Plan Review Details - Permit 13100594
Plan Review Stops For Permit 13100594
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-04-08 Cont ID  
Sent By jwitmer Date 2014-04-08 Time 10:06 Rev Time 0.00
Received By jwitmer Date 2014-04-08 Time 09:44 Sent To  
Notes
2014-04-08 10:06:204/08/2014
 ROOFING PRODUCT APPROVAL SUBMITTED:
  
 NOA: 13-0129.20
 JOHN MANSVILLE MODIFIED BITUMEN ROOFING SYSTEMS OVER
 CONCRETE DECK.
 PAGE 39 OF 40 TO BE INSTALLED
 MAXIMUM DESIGN PRESSURE OF -275, VASD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
2014-03-27 19:29:48RETURNED TO BIN "B29"

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-02 Cont ID  
Sent By mricard Date 2013-11-02 Time 08:04 Rev Time 0.00
Received By jwitmer Date 2013-11-01 Time 13:13 Sent To  
Notes
2013-11-02 07:20:29BUILDING PLAN REVIEW
 PERMIT: 13100594
 ADD: 2727 GEORGIA AVE
 CONT: ROYAL BUILDERS
 TEL: (561) 798-0901
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. NOV. 02/ 2013
 ACTION: DENIED
  
 1) SHEET C1. UNDER THE HEADING DESIGN CRITERIA THE
 DESIGNER LIST THE OCCUPANCY, AND BUILDING TYPE, THE
 PERMIT APPLICATION UNDERTHE DESCIPTION OF WORK WROTE
 EXISTING DAYCRE RENOVATIONS. THE DESIGNER NEEDS TO PICK
 UNDER THE 2010 FL EXISTING BUILDING CODE WHICH WHICH
 COMPLIANCE METHOD WAS USED INDEVELOPING THIS PLAN. FOR
 THIS REVIEW I WILL COMPLETE MY REVIEW USING THE WORK
 AREA METHOD, LEVEL II.
 101.5 COMPLIANCE METHODS.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1
 THROUGH 101.5.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER.
  
 EXCEPTION: SUBJECT TO THE APPROVAL OF THE CODE
 OFFICIAL, ALTERATIONS COMPLYING WITH THE LAWS IN
 EXISTENCE AT THE TIME THE BUILDING OR THE AFFECTED
 PORTION OF THE BUILDING WAS BUILT SHALL BE CONSIDERED
 IN COMPLIANCE WITH THE PROVISIONS OF THIS CODE UNLESS
 THE BUILDING IS UNDERGOING MORE THAN A LIMITED
 STRUCTURAL ALTERATION AS DEFINED IN SECTION 807.4.3.
 NEW STRUCTURAL MEMBERS ADDED AS PART OF THE ALTERATION
 SHALL COMPLY WITH THE FLORIDA BUILDING CODE, BUILDING.
 ALTERATIONS OF EXISTING BUILDINGS IN FLOOD HAZARD AREAS
 SHALL COMPLY WITH SECTION 601.3.
  
 101.5.1 PRESCRIPTIVE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS AND CHANGES OF
 OCCUPANCY COMPLYING WITH CHAPTER 3 OF THIS CODE IN
 BUILDINGS COMPLYING WITH THE FLORIDA FIRE PREVENTION
 CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
  
 101.5.2 WORK AREA COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTERS 4 THROUGH 12 OF THIS CODE
 SHALL BE CONSIDERED IN COMPLIANCE WITH THE PROVISIONS
 OF THIS CODE.
  
 101.5.3 PERFORMANCE COMPLIANCE METHOD.
 REPAIRS, ALTERATIONS, ADDITIONS, CHANGES IN OCCUPANCY
 AND RELOCATED BUILDINGS COMPLYING WITH CHAPTER 13 OF
 THIS CODE SHALL BE CONSIDERED IN COMPLIANCE WITH THE
 PROVISIONS OF THIS CODE.
  
 2) 2010 FL EXST BLDG CODE MEANS OF EGRESS EXCEPTION #
 2. MEANS OF EGRESS CONFORMING TO THE REQUIREMENTS OF
 THE FLORIDA BUILDING CODE, BUILDING AND THE FLORIDA
 FIRE PREVENTION CODE UNDER WHICH THE BUILDING WAS
 CONSTRUCTED SHALL BE CONSIDERED COMPLIANT MEANS OF
 EGRESS IF, IN THE OPINION OF THE CODE OFFICIAL, THEY DO
 NOT CONSTITUTE A DISTINCT HAZARD TO LIFE.
 SHEET A-1 THE EXISTING WHAT APPEARS TO BE FENCES WITH
 GATES, THERE DOES NOT APPEAR TO BE ANY WORK TO BE
 COMPLETED ON THESE ITEMS, BUT AS STATED ABOVE IF IN THE
 OPINION THEY DO NOT CONSTITUTE A DISTINCT HAZARD TO
 LIFE, IT WOULD APPEAR TO BE A ISSUE SINCE THEY SWING
 IN. THE SECOND QUESTION IS ARE THESE GATES LOCKED, IF
 SO HOW ARE THEY RELEASE IN CASE OF AN EMERGENCY.
  
