| 2013-11-06 14:32:30 | 313 DATURA STREET |
| | PERMIT #13100881 |
| | MASTER #13050713 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | GENERAL |
| | - PROVIDE LOCKING KNOX CAPS ON FIRE DEPARTMENT |
| | CONNECTION. |
| | |
| | - FIRE SPRINKLER SYSTEM SHALL BE MONITORED BY AN |
| | APPROVED SUPERVISING STATION IN ACCORDANCE WITH NFPA |
| | 72. |
| | |
| | - SPRINKLER PROTECTION WILL BE REQUIRED ON THE FIRST |
| | AND SECOND FLOOR OF THE ENCLOSED STAIR BECAUSE THE |
| | STAIR SHAFT IS DISCONTINUOUS TO THE THIRD FLOOR. |
| | |
| | 1ST FLOOR |
| | - PROVIDE SPRINKLER PROTECTION BELOW STAIR #1 IF |
| | PROTECTION DOES NOT ALREADY EXIST. |
| | |
| | - SPRINKLER BRANCH LINES ARE PERMITTED TO SUPPLY |
| | SPRINKLERS IN ELECTRICAL ROOMS; HOWEVER, BRACHLINES |
| | SHALL NOT BE ROUTED THROUGH (IN AND OUT) ELECTRICAL |
| | ROOMS. SEE ELECTRICAL ROOM #109 & #114. |
| | |
| | 2ND FLOOR |
| | - PROVIDE SPRINKLER PROTECTION IN ELEVATOR MACHINE ROOM |
| | #216. |
| | |
| | NOTE: SPRINKLERS IN STOARGE SPACE #100 INDICATED AS |
| | "NOT IN CONTRACT" NIC - |
| | PER NFPA 25 SECTION 5.3.1.1.1, WHERE SPRINKLERS HAVE |
| | BEEN IN SERVICE FOR 50 YEARS, THEY SHALL BE REPLACED OR |
| | REPRESENTATIVE SAMPLES FROM ONE OR MORE SAMPLE AREAS |
| | SHALL BE TESTED. TEST PROCEDURES SHALL BE REPEATED AT |
| | 10-YEAR INTERVALS. WHERE REQUIRED BY THIS SECTION, |
| | SAMPLE SPRINKLERS SHALL BE SUBMITTED TO A RECOGNIZED |
| | TESTING LABORATORY ACCEPTABLE TO THE AUTHORITY HAVING |
| | JURISDICTION FOR FIELD SERVICE TESTING. |
| | |