Plan Review Details - Permit 13100993
Plan Review Stops For Permit 13100993
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-12-22 Cont ID  
Sent By shill Date 2013-12-22 Time 10:50 Rev Time 0.00
Received By shill Date 2013-12-22 Time 10:50 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-11-18 Cont ID  
Sent By shill Date 2013-11-18 Time 13:46 Rev Time 0.00
Received By shill Date 2013-11-18 Time 13:46 Sent To  
Notes
2013-11-18 14:10:17****CORRECTIONS****
 REVIEW OF RESUBS DATED 11/8 AND 11/13
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 A PHOTOGRAPH OF A FLOOR PLAN WAS PROVIDED. IT APPEARS
 THAT EMERGENCY MEANS OF ESCAPE AND RESCUE IS NOT
 APPLICABLE. PLEASE PROVIDE TWO LEGIBLE PLANS WITH THE
 INFORMATION CONTAINED ON THE PHOTOGRAPH, FBC 107.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 BASED ON THE PHOTOGRAPHS PROVIDED, THE AFFECTED WINDOWS
 ARE A PART OF THE BUILDING ENVELOPE. IMPACT PROTECTION
 IS REQUIRED AS THESE WINDOWS ARE NOT INDOORS BUT A PART
 OF THE OUTDOOR BUILDING ENVELOPE AND ARE SUBJECT TO
 PRESSURES AS WELL AS DEBRIS.
  
 3. PROVIDE BUILDING HEIGHT SO DESIGN PRESSURE
 REQUIREMENTS CAN BE DETERMINED FBC 1609.
  
 NOT ADDRESSED.
  
 4. ADDRESS ON PLAN IS INCORRECT. PLEASE REVISE. (1800
 VISTA DELLAGO)
  
 NOT ADDRESSED.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-30 Cont ID  
Sent By shill Date 2013-10-30 Time 19:32 Rev Time 0.00
Received By shill Date 2013-10-30 Time 19:32 Sent To  
Notes
2013-10-30 19:34:36****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS. NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 604.1. THE CLEAR OPENING
 CANNOT BE REDUCED BY MORE THAN 5%.
  
 2. IMPACT PROTECTION REQUIRED,FBC1609.1.4, FBC R
 301.2.1.2. PROVIDE PRODUCT APPROVALS AND, IF SHUTTERS
 ARE USED, COMPLETE THE SAMPLE INSTALLATION SCHEDULE
 (AVAILABLE IN THE LOBBY AND AT HTTP://WWW.CITYOFWPB.COM
 /CONSTRUCTION/PDF/SCHEDULE_FOR_INSTALLATION.PDF)
  
 3. PROVIDE BUILDING HEIGHT SO DESIGN PRESSURE
 REQUIREMENTS CAN BE DETERMINED FBC 1609.
  
 4. ADDRESS ON PLAN IS INCORRECT. PLEASE REVISE. (1800
 VISTA DELLAGO)
  

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2013-12-22 Cont ID  
Sent By shill Date 2013-12-22 Time 10:50 Rev Time 0.00
Received By shill Date 2013-12-07 Time 07:59 Sent To  
Notes
2013-12-07 08:00:01SENT TO S HILL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-11-18 Cont ID  
Sent By shill Date 2013-11-18 Time 14:15 Rev Time 0.00
Received By shill Date 2013-11-13 Time 14:10 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-18 Cont ID  
Sent By shill Date 2013-11-18 Time 14:15 Rev Time 0.00
Received By shill Date 2013-11-08 Time 13:46 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-30 Cont ID  
Sent By shill Date 2013-10-30 Time 19:34 Rev Time  
Received By shill Date 2013-10-28 Time   Sent To  
Notes
2013-10-28 14:48:20<5000 BLDG