 2010 EXIST BLDG CODE 705.4.2 DOOR SWING. IN THE WORK
 AREA AND IN THE EGRESS PATH FROM ANY WORK AREA TO THE
 EXIT DISCHARGE, ALL EGRESS DOORS SERVING AN OCCUPANT
 LOAD GREATER THAN 50 SHALL SWING IN THE DIRECTION OF
 EXIT TRAVEL.
  
 3) WITH THE NEW WINDOWS AND DOORS THEY ARE TO MEET THE
 REQUIREMENTS OF 2010 EXISTING BUILDING CODE LEVEL II
 701.3 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING.
 SHEET A2 INDICATES THE WIND CRITERIA AS A B EXPOSURE,
 IN BOTH THE NE EXPOSURE AND SW EXPOSURE 1609.4.2
 SURFACE ROUGHNESS CATEGORIES "C". THIS SURFACE
 ROUGHNESS SHALL ALSO APPLY TO ANY BUILDING LOCATED
 WITHIN SURFACE ROUGHNESS B-TYPE TERRAIN WHERE THE
 BUILDING IS WITHIN 100 FEET HORIZONTALLY IN ANY
 DIRECTION OF OPEN AREAS OF SURFACE ROUGHNESS C OR
 D-TYPE TERRAIN THAT EXTENDS MORE THAN 600 FEET (182.9
 M) AND WIDTH GREATER THAN 150 FEET IN THE UPWIND
 DIRECTION. SHORT-TERM (LESS THAN TWO YEAR) CHANGES IN
 THE PRE-EXISTING TERRAIN EXPOSURE, FOR THE PURPOSES OF
 DEVELOPMENT, SHALL NOT BE CONSIDERED SURFACE ROUGHNESS
 C. PRESSURES TO BE RECALCULATED.
  
 4) SHEET A2 DETAIL # 2, INDICATES THE USE OF PAPER BACK
 LATH, PLEASE NOTE 2010 FBC-B 1404.2.1
 WHERE CEMENT PLASTER (STUCCO) IS TO BE APPLIED TO LATH
 OVER FRAME CONSTRUCTION, MEASURES SHALL BE TAKEN TO
 PREVENT BONDING BETWEEN THE CEMENT PLASTER AND THE
 WATER RESISTIVE BARRIER. A BOND BREAK SHALL BE PROVIDED
 BETWEEN THE WATER RESISTIVE BARRIER AND THE CEMENT
 PLASTER (STUCCO) CONSISTING OF ONE OF THE FOLLOWING:
 1. TWO LAYERS OF AN APPROVED WATER RESISTANT BARRIER OR
 2. ONE LAYER OF AN APPROVED WATER RESISTANT BARRIER
 OVER AN APPROVED PLASTIC HOUSE WRAP, OR
 3. OTHER APPROVED METHODS OR MATERIALS APPLIED IN
 ACCORDANCE WITH THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS.
  
 5) NO ROOFING PRODUCT APPROVAL WAS SUBMITTED FOR THE
 ADDITIONS. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE
 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR
 CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(D) ROOFING PRODUCTS AND ASSEMBLIES
  
