Plan Review Details - Permit 13100575
Plan Review Stops For Permit 13100575
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2014-04-13 Cont ID  
Sent By skennedy Date 2014-04-13 Time 11:10 Rev Time 0.00
Received By skennedy Date 2014-04-13 Time 11:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-02-21 Cont ID  
Sent By skennedy Date 2014-02-21 Time 14:21 Rev Time 0.00
Received By skennedy Date 2014-02-21 Time 14:21 Sent To  
Notes
2014-02-21 14:25:20RECORDS APPEAR TO INDICATE THE SECOND FLOOR SPACE IS AN
 EXISTING DWELLING UNIT. IS IT THE INTENT OF THIS
 APPLICATION FOR IMPROVEMENT TO CONVERT THE EXISTING
 BUILDING INTO A TWO DWELLING BUILDING, OR IS THIS AN
 EXTENSION OF LIVING AREA WITH A SINGLE STRUCTURE
 CONSTITUTING ON DEWLLING? IF TWO UNITS, YOU MUST COMPLY
 WITH THE REQUIREMENTS FOR FIRE SEPARATION PER FBC R
 302.3 1-HR . THE SUMBITTED PLAN AND PROPERTY APPRAISER
 RECORDS APPEAR TO INDICATE THE EXISTING SPACE PROPROSED
 FOR IMPROVEMENT IS A STORAGE AREA. IN THAT CASE, THE
 DESIGN PARAMETERS MUST CONSIDER FBC-E CHAPTER 9 CHANGE
 OF OCCUPANCY. FBC 107.3.5.3 ? PROVIDE AN ENERGY
 SUBMITTAL. PROVIDE DETAILS FOR THE WINDOW OPENING
 PROPOSED TO BE FILLED IN. THIS REVIEW IS INCOMPLETE
 PENDING FURTHER CLARIFICATION OF THE INTENT OF THE
 APPLICATION.
2014-02-18 13:58:44MCDOUGAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-11-25 Cont ID  
Sent By skennedy Date 2013-11-25 Time 08:57 Rev Time 0.00
Received By skennedy Date 2013-11-25 Time 08:56 Sent To  
Notes
2013-11-25 09:00:19THE RESUBMITTED PLAN IS A DUPLICATE OF THE ORIGINAL
 SUBMITTAL. NONE OF THE COMMENTS WERE ANSWERED. BE
 ADVISED A THIRD REVIEW INDICATING THE SAME CONSISTENT
 DEFICIENCIES WILL RESULT IN PLAN REVIEW PENALTIES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-07 Cont ID  
Sent By skennedy Date 2013-11-07 Time 11:57 Rev Time 0.00
Received By skennedy Date 2013-11-06 Time 16:29 Sent To  
Notes
2013-11-07 11:57:39PLEASE ADDRESS THE ITEMS NOTED BELOW:
 FBC 107.3.5.3 ? PROVIDE A SITE PLAN TO DEMONSTRATE
 SETBACKS AND BUILDING SEPARATION. INCLUDE THE USE OF
 THE OTHER BUILDING ON THE PROPERTY.
 FBC 107.3.5.3 ? PROVIDE A FLOOR PLAN OF THE SECOND
 FLOOR AND INDICATE THE USE OF THAT SPACE. RECORDS
 APPEAR TO INDICATE THE SECOND FLOOR SPACE IS AN
 EXISTING DWELLING UNIT. IS IT THE INTENT OF THIS
 APPLICATION FOR IMPROVEMENT TO CONVERT THE EXISTING
 BUILDING INTO A TWO DWELLING BUILDING? IF SO, YOU MUST
 COMPLY WITH THE REQUIREMENTS FOR FIRE SEPARATION PER
 FBC R 302.3 1-HR . THE SUMBITTED PLAN AND PROPERTY
 APPRAISER RECORDS APPEAR TO INDICATE THE EXISTING SPACE
 PROPROSED FOR IMPROVEMENT IS A STORAGE AREA. IN THAT
 CASE, THE DESIGN PARAMETERS MUST CONSIDER FBC-E CHAPTER
 9 CHANGE OF OCCUPANCY. FBC 107.3.5.3 ? PROVIDE AN
 ENERGY SUBMITTAL. THIS REVIEW IS INCOMPLETE PENDING
 FURTHER CLARIFICATION OF THE INTENT OF THE APPLICATION.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2014-04-07 Cont ID  
Sent By albarran Date 2014-04-13 Time 11:10 Rev Time 0.00
Received By skennedy Date 2014-04-07 Time 13:14 Sent To B
Notes
2014-04-13 11:11:05REVIEW BY MIKE ALBARRAN.
2014-04-07 14:31:13AS INDICATED IN THE SCOPE OF WORK DESCRIBED ON THE
 PLANS THIS PERMIT IS LIMITED ONLY TO THE FIRST/GROUND
 FLOOR UNIT. HABITABLE SPACE IS BEING PROVIDED
 THEREFORE, AS PER THE FBC-R 303.8 HEATING IS REQUIRED
 FOR THIS UNIT.
  
