Plan Review Details - Permit 13100605
Plan Review Stops For Permit 13100605
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-11-25 Cont ID  
Sent By shill Date 2013-11-25 Time 11:23 Rev Time 0.00
Received By shill Date 2013-11-25 Time 11:23 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-11-19 Cont ID  
Sent By shill Date 2013-11-19 Time 09:11 Rev Time 0.00
Received By shill Date 2013-11-18 Time 17:33 Sent To FIRE
Notes
2013-11-18 17:42:09****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 IT APPEARS ENGINEER IS ELECTING TO USE FBC 2010
 EXISTING BUILDING 303.1, PRESCRIPTIVE COMPLIANCE
 METHODS).
  
 THEREFORE, ALL COMMENTS WILL REFER TO FBC 2010 PER FBC
 2010 EXISTING BUILDING, ALTERATIONS SHALL COMPLY WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING CODE,
 BUILDING.
  
 SEE FBC 704.3 REGARDING PROTECTION OF THE PRIMARY
 STRUCTURAL FRAME OTHER THAN COLUMNS. ENCASEMENT IS
 REQUIRED, PLEASE NOTE EXCEPTION. IF USING THE
 EXCEPTION, NOTE ON THE PLAN.
  
 EVEN WITH THE EXCEPTION, THE PROPOSED ALTERATION DOES
 NOT MAINTAIN ENCASEMENT AS THE PROPOSED ALTERATION
 PENETRATES THE FIRE RATED ASSEMBLY. ADDITIONALLY, THE
 PROPOSED ALTERATION IS NOT CONSISTENT WITH THE UL
 ASSEMBLY REFERENCED. NOTE THAT ENCASEMENT OF STRUCTURAL
 MEMBERS IN FBC 704 DOES NOT INCLUDE PROVISIONS FOR
 PENETRATIONS (UNLIKE FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS).
  
 PLEASE FEEL FREE TO CONTACT ME TO DISCUSS.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-19 Cont ID  
Sent By shill Date 2013-10-19 Time 08:28 Rev Time 0.00
Received By shill Date 2013-10-19 Time 08:28 Sent To FIRE
Notes
2013-10-19 08:36:00****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. THIS BUILDING WAS CONSTRUCTED AS A FBC 2004 TYPE VA
 WHICH REQUIRES 1 HOUR FOR ROOF FRAMING. IT IS LIKELY
 THAT THE CEILING DRYWALL NOTED ON SK-02 "A" IS A PART
 OF THE RATED ASSEMBLY.
  
 SEE FBC 704 AND REVISE PLAN TO SHOW COMPLIANCE. IF
 EXCEPTIONS ARE USED, PLEASE NOTE ON PLAN. SEE ALSO FBC
 2010 EXISTING BUILDING 503.
  
 AN ATTEMPT WAS MADE TO LOCATE THE FIRE RATED ASSEMBLY
 FOR THIS AREA; HOWEVER, DUE TO PLAN SIZE, I WAS UNABLE
 TO LOCATE QUICKLY. IF YOU WISH TO OBTAIN A SET OF
 PLANS, PLEASE SUBMIT A RECORDS RESEARCH REQUEST TO
 [email protected] OR [email protected]
  
 2. REVISE PLAN TO INCLUDE COMPLIANCE METHOD FOR
 ALTERATION, SEE FBC 2010 EXISTING BUILDING 101.5.
 COMPLIANCE METHOD NOT CLEAR SO CODES REFERENCED MAY NOT
 BE CORRECT.

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By albarran Date 2013-10-28 Time 11:24 Rev Time 0.00
Received By albarran Date 2013-10-28 Time 11:17 Sent To I
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-22 Cont ID  
Sent By lphilmor Date 2013-10-22 Time 09:54 Rev Time 0.00
Received By lphilmor Date 2013-10-22 Time 09:54 Sent To E
Notes
2013-10-22 09:56:231611 WORTHINGTON ROAD
 PERMIT #13100605
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE ADDRESS PROVIDED ON THE PLANS DOES NOT MATCH THE
 ADDRESS PROVIDED ON THE PERMIT APPLICATION
  
 SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE
 INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER
 SYSTEM AND/OR FIRE ALARM SYSTEM.
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-25 Cont ID  
Sent By shill Date 2013-11-25 Time 11:23 Rev Time 0.00
Received By shill Date 2013-11-13 Time 08:57 Sent To  
Notes
2013-11-13 08:58:10INCOMING SENT TOSAMANTHAS' DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-28 Cont ID  
Sent By jlmitch Date 2013-10-28 Time 17:48 Rev Time 0.00
Received By jlmitch Date 2013-10-18 Time 17:29 Sent To  
Notes
2013-10-18 17:29:28TO SH DESK
  