MAXIMUM FROM THE REAR EDGE OF THE SEAT MEASURED
 HORIZONTALLY.
  
 4) PLANS DO NOT HAVE DETAILS FOR THE CASH WRAP AND
 COMPLIANCE WITH THE 2010 FL ACCESSIBILITY CODE SECTION
 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A
 COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A
 REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK
 STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL
 BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION
 WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH
 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR
 GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF
 THE COUNTER.
 FIGURE 904.4 (EXCEPTION)
 ALTERATION OF SALES AND SERVICE COUNTERS
  
 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915
 MM) MINIMUM LENGTH OF COUNTER.
  
 EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS
 THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER
 SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE
 THE FINISH FLOOR.
  
 904.4.2 FORWARD APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH
 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A FORWARD APPROACH TO THE COUNTER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-19 Cont ID  
Sent By skennedy Date 2013-11-19 Time 17:25 Rev Time 0.00
Received By skennedy Date 2013-11-19 Time 17:22 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By scaldero Date 2013-10-31 Time 18:03 Rev Time 0.00
Received By scaldero Date 2013-10-31 Time 18:03 Sent To  
Notes
2013-10-31 18:08:23PERMIT #13101054
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-22 Cont ID  
Sent By shill Date 2013-11-22 Time 17:40 Rev Time 0.00
Received By shill Date 2013-10-30 Time 11:46 Sent To  
Notes
2013-11-19 17:26:22SENT TO EZ
2013-10-30 11:46:29B17

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-18 Cont ID  
Sent By jwitmer Date 2013-11-18 Time 12:50 Rev Time 0.00
Received By jwitmer Date 2013-11-18 Time 12:24 Sent To  
Notes
2013-11-18 12:50:09MECHANICAL PLAN REVIEW
 PERMIT: 13101054
 ADD: 1781 PALM BEACH LAKES # W243
 CONT: TO BE DETERMINED
 TEL: (561)373-3902 CONTACT KARI NEVELLE
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON./ NOV. 18/ 2013
  
 ACTION: MECHANICAL PROVISO
 MECHANICAL APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) 2010 FLORIDA BUILDING CODE-MECHANICAL 606.2.1 SUPPLY
 AIR SYSTEMS.
 SMOKE DETECTORS SHALL BE INSTALLED IN SUPPLY AIR
 SYSTEMS WITH A DESIGN CAPACITY GREATER THAN 2,000 CFM
 (0.9 M3/S) IN THE SUPPLY AIR DUCT.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-11-14 Cont ID  
Sent By lwagner Date 2013-11-14 Time 10:25 Rev Time 0.00
Received By lwagner Date 2013-11-14 Time 09:59 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status N Date 2013-11-22 Cont ID  
Sent By shill Date 2013-11-22 Time 17:40 Rev Time 0.00
Received By shill Date 2013-11-22 Time 17:40 Sent To  
Notes
2013-11-22 17:40:21CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY?S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THE
 MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED HAS
 A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: ?THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS.?
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A ?SAFE? CLIMATE
 WITHIN A BUILT ENVIRONMENT ? RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS ?QUALITY OF LIFE.? A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER?S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS AND ANTI-THEFT TAGS
 ON MERCHANDISE.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
 (14) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
 (15) INTERIOR SHELVING AND DISPLAYS SHOULD BE NO HIGHER
 THAN FIVE FEET, EVEN LESS IN FRONT OF WINDOWS.
  
  
 OFFICER K. TUCKER-CARSILLO
 CRIME PREVENTION UNIT
 WEST PALM BEACH POLICE DEPT
 600 BANYAN BLVD
 WEST PALM BEACH, FL 33401
 (561) 822-1620 OFFICE
 (561) 822-1648 FAX
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-11-22 Cont ID  
Sent By eschneid Date 2013-11-22 Time 15:52 Rev Time 0.25
Received By eschneid Date 2013-11-22 Time 15:52 Sent To B
Notes
2013-10-30 15:47:2410/29/13