Plan Review Details - Permit 13100987
Plan Review Stops For Permit 13100987
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-11-05 Cont ID  
Sent By jwitmer Date 2013-11-05 Time 12:33 Rev Time 0.00
Received By jwitmer Date 2013-11-05 Time 12:00 Sent To  
Notes
2013-11-05 12:29:22BUILDING PLAN REVIEW
 PERMIT: 13100987
 ADD: 1741 PALM BEACH LAKES # E241
 CONT: TO BE DETERMINED
 TEL: (561)
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. NOV. 05/ 2013
 ACTION: BUILDING PROVISO
  
 PB OUTLET MALLS:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-13 Cont ID  
Sent By albarran Date 2013-11-13 Time 16:23 Rev Time 0.00
Received By albarran Date 2013-11-13 Time 15:26 Sent To I
Notes
2013-11-13 16:24:27SENT TO SH DESK

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By scaldero Date 2013-10-31 Time 17:34 Rev Time 0.00
Received By scaldero Date 2013-10-31 Time 17:22 Sent To  
Notes
2013-10-31 17:34:30PERMIT # 13100987
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ****PROVISO*****
 1) THE ADDRESS PROVIDED ON THE PLANS DOES NOT MATCH THE
 ADDRESS PROVIDED ON THE PERMIT APPLICATION. 1801 IS THE
 ENTIRE SITE. PLAN NEEDS TO REFLECT CORRECT ADDRESS -
 1741 PALM BEACH LAKES BLVD.
  
 2) SHEET 2: ADDTIONAL EXIT SIGNS NEEDED AS MARKED ON
 PLAN.
  
 3) SHEET E1.1: EMERGENCY LIGHTING NEEDED IN STOREROOM
 AND NEAR RESTROOM.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-20 Cont ID  
Sent By skennedy Date 2013-11-20 Time 14:06 Rev Time 0.00
Received By skennedy Date 2013-11-19 Time 12:42 Sent To  
Notes
2013-11-20 14:08:21APPPROVED, UP FRONT IN PBOM
2013-11-19 14:07:36SENT TO PBOM DENIED PLANS.
2013-11-19 12:43:08INCOMING SENT TO S KENNEDY OFFICE. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-15 Cont ID  
Sent By skennedy Date 2013-11-15 Time 16:18 Rev Time 0.00
Received By skennedy Date 2013-10-28 Time 16:32 Sent To  
Notes
2013-10-29 16:33:02SENT TO B11 SHELF FOR REVIEW. JG.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-11-20 Cont ID  
Sent By skennedy Date 2013-11-20 Time 14:06 Rev Time 0.00
Received By skennedy Date 2013-11-20 Time 14:06 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-11-20 Cont ID  
Sent By skennedy Date 2013-11-19 Time 14:00 Rev Time 0.00
Received By skennedy Date 2013-11-19 Time 13:50 Sent To  
Notes
2013-11-19 14:06:31THE SUBMITTED ENERGY FORMS ARE IDENTIFIED AS "COM CHECK
 SOFTWARE VERSION 3.9.2." THIS IS NOT FLORIDA BUILDING
 COMMISSION APPROVED SOFTWARE AS ALLOWED BY FBC-ENERGY
 CONSERVATION SECTION 103.2.1, T-103.2.1. PLEASE
 RESUBMIT WITH APPROVED FORMS.
  
 STEVEN KENNEDY
 561 805 6710
 [email protected]
  

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-11-15 Cont ID  
Sent By skennedy Date 2013-11-15 Time 16:08 Rev Time 0.00
Received By skennedy Date 2013-11-15 Time 16:08 Sent To  
Notes
2013-11-15 16:11:06PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 FBC 107.3.5.1.6 ENERGY CALCULATIONS - PROVIDE AN ENERGY
 SUBMITTAL COMPLIANT WITH FBC-E 103
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-11-04 Cont ID  
Sent By lwagner Date 2013-11-04 Time 09:33 Rev Time 0.00
Received By lwagner Date 2013-11-04 Time 09:21 Sent To  
Notes
***NONE***

Review Stop POLICE POLICE
Rev No 1 Status N Date 2013-11-15 Cont ID  
Sent By skennedy Date 2013-11-15 Time 16:18 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-11-15 Cont ID  
Sent By eschneid Date 2013-11-15 Time 11:42 Rev Time 0.25
Received By eschneid Date 2013-11-15 Time 11:42 Sent To  
Notes
2013-10-30 15:46:5910/29/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved