Plan Review Details - Permit 13100921
Plan Review Stops For Permit 13100921
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-09 Cont ID  
Sent By rmcdouga Date 2013-11-09 Time 12:00 Rev Time 0.00
Received By rmcdouga Date 2013-11-09 Time 10:08 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-09 Cont ID  
Sent By rmcdouga Date 2013-10-30 Time 07:23 Rev Time 0.00
Received By rmcdouga Date 2013-10-29 Time 18:26 Sent To  
Notes
2013-10-30 07:33:31REVISED SHEETS A-1, A-2, A-5 AND A-6 ARE APPROVED AS
 RED-LINED.
  
 THE PRODUCT APPROVAL THAT WAS SUBMITTED FOR STEEL
 STRUCTURAL ROOF PANEL (NOA NO. 08-0827.20) IS DENIED.
 THE DESIGNER OF RECORD IS REQUIRED TO REVIEW AND
 APPROVE THE PRODUCT APPROVAL IN WRITING. THIS PRODUCT
 IS DESIGNED AND TESTED TO BE INSTALLED OVER A METAL
 FRAME ROOF AS A STRUCTURAL COMPONENT OF THE MAIN WIND
 FORCE RESISTING SYSTEM, RATHER THAN CLADDING. THE PLANS
 INDICATE THAT THIS STRUCTURE HAS WOOD TRUSSES COVERED
 WITH A PLYWOOD DECK. SINCE IT WILL NOT BE INSTALLED PER
 THE MANUFACTURER'S INSTALLATION INSTRUCTIONS, IF YOU
 WISH TO USE THIS PRODUCT YOU WILL NEED TO SUBMIT IT AS
 ALLOWED BY CITY AMENDMENT 104.11 ALTERNATIVE
 MATERIALS,DESIGN AND METHODS OF CONSTRUCTION FOR THE
 BUILDING OFFICIALS APPROVAL. THE FASTENER SIZE,TYPE,
 SPACING, SPANS AND ROW SPACING WILL NEED TO BE
 SPECIFIED AND SHOWN TO BE COMPLIANT WITH THE APPLICABLE
 CODE. (2007 FBC W/2009 REVISIONS)

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-09 Cont ID  
Sent By rmcdouga Date 2013-11-09 Time 12:00 Rev Time 0.00
Received By rmcdouga Date 2013-11-09 Time 10:08 Sent To  
Notes
2013-11-09 12:04:11 
  
 RED-LINED PLANS
2013-11-07 16:41:40NEW SHEETS SUBMITTED. JG.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-30 Cont ID  
Sent By rmcdouga Date 2013-10-30 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2013-10-30 Time 08:33 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 2 Status N Date 2013-11-09 Cont ID  
Sent By rmcdouga Date 2013-11-09 Time 12:02 Rev Time 0.00
Received By rmcdouga Date 2013-11-09 Time 12:03 Sent To  
Notes
2013-11-09 12:03:20METAL ROOF WAS APPROVED ON PREVIOUS REVIEW.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-10-24 Cont ID  
Sent By fmittner Date 2013-10-24 Time 16:30 Rev Time 0.00
Received By fmittner Date 2013-10-24 Time 16:30 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-09 Cont ID  
Sent By rmcdouga Date 2013-11-09 Time 12:03 Rev Time 0.00
Received By rmcdouga Date 2013-11-07 Time 16:39 Sent To  
Notes
2013-11-07 16:40:35SENT TO ZONING FOR HISTORICAL REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-30 Cont ID  
Sent By rmcdouga Date 2013-10-30 Time 08:33 Rev Time 0.00
Received By rmcdouga Date 2013-10-24 Time 18:21 Sent To  
Notes
2013-10-24 18:22:08SENT R MCDOUGAL

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-10-30 Cont ID  
Sent By rmcdouga Date 2013-10-30 Time 06:52 Rev Time 0.00
Received By rmcdouga Date 2013-10-30 Time 06:52 Sent To  
Notes
2013-10-30 07:00:07NO REVISED MECHANICAL PLANS WERE SUBMITTED.

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-11-09 Cont ID  
Sent By rmcdouga Date 2013-11-09 Time 12:01 Rev Time 0.00
Received By rmcdouga Date 2013-11-09 Time 10:07 Sent To  
Notes
2013-11-09 12:02:30APPROVED WITH EXCEPTION. RED-LINED PLANS.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-10-29 Cont ID  
Sent By rmcdouga Date 2013-10-29 Time 19:33 Rev Time 0.00
Received By rmcdouga Date 2013-10-29 Time 18:26 Sent To  
Notes
2013-10-29 19:34:162007 FBC WITH 2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE PLUMBING RISER DIAGRAM ON REVISED SHEET E-1 DOES
 NOT MATCH THE FLOOR PLAN. THE MASTER BATH HAS A SINGLE
 BOWL VANITY, A SHOWER IS SHOWN AT THE 1/2 BATH AND THE
 KITCHEN SINK IS LABELED AS A VANITY. PLEASE CORRECT.
 CITY AMENDMENTS 107.2.1
  
 2) THE SHOWER AND TUB IN THE MASTER BATH AND THE
 WATERCLOSET AND TUB IN THE FULL BATH ARE NOT PROPERLY
 VENTED. P3108.2 VENT CONNECTIONS. THE DRY VENT
 CONNECTION TO THE WET VENT SHALL BE AN INDIVIDUAL VENT
 OR COMMON VENT TO THE LAVATORY, BIDET, SHOWER OR
 BATHTUB. IN VERTICAL WET VENT SYSTEMS, THE MOST
 UPSTREAM FIXTURE DRAIN CONNECTION SHALL BE A DRY-VENTED
 FIXTURE DRAIN CONNECTION. IN HORIZONTAL WET-VENT
 SYSTEMS, NOT MORE THAN ONE WET-VENTED FIXTURE DRAIN
 SHALL DISCHARGE UPSTREAM OF THE DRY-VENTED FIXTURE
 DRAIN CONNECTION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 1 Status P Date 2013-10-24 Cont ID  
Sent By fmittner Date 2013-10-24 Time 16:29 Rev Time 0.00
Received By fmittner Date 2013-10-24 Time 16:29 Sent To  
Notes
***NONE***