| 2013-10-26 12:23:16 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SHOW COMPLIANCE WITH FBC R311.2 EGRESS DOOR. |
| | AT LEAST ONE EGRESS DOOR SHALL BE PROVIDED FOR EACH |
| | DWELLING UNIT. THE EGRESS DOOR SHALL BE SIDE-HINGED, |
| | AND SHALL PROVIDE A MINIMUM CLEAR WIDTH OF 32 INCHES |
| | (813 MM) WHEN MEASURED BETWEEN THE FACE OF THE DOOR AND |
| | THE STOP, WITH THE DOOR OPEN 90 DEGREES (1.57 RAD). THE |
| | MINIMUM CLEAR HEIGHT OF THE DOOR OPENING SHALL NOT BE |
| | LESS THAN 78 INCHES (1981 MM) IN HEIGHT MEASURED FROM |
| | THE TOP OF THE THRESHOLD TO THE BOTTOM OF THE STOP. |
| | OTHER DOORS SHALL NOT BE REQUIRED TO COMPLY WITH THESE |
| | MINIMUM DIMENSIONS. EGRESS DOORS SHALL BE READILY |
| | OPENABLE FROM INSIDE THE DWELLING WITHOUT THE USE OF A |
| | KEY OR SPECIAL KNOWLEDGE OR EFFORT. |
| | |
| | 2) SHOW COMPLIANCE WITH FBC R703.6.3 |
| | WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED TO LATH |
| | OVER FRAME CONSTRUCTION, MEASURES SHALL BE TAKEN TO |
| | PREVENT BONDING BETWEEN THE CEMENT PLASTER AND THE |
| | WATER-RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED |
| | BETWEEN THE WATER-RESISTIVE BARRIER AND THE CEMENT |
| | PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING: |
| | |
| | 1. TWO LAYERS OF AN APPROVED WATER-RESISTANT BARRIER |
| | MATERIAL; OR |
| | |
| | 2. ONE LAYER OF AN APPROVED WATER-RESISTANT BARRIER |
| | OVER AN APPROVED PLASTIC HOUSE WRAP; OR |
| | |
| | 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN |
| | ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS. |
| | |
| | 3) SHOW COMPLIANCE WITH FBC R806.1 VENTILATION |
| | REQUIRED. |
| | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE |
| | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF |
| | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE |
| | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE |
| | ENTRANCE OF RAIN. EXCEPTION: ATTIC SPACES, DESIGNED BY |
| | A PROFESSIONAL ENGINEER OR ARCHITECT LICENSED TO |
| | PRACTICE IN THE STATE, DESIGNED TO ELIMINATE THE ATTIC |
| | VENTING.( SEE FBC R806.4) |
| | |
| | 4) FBC ENERGY CONSERVATION 101.4.3 ADDITIONS, |
| | ALTERATIONS, RENOVATIONS OR REPAIRS. |
| | ADDITIONS, ALTERATIONS, RENOVATIONS OR REPAIRS TO AN |
| | EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| | SHALL CONFORM TO THE PROVISIONS OF TABLE 101.4.1 OF |
| | THIS CODE AS THEY RELATE TO NEW CONSTRUCTION WITHOUT |
| | REQUIRING THE UNALTERED PORTION(S) OF THE EXISTING |
| | BUILDING OR BUILDING SYSTEM TO COMPLY WITH THIS CODE. |
| | TABLE 101.4.1 |
| | NONEXEMPT EXISTING BUILDINGS |
| | RENOVATIONS |
| | MINIMUM CODE ENVELOPE, EQUIPMENT AND LIGHTING |
| | EFFICIENCY LEVELS SHALL BE MET FOR COMPONENTS BEING |
| | CHANGED. |
| | ENVELOPE: SECTION 402 OR 502 |
| | EQUIPMENT: SECTION 403 OR 503, 504 |
| | LIGHTING: SECTION 404 OR 505 |
| | |
| | SHOW COMPLIANCE WITH SECTION 401.2 AND TABLE 402.1 FOR |
| | REQUIRED R-30 CEILING INSULATION AND R-13 UNDER FLOOR |
| | CAVITY INSULATION. |
| | |
| | 5) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED |
| | BY DCA RULE 9N-3 FOR THE EXTERIOR IMPACT RATED WINDOWS |
| | AND DOORS, THE ROOF COVERING MATERIAL FOR THE NEW FLAT |
| | ROOF AND THE SIMPSON HANGERS AND OTHER CONNECTORS. |
| | |
| | 6) COMPLY WITH CITY AMENDMENT 107.3.4.1 WHICH REQUIRES |
| | THE PRODUCT APPROVALS TO BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD FOR THE PROJECT. |
| | |
| | 7) ON SHEET S1, AN RAS 117 CALCULATION FOR ENHANCED |
| | FASTENING OF THE BASE SHEET FOR THE FIRESTONE FLAT |
| | ROOFING MATERIAL WITH NOA NO. 05-0830.10. THIS PRODUCT |
| | APPROVAL HAS EXPIRED AND IS NOT ACCEPTABLE. ALSO, AN |
| | OLDER EDITION ON ASCE 7 IS SPECIFIED. PLEASE REVISE FOR |
| | THE CURRENT ROOFING PRODUCT APPROVAL. |
| | |
| | 8) PLEASE CLARIFY THE WALL SECTION NOTE ON SHEET S1 |
| | THAT REFERENCES .625 " ROUGH SAWN STUCCO. IF YOU ARE |
| | REFERRING TO A HARDI-BOARD TYPE CEMENT PANEL, SUBMIT |
| | TWO COPIES OF THE PRODUCT APPROVALS FOR IT. |
| | |
| | 9) PLEASE PROVIDE A RESPONSE LETTER WITH THE RESUMITTAL |
| | INDICATING HOW THE REVIEW COMMENTS WERE ADDRESSED. THIS |
| | WILL HELP EXPEDITE REVIEW TIME. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |