Plan Review Details - Permit 13100847
Plan Review Stops For Permit 13100847
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-04 Cont ID  
Sent By jwitmer Date 2013-12-04 Time 07:33 Rev Time 0.00
Received By jwitmer Date 2013-12-04 Time 06:59 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-11-04 Cont ID  
Sent By jwitmer Date 2013-11-04 Time 09:26 Rev Time 0.00
Received By jwitmer Date 2013-11-04 Time 08:49 Sent To  
Notes
2013-11-04 09:16:51BUILDING PLAN REVIEW
 PERMIT: 13100847
 ADD: 871 VILLAGE BLVD # 601
 CONT: PAGE CONTRACTING
 TEL: (954)868-7561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY NOV. 04/ 2013
 ACTION: BUILDING PROVISOS:
  
 1) SHEET A2.00 THE DESIGNER INDICATES TTHE USE OF 1
 HOUR FIRE RATED TENANT SEPERATION WALLS, PLEASE PROVIDE
 COMPLIANCE WITH THE FOLLOWING :
 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 2) SHEET A8.02 THE PLANS SHOW A ELEVATION VIEW OF THE
 CASH WRAP BUT NO DIMENSIONS, PLEASE COMPLY WITH: 2010
 FL ACESSIBILITY CODE 904.4 SALES AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
 904.4.1 PARALLEL APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 36 INCHES (915
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 ABOVE THE FINISH FLOOR SHALL BE PROVIDED. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A PARALLEL APPROACH ADJACENT TO THE 36 INCH (915
 MM) MINIMUM LENGTH OF COUNTER.
  
 EXCEPTION: WHERE THE PROVIDED COUNTER SURFACE IS LESS
 THAN 36 INCHES (915 MM) LONG, THE ENTIRE COUNTER
 SURFACE SHALL BE 36 INCHES (915 MM) HIGH MAXIMUM ABOVE
 THE FINISH FLOOR.
  
 904.4.2 FORWARD APPROACH.
 A PORTION OF THE COUNTER SURFACE THAT IS 30 INCHES (760
 MM) LONG MINIMUM AND 36 INCHES (915 MM) HIGH MAXIMUM
 SHALL BE PROVIDED. KNEE AND TOE SPACE COMPLYING WITH
 306 SHALL BE PROVIDED UNDER THE COUNTER. A CLEAR FLOOR
 OR GROUND SPACE COMPLYING WITH 305 SHALL BE POSITIONED
 FOR A FORWARD APPROACH TO THE COUNTER.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-20 Cont ID  
Sent By skennedy Date 2013-12-20 Time 16:54 Rev Time 0.00
Received By skennedy Date 2013-12-20 Time 16:53 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-14 Cont ID  
Sent By albarran Date 2013-11-14 Time 19:23 Rev Time 0.00
Received By albarran Date 2013-11-14 Time 19:11 Sent To  
Notes
2013-11-14 19:25:12RETURNED TO BIN FOR FIRE REVIEW
2013-11-14 19:24:43THE SUBMITTED DRAWINGS FAIL TO MEET THE REQUIREMENTS OF
 THE 2010 FBC-ENERGY CONSERVATION

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-11-19 Cont ID  
Sent By scaldero Date 2013-11-19 Time 14:36 Rev Time 0.00
Received By scaldero Date 2013-11-19 Time 14:29 Sent To  
Notes
2013-11-19 14:38:05PERMIT # 13100847
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVISOS:
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-20 Cont ID  
Sent By skennedy Date 2013-12-20 Time 16:54 Rev Time 0.00
Received By skennedy Date 2013-11-22 Time 09:49 Sent To  
Notes
2013-11-25 09:58:30B12
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-25 Cont ID  
Sent By shill Date 2013-11-19 Time 09:49 Rev Time 0.00
Received By shill Date 2013-10-23 Time 17:32 Sent To  
Notes
2013-10-25 17:32:24B06

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By hmoser Date 2013-11-05 Time 10:44 Sent To  
Notes
2013-11-05 11:35:48PASS PROVISO
 REFER TO SECTION 503.2.4.4 SHUT OFF B DAMPER CONTROLS.
 ( FOR FRESH AIR ) FLORIDA ENERGY CODE
 PLAN REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-12-04 Cont ID  
Sent By jwitmer Date 2013-12-04 Time 07:41 Rev Time 0.00
Received By jwitmer Date 2013-12-04 Time 07:33 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By lwagner Date 2013-10-28 Time 13:02 Rev Time 0.00
Received By lwagner Date 2013-10-28 Time 12:34 Sent To  
Notes
2013-10-28 12:53:56FBC 2010 ACCESSIBILITY CODE
 FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. BUSINESS/ MERCANTILE OCCUPANCIES WITH OVER 15
 OCCUPANTS REQUIRE A HIGH/LO DRINKING FOUNTAIN.
 PLUMBING TABLE 403.1 (E) (F)
 FBC ACCESSIBILITY CODE 2010 211.2 MINIMUM NUMBER. NO
 FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-11-22 Cont ID  
Sent By avann Date 2013-11-22 Time 14:59 Rev Time 0.00
Received By ajones Date 2013-11-22 Time 14:59 Sent To  
Notes
2013-10-30 15:30:0110/29/13