Plan Review Details - Permit 13100930
Plan Review Stops For Permit 13100930
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-01-16 Cont ID  
Sent By rbrown Date 2014-01-16 Time 18:58 Rev Time 0.00
Received By rbrown Date 2014-01-16 Time 18:58 Sent To  
Notes
2014-01-16 19:07:02SEE SEPARATE REVIEW DATED 12/13/13 ALSO. THIS REVIEW IS
 FOR FOLDING DOORS ONLY.
  
 FOLDING DOOR RATIONAL ANALYSIS FOR INCREASED DOOR
 HEIGHT REVIEWED. NO OBJECTIONS. FIELD VERIFY MULTIPOINT
 LOCKING AT 'SLIDING CORNER POST" FOR L-SHAPED DOOR
 CONFIGURATION.
  
 END OF REVIEW
 TELEPHONE: (561) 805 6652 ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-21 Cont ID  
Sent By rmcdouga Date 2014-01-21 Time 13:36 Rev Time 0.00
Received By rmcdouga Date 2013-12-13 Time 17:58 Sent To  
Notes
2014-01-21 13:37:59SEE REVIEW NOTES FOR EXTERIOR FOLDING DOOR SYSTEM
 REQUIRING : FIELD VERIFY MULTI-POINT LOCKING SYSTEM AT
 "SLIDING CORNER POST" FOR THE L-SHAPED DOOR
 CONFIGURATION.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-01 Cont ID  
Sent By rmcdouga Date 2013-11-01 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2013-10-31 Time 17:45 Sent To  
Notes
2013-10-31 17:46:372010 FBC
  
 REVISIONS
  
 1) THE REVISED PRODUCT APPROVALS FOR THE FRENCH DOORS,
 THE FIXED WINDOWS AND THE GARAGE DOOR ARE OK.
  
 2) THE PRODUCT APPROVALS FOR THE METAL ROOF WERE
 APPROVED UNDER A PREVIOUS REVISION AND ARE NOT REQUIRED
 TO BE SUBMITTED AGAIN.
  
 3) IN ORDER TO PROPERLY REVIEW THE PRODUCT APPROVALS
 FOR THE WINDOWS AND DOORS, THE WINDOW AND DOOR
 SCHEDULES ON SHEET A1.1 NEED TO BE REVISED TO SPECIFY
 THE CORRECT TYPES, SIZES AND THE LOCATIONS OF THE
 WINDOWS AND DOORS. PRODUCT APPROVALS WERE SUBMITTED FOR
 CASEMENT AND HORIZONTAL SLIDING WINDOWS. A PRODUCT
 APPROVAL WAS SUBMITTED FOR GLAZED FRENCH DOORS.
 HOWEVER, NO PRODUCT APPROVALS HAVE BEEN SUBMITTED FOR
 THE SOLID CORE FIBERGLASS DOORS ( NOS. 2 AND 7 IN THE
 SCHEDULE). CITY AMENDMENTS 107.2.1, FBCR 301.2.1 AND
 DCA RULE 9N-3
  
 4) THE REQUIRED OPENING PRESSURES LISTED IN THE
 SCHEDULE, STILL APPEAR TO BE A LITTLE LOW. PLEASE
 REVIEW TO SEE THAT PRESSURES ARE FOR 170 MPH VULT / 132
 VASD, EXPOSURE C WITH A 20 FT MEAN ROOF HEIGHT. FBC
 R301.2.1
  
 5) SPECIFY THE MULLION DIMENSIONS AND THICKNESS AND
 INDICATE THE MULLION SPAN AND OPENING SIZE FOR EACH
 ASSEMBLY BY CIRCLING THESE ITEMS ON THE MULLION PRODUCT
 APPROVAL OR SUBMIT A DETAIL THAT PROVIDES THIS
 INFORMATION. FBC R301.2.1
  
 6) PLEASE SUBMIT TWO SETS OF A KEY PLAN AND AN
 INSTALLATION SCHEDULE THAT INDICATE WHERE AND HOW THE
 NAUTILUS ROLLING SHUTTER SYSTEM WILL BE INSTALLED.
 SPECIFY THE REQUIRED PRESSURES FOR THE OPENINGS, THE
 OPENING SIZES, THE SLAT SPAN, THE SUBSTRATE, THE EDGE
 DISTANCE, THE ANCHOR TYPES, ANCHOR SPACING, MULLION
 SPANS, STORM BAR SPANS AND ALL OTHER PERTINENT
 INFORMATION FROM THE PRODUCT APPROVAL DRAWINGS THAT IS
 REQUIRED TO PROPERLY INSTALL THE SYSTEM. FBC CITY
 AMENDMENTS 107.2.1 AND FBC R301.2.1.2
  
 7) THE ENGINEER'S REPORT THAT WAS SUBMITTED FOR THE
 CUSTOM FOLDING EXTERIOR DOOR SYSTEM IS INCOMPLETE.
 SUBMIT TWO COPIES OF THE REFERENCED TEST REPORT
 NCTL-3846-1 AND ANY OTHER REPORTS, PRODUCT APPROVALS,
 DOCUMENTS OR CALCULATIONS THAT MAY BE REQUIRED TO SHOW
 THAT THE CUSTOM DOOR ASSEMBLIES WHEN INSTALLED IN THE
 SPECIFIED CONFIGURATIONS ARE EQUAL TO THE TESTED
 ASSEMBLIES. THE BUILDING OFFICIAL WILL REVIEW THE
 DOCUMENTS AND ENGINEERING TO DETERMINE IF THE DOORS
 WILL COMPLY WITH SECTION R612.83 OF THE FLORIDA
 BUILDING CODE.
  
 WHEN YOU RESUBMIT THE REVISIONS, PLEASE SUBMIT A
 RESPONSE LETTER INDICATING HOW THE COMMENTS HAVE BEEN
 ADDRESSED. USE THE REVISION NUMBER ON THE RESUBMITTAL
 FORM. THANKS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-21 Cont ID  
Sent By rmcdouga Date 2014-01-21 Time 13:40 Rev Time 0.00
Received By rmcdouga Date 2013-12-09 Time 18:24 Sent To  
Notes
2013-12-09 18:23:50SENT TO RMCDOUGAL DESK

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-01 Cont ID  
Sent By rmcdouga Date 2013-11-01 Time 15:34 Rev Time 0.00
Received By rmcdouga Date 2013-10-25 Time 15:03 Sent To  
Notes
2013-10-25 15:04:06SENT TO R. MCDOUGALS' DESK. JW