Plan Review Details - Permit 13100775
Plan Review Stops For Permit 13100775
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-27 Cont ID  
Sent By jwitmer Date 2013-11-27 Time 09:42 Rev Time 0.00
Received By jwitmer Date 2013-11-27 Time 07:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-07 Cont ID  
Sent By jwitmer Date 2013-11-07 Time 12:26 Rev Time 0.00
Received By jwitmer Date 2013-11-05 Time 14:58 Sent To  
Notes
2013-11-07 12:16:32BUILDING PLAN REVIEW
 PERMIT: 13100775
 ADD: 7432 S DIXIE HWY
 CONT: LANTANA
 TEL: (561)312-3600
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: THURSDAY NOV. 07/2013
 ACTION: DENIED
  
 1) COVERSHEET CODE INFORMATION:
 1A) PLANS LIST THIS AS A BUSINESS OCCUPANCY, PLEASE
 REVIEW 2010 FBC-B 303.1.1
 RESTAURANTS AND DRINKING ESTABLISHMENTS WITH AN
 OCCUPANT LOAD OF LESS THAN 50 PERSONS SHALL BE
 CLASSIFIED AS GROUP M, MERCANTILE. 303.1 RESTARAUNTS
 WITH 50 OR MORE OCCUPANTS ARE A A-2 OCCUPANCY.
  
 1B) THE CODE INFORMATION PROVIDES A OCCUPANT LOAD OF 49
 OCCUPANTS FOR THE SEATING AREA ONLY THERE IS 1040 SQ FT
 OF KITCHEN AREA NOT ATTRIBUTED FOR, 1040/ 200= AN
 ADDITIONAL 6 OCCUPANTS OR TOTAL OCCUPANT LOAD OF 55.
  
 2) 2010 FBC-B TABLE 1015.1 WILL REQUIRE 2 MEANS OF
 EGRESS.
  
 3) THE REQUIRED 2 MEANS OF EGRESS WILL BE REQUIRED TO
 BE 1/2 OF THE OVERALL DIAGONAL DISTANCE OF THE TENANT
 SPACE APART. 1015.2.1 TWO EXITS OR EXIT ACCESS
 DOORWAYS.
 WHERE TWO EXITS OR EXIT ACCESS DOORWAYS ARE REQUIRED
 FROM ANY PORTION OF THE EXIT ACCESS, THE EXIT DOORS OR
 EXIT ACCESS DOORWAYS SHALL BE PLACED A DISTANCE APART
 EQUAL TO NOT LESS THAN ONE-HALF OF THE LENGTH OF THE
 MAXIMUM OVERALL DIAGONAL DIMENSION OF THE BUILDING OR
 AREA TO BE SERVED MEASURED IN A STRAIGHT LINE BETWEEN
 EXIT DOORS OR EXIT ACCESS DOORWAYS.
  
 4) PANIC HARDWARE REQUIRED. 1008.1.10 PANIC AND FIRE
 EXIT HARDWARE.
 DOORS SERVING A GROUP H OCCUPANCY AND DOORS SERVING
 ROOMS OR SPACES WITH AN OCCUPANT LOAD OF 50 OR MORE IN
 A GROUP A OR E OCCUPANCY SHALL NOT BE PROVIDED WITH A
 LATCH OR LOCK UNLESS IT IS PANIC HARDWARE OR FIRE EXIT
 HARDWARE.
  
 5) SINCE THE OCCUPANT LOAD IS 50 OR MORE CREATING AN A2
 OCCUPANCY PLEASE REVIEW FBC-B TABLE 508.4. BETWEEN AN
 ASSEMBLY OCCUPANCY AND EITHER BUSINESS OR MERCANTILE A
 2 HOUR FIRE SEPERATION IS REQUIRED.
  
 6) 2010 FBC-B 713.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-20 Cont ID  
Sent By skennedy Date 2013-11-20 Time 09:49 Rev Time 0.00
Received By skennedy Date 2013-11-20 Time 09:49 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-11-27 Cont ID  
Sent By lphilmor Date 2013-11-27 Time 13:39 Rev Time 0.00
Received By lphilmor Date 2013-11-27 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-13 Cont ID  
Sent By lphilmor Date 2013-11-13 Time 15:32 Rev Time 0.00
Received By lphilmor Date 2013-11-13 Time 15:06 Sent To  
Notes
2013-11-13 15:32:504732 S. DIXIE HWY
 PERMIT # 13100775
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 1. PLAN INDICATES THAT THE OCCUPANCY IS BUSINESS.
 RESTAURANTS WITH AN OCCUPANT LOAD OF LESS THAN 50 SHALL
 BE CLASSIFIED AS MERCANTILE. RESTAURANTS WITH OCCUPANT
 LOADS OF MORE THAN 50 SHALL BE CLASSIFIED AS ASSEMBLY.
 2. OCCUPANT LOAD STATED ON PLANS DOES NOT APPEAR TO
 ACCOUNT FOR KITCHEN AREA AND OFFICE. AT 50 OR MORE
 PERSONS, TWO MEANS OF EGRESS ARE REQUIRED.
 3. MEANS OF EGRESS SHALL BE CALCULATED AT 1/2 OF THE
 OVERALL DIAGONAL OF SPACE AS THE BUILDING DOES NOT HAVE
 A SPRINKLER SYSTEM.
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-02 Cont ID  
Sent By lwagner Date 2013-12-02 Time 07:35 Rev Time 0.00
Received By lwagner Date 2013-11-22 Time 17:31 Sent To  
Notes
2013-11-22 17:32:15C22

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-20 Cont ID  
Sent By skennedy Date 2013-11-20 Time 09:59 Rev Time 0.00
Received By skennedy Date 2013-10-22 Time 08:58 Sent To  
Notes
2013-10-23 08:58:52SENT TO C11 SHELF FOR REVIEW. JG.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2013-11-27 Cont ID  
Sent By jwitmer Date 2013-11-27 Time 09:42 Rev Time 0.00
Received By jwitmer Date 2013-11-27 Time 09:42 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-11-20 Cont ID  
Sent By skennedy Date 2013-11-20 Time 09:26 Rev Time 0.00
Received By skennedy Date 2013-11-20 Time 09:26 Sent To  
Notes
2013-11-20 09:26:52SEE NOTE #7 OF BUIOLDING PLAN REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-20 Cont ID  
Sent By skennedy Date 2013-11-20 Time 09:59 Rev Time 0.00
Received By skennedy Date 2013-11-20 Time 09:59 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-12-02 Cont ID  
Sent By lwagner Date 2013-12-02 Time 07:35 Rev Time 0.00
Received By lwagner Date 2013-12-02 Time 07:03 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-11-14 Cont ID  
Sent By lwagner Date 2013-11-14 Time 11:01 Rev Time 0.00
Received By lwagner Date 2013-11-14 Time 10:44 Sent To  
Notes
2013-11-14 11:01:42FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 PLEASE INCLUDE THE HAND SINK THAT IS NEAR THE MOP SINK
 ON THE SANITARY AND WATER DRAWINGS.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status N Date 2013-10-30 Cont ID  
Sent By ajones Date 2013-10-30 Time 14:48 Rev Time 0.00
Received By ajones Date 2013-10-30 Time 14:48 Sent To  
Notes
***NONE***