 ROUTED TO JULIO
  

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2014-02-18 Cont ID  
Sent By albarran Date 2014-02-18 Time 13:54 Rev Time 0.00
Received By albarran Date 2014-02-18 Time 13:54 Sent To B
Notes
2014-02-18 13:58:15THIS FILE WAS RETURNED TO ME FROM ZONING, AFFIRMING THE
 NON-COMPLIANCE OF A THIRD METER ON THIS SITE.
 THE SITE PLANS SHALL BE REVISED TO INCLUDE THE LOCATION
 OF ALL THE SERVICES ON THIS PROPERTY.
 YOU SHALL ALSO REVISE THE ELECTRICAL DRAWING TO MATCH
 THE ACTUAL CONDITIONS OF THE SITE.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2014-02-18 Cont ID  
Sent By albarran Date 2014-02-18 Time 13:52 Rev Time 0.00
Received By albarran Date 2014-02-18 Time 13:52 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-02-12 Cont ID  
Sent By albarran Date 2014-02-12 Time 15:52 Rev Time 0.00
Received By albarran Date 2014-02-12 Time 15:11 Sent To Z
Notes
2014-02-12 15:56:29ACCORDING TO THE SUBMITTED PLANS, THERE IS NO WORK
 BEING DONE IN THE UPSTAIRS APARTMENT. I HAVE BEEN
 CALLED IN TO INSPECT INSIDE THAT UNIT AND WORK HAS BEEN
 DONE.
 FURTHERMORE, AS A RESULT OF A SITE VISIT, THE
 CONDITIONS AS INDICATED ON THE PLANS, DO NOT MATCH.
 THIS FILE SHOULD BE ROUTED TO ZONING TO CONFIRM THE
 LEGITIMACY OF THE THIRD METER FOR A THIRD DWELLING
 UNIT.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2013-11-25 Cont ID  
Sent By skennedy Date 2013-11-25 Time 09:01 Rev Time 0.00
Received By skennedy Date 2013-11-25 Time 09:01 Sent To  
Notes
2013-11-25 09:01:40THE RESUBMITTED PLAN IS A DUPLICATE OF THE ORIGINAL
 SUBMITTAL. NONE OF THE COMMENTS WERE ANSWERED. BE
 ADVISED A THIRD REVIEW INDICATING THE SAME CONSISTENT
 DEFICIENCIES WILL RESULT IN PLAN REVIEW PENALTIES.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-07 Cont ID  
Sent By skennedy Date 2013-11-07 Time 12:10 Rev Time 0.00
Received By skennedy Date 2013-11-07 Time 12:02 Sent To  
Notes
2013-11-07 12:10:01FBC- 107.3.5.3 ? ELECTRIC SERVICE RISER WITH WIRE
 SIZES, CONDUIT DETAIL AND GROUNDING DETAIL. PROVIDE
 COMPLETE LOAD CALCULATIONS, PANEL SCHEDULES AND SHOW
 CIRCUITS, WIRE SIZES, AND OCP. SHOW THE SERVICE TO THE
 UPPER FLOOR.

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-04-13 Cont ID  
Sent By skennedy Date 2014-04-13 Time 11:11 Rev Time 0.00
Received By skennedy Date 2014-04-01 Time 16:55 Sent To PC
Notes
2014-04-01 17:00:17SENT TO ZONING BOX.

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-02-21 Cont ID  
Sent By skennedy Date 2014-02-21 Time 14:25 Rev Time 0.00
Received By skennedy Date 2013-12-30 Time 11:20 Sent To  
Notes
2013-12-30 11:22:06SENT TO STEVE KENNEDY

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-25 Cont ID  
Sent By skennedy Date 2013-11-25 Time 09:01 Rev Time 0.00
Received By skennedy Date 2013-11-20 Time 11:15 Sent To  
Notes
2013-11-21 11:15:32SENT TO ZONING SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-07 Cont ID  
Sent By skennedy Date 2013-11-07 Time 12:14 Rev Time 0.00
Received By skennedy Date 2013-10-17 Time 16:08 Sent To  
Notes
2013-10-18 16:09:08R04
  

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2014-04-17 Cont ID  
Sent By skennedy Date 2014-04-17 Time 11:18 Rev Time 0.00
Received By skennedy Date 2014-04-17 Time 11:18 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2014-02-21 Cont ID  
Sent By skennedy Date 2014-02-21 Time 14:18 Rev Time 0.00
Received By skennedy Date 2014-02-21 Time 14:18 Sent To  
Notes
2014-02-21 14:20:48IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED.
 THE PLANS ARE TO BE STAMPED AND RECEIPT PROVIDED.
 CONTACT 561 233 5100.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2014-04-13 Cont ID  
Sent By skennedy Date 2014-04-13 Time 11:08 Rev Time 0.00
Received By skennedy Date 2014-04-13 Time 11:08 Sent To  
Notes
2014-04-13 11:10:01APPROVED WITH EXCEPTION TO PROVIDE A MECHANICAL PLAN
 AND ENERGY SUBMITTAL AS A REVISION.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status F Date 2014-02-21 Cont ID  
Sent By skennedy Date 2014-02-21 Time 14:14 Rev Time 0.00
Received By skennedy Date 2014-02-21 Time 14:14 Sent To  
Notes
2014-02-21 14:14:55PROVIDE A MECHANICAL PLAN AND ENERGY SUBMITTAL PER FBC
 107.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2013-11-25 Cont ID  
Sent By skennedy Date 2013-11-25 Time 09:00 Rev Time 0.00
Received By skennedy Date 2013-11-25 Time 09:00 Sent To  
Notes
2013-11-25 09:00:44THE RESUBMITTED PLAN IS A DUPLICATE OF THE ORIGINAL
 SUBMITTAL. NONE OF THE COMMENTS WERE ANSWERED. BE
 ADVISED A THIRD REVIEW INDICATING THE SAME CONSISTENT
 DEFICIENCIES WILL RESULT IN PLAN REVIEW PENALTIES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-11-07 Cont ID  
Sent By mricard Date 2013-11-04 Time 11:45 Rev Time 0.00
Received By skennedy Date 2013-11-07 Time 12:11 Sent To P
Notes
2013-11-07 12:12:40PROVIDE A MECHANICAL PLAN. THIS REPLACES THE PREVIOUS
 REVIEW.

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-02-21 Cont ID  
Sent By skennedy Date 2014-02-21 Time 14:12 Rev Time 0.00
Received By skennedy Date 2014-02-21 Time 14:12 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2013-11-25 Cont ID  
Sent By skennedy Date 2013-11-25 Time 09:00 Rev Time 0.00
Received By skennedy Date 2013-11-25 Time 09:00 Sent To  
Notes
2013-11-25 09:01:11THE RESUBMITTED PLAN IS A DUPLICATE OF THE ORIGINAL
 SUBMITTAL. NONE OF THE COMMENTS WERE ANSWERED. BE
 ADVISED A THIRD REVIEW INDICATING THE SAME CONSISTENT
 DEFICIENCIES WILL RESULT IN PLAN REVIEW PENALTIES.

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-11-07 Cont ID  
Sent By skennedy Date 2013-11-07 Time 12:12 Rev Time 0.00
Received By skennedy Date 2013-11-07 Time 12:00 Sent To  
Notes
2013-11-07 12:02:09IDENTIFY THE SIZE OF THE WASTE LINE FROM THE SHOWER ON
 DOWN.

Review Stop Z ZONING
Rev No 5 Status P Date 2014-04-03 Cont ID  
Sent By DKittred Date 2014-04-03 Time 09:19 Rev Time 0.00
Received By dkittred Date 2014-04-02 Time 08:57 Sent To E
Notes
2014-04-03 09:21:174/3/14 SENT TO MA (ELECTRICAL). DK
  
2014-04-03 09:19:29PLANNING AND ZONING COMMENTS:
  
 4/3/14
  
 RENOVATION OF THE 1ST FLOOR OF THE ACCESSORY STRUCTURE
 HAS BEEN APPROVED BY THE PLANNING DIVISION. RENOVATED
 SPACE IS TO BE IN ASSOCIATION WITH THE MAIN HOUSE ONLY
 AND IS NOT PERMITTED TO HAVE A KITCHEN OR BE RENTED AS
 A SEPARATE UNIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-04-02 08:57:494/2/14 RESUB ZONING, SENTO TO DK.SG

Review Stop Z ZONING
Rev No 4 Status F Date 2014-02-18 Cont ID  
Sent By dkittred Date 2014-02-18 Time 11:29 Rev Time 0.00
Received By dkittred Date 2014-02-13 Time   Sent To E
Notes
2014-02-18 11:29:13PLANNING AND ZONING COMMENTS: ***FAILED***
  
 2/18/14
  
 1. PLANS WERE RE-REVIEWED GENERATING COMMENTS ON THE
 SUBMITTED REVISION. SEPARATE ELECTRICAL METER WILL NOT
 BE PERMITTED FOR THE PROPOSED RENNOVATED SPACE AND
 NEEDS TO BE UPDATED APPROPRIATELY ON THE PLANS.
 RENNOVATED SPACE IS TO BE IN ASSOCIATION WITH THE
 PRINCIPAL STRUCTURE AND IS NOT PERMITTED TO BE RENTED
 OR UTILIZED AS A SEPARATE ACCESSORY APARTMENT.
  
 NOTE: A THIRD METER FOR THE PROPERTY INDICATES THIS
 RENNOVATED SPACE WILL BE RENTED SEPARATELY WHICH IS NOT
 PERMITTED. AN ACCESSORY APARTMENT ALREADY EXISTS ON THE
 SECOND FLOOR OF THE ACCESSORY STRUCTURE ON THE PROPERTY
 WHICH IS GRANDFATHERED-IN. NO ADDITIONAL ACCESSORY
 APARTMENTS ARE PERMITTED AT THIS LOCATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2014-02-13 15:05:562/13/13 ZONING RECEIVED. SENT TO DK FOR REVIEW. SG
2014-02-12 15:59:43HAVING READ THE PREVIOUS ZONING NOTES, THERE WAS SOME
 DOUBT AS TO THE POSSIBILITY OF THE REAR APARTMENT, THE
 SUBMITTED DRAWING DOES NOT MATCH THE SITE CONDITIONS,
 BUT THERE IS A THIRD METER ON THIS PROPERTY. PLEASE
 VERIFY/CONFIRM THE LEGITIMACY OF THAT THIRD METER. ONCE
 YOUR REVIEW IS COMPLETED, PLEASE RETURN IT TO MY DESK.
 MA

Review Stop Z ZONING
Rev No 3 Status P Date 2014-01-10 Cont ID  
Sent By dkittred Date 2014-01-10 Time 09:33 Rev Time 0.00
Received By dkittred Date 2014-01-10 Time 09:19 Sent To  
Notes
2014-01-10 09:34:231/10/14 - SENT BACK TO SK.(DK)
2014-01-02 12:13:041/2/14

Review Stop Z ZONING
Rev No 2 Status F Date 2013-11-22 Cont ID  
Sent By dkittred Date 2013-11-22 Time 17:59 Rev Time 0.00
Received By dkittred Date 2013-11-22 Time 13:16 Sent To  
Notes
2013-11-22 17:59:4811/22/13 SENT TO SK.
2013-11-22 17:46:09PLANNING AND ZONING COMMENTS: ***FAILED***
  
 11/22/13
 PREVIOUS COMMENTS PROVIDED ON 10/31/13 WERE NOT
 ADDRESSED.
  
 1. RESUBMITTAL DOES NOT INCLUDE A SURVEY OR PLOT PLAN
 INDICATING THE LOCATION OF THE STRUCTURE.
  
 2. RESUBMITTAL NEEDS TO INCLUDE A STATEMENT OF THE
 INTENT OF THE RENNOVATED SPACE. IT IS STILL UNCLEAR IF
 THE APPLICANT INTENDS ON USING THE SPACE FOR AN
 ACCESSORY APARTMENT OR DETACHED BEDROOM. IF THE
 APPLICANT CAN NOT MEET THE REQUIREMENTS FOR AN
 ACCESSORY APARTMENT OR DOES NOT WISH TO UTILIZE THE
 SPACE AS AN ACCESSORY APARTMENT THEN KITCHEN FACILITIES
 NEED TO BE REMOVED FROM THE PLANS. THE MOST THAT CAN BE
 INCLUDED WITHOUT BEING CONSIDERED A KITCHEN FACILITY IS