 6) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-03-27 Cont ID  
Sent By albarran Date 2014-03-27 Time 19:26 Rev Time 0.00
Received By albarran Date 2014-03-27 Time 17:45 Sent To B
Notes
2014-03-27 19:28:43IN AN ATTEMPT TO GET THIS APPROVED, I IMPOSED THE
 FOLLOWING CONDITIONS ON THE PLANS:
 AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND
 RACEWAY SHALL BE CONSIDERED A WET LOCATION; YOUR
 FEEDERS SHALL BE SO LISTED.
 THE RISER DIAGRAM DOES NOT REFLECT THE REQUIRED
 GROUNDING AS PER NEC 250.24 FOR THE NEW DISCONNECT.
 AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE GFI
 PROTECTED
 AS PER NEC 300.5(B), THE INTERIOR OF AN UNDERGROUND
 RACEWAY SHALL BE CONSIDERED A WET LOCATION; YOUR
 FEEDERS SHALL BE SO LISTED.
 THE RISER DIAGRAM DOES NOT REFLECT THE REQUIRED
 GROUNDING AS PER NEC 250.24 FOR THE NEW DISCONNECT.
 AS PER NEC 422.52, ELECTRIC WATER COOLERS SHALL BE GFI
 PROTECTED
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-06 Cont ID  
Sent By albarran Date 2013-11-06 Time 17:47 Rev Time 0.00
Received By albarran Date 2013-11-06 Time 17:14 Sent To  
Notes
2013-11-06 17:54:14THE FOLLOWING ITEMS NEED CORRECTIONS:
 1. THE EXISTING FEEDER SERVING THE KITCHEN PANEL & LP1
 IS 4/0 AL WHICH IS ONLY GOOD FOR 136 AMP WITHOUT TAKING
 INTO ACCOUNT ANY POSSIBLE VOLTAGE DROP DUE TO DISTANCE
 NOT INDICATED.
 2. PROVIDE LOAD CALC FOR THE KITCHEN PANEL AND ADD THEM
 TO THE PROVIDED LOAD CALC FOR LP1.
 3. FBC-ENERGY CONSERVATION HAS SPECIFIC REQUIREMENTS
 WHICH ARE NOT INCLUDED ON THE SUBMITTED DRAWINGS.
 $. SUBMIT A FULL RISER DIAGRAM FOR THE FIRE ALARM ALONG
 WITH THE STANDBY BATTERY CALCS.
  
 RETURNED TO BIN FOR FURTHER REVIEWS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-03-17 Cont ID  
Sent By scaldero Date 2014-03-17 Time 14:33 Rev Time 0.00
Received By scaldero Date 2014-03-17 Time 14:33 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-11-20 Cont ID  
Sent By lphilmor Date 2013-11-20 Time 15:59 Rev Time 0.00
Received By lphilmor Date 2013-11-20 Time 15:56 Sent To  
Notes
2013-11-20 15:59:042727 GEORGIA AVE
  
 PERMIT # 13100594
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO****
  
 1. ADDITIONAL EXIT SIGNS WILL BE NEEDED FOR WEST EXITS
 OF EACH CLASSROOM.
 2. PROVIDE A 2-HR SEPARATION BETWEEN FOOD PANTRY AND
 CLASSROOM OR PROVIDE TIMELINE TO CONVERT PANTRY TO
 CLASSROOM.
  
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-08 Cont ID  
Sent By jwitmer Date 2014-04-08 Time 10:06 Rev Time 0.00
Received By jwitmer Date 2014-03-12 Time 17:17 Sent To  
Notes
2014-03-12 17:18:32RESUBMITTAL SENT TO B29 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-21 Cont ID  
Sent By shill Date 2013-11-21 Time 09:23 Rev Time 0.00
Received By shill Date 2013-10-17 Time 18:28 Sent To  
Notes
2013-10-18 15:32:59B29
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status N Date 2014-04-08 Cont ID  
Sent By jwitmer Date 2014-04-08 Time 10:00 Rev Time 0.00
Received By jwitmer Date 2014-04-08 Time 10:00 Sent To  
Notes
2014-04-08 10:00:34PALM BEACH COUNTY IMPACT FEE OFFICE:
 TRACK # MU-2014-000494-0000
 $2,873.27

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-25 Cont ID  
Sent By mricard Date 2013-10-25 Time 13:04 Rev Time 0.00
Received By mricard Date 2013-10-25 Time 11:02 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By lwagner Date 2013-10-28 Time 12:20 Rev Time 0.00
Received By lwagner Date 2013-10-28 Time 11:05 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2014-03-13 Cont ID  
Sent By dkittred Date 2014-03-13 Time 14:45 Rev Time 0.00
Received By dkittred Date 2014-03-13 Time 14:19 Sent To  
Notes
2014-03-13 10:58:023/13/14

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-31 Cont ID  
Sent By dkittred Date 2013-10-31 Time 12:12 Rev Time 0.00
Received By dkittred Date 2013-10-30 Time 17:39 Sent To  
Notes
2013-10-31 13:43:27EMAILED APPLICANT COMMENTS 10/31/13. DK
  
2013-10-31 12:12:35PLANNING & ZONING COMMENTS: ***FAILED***
  
 1. PLEASE PROVIDE SURVEY/SITE PLAN INDICATING PROPOSED
 ADDITIONS AND SETBACKS FROM THE PROPERTY LINE.
  
 2. PROPERTY HAS A CLASS B SPECIAL USE PERMIT (REF: CASE
 2580, 2212) TO OPERATE A DAYCARE WITH CONDITIONS. WILL
 THERE BE ANY CHANGES TO THE PROPOSED DAYCARE
 OPERATIONS, INCLUDING ANY CHANGES TO THE NUMBER OF
 STUDENTS, WITH THE RENOVATION?
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-10-30 15:22:4010/29/13


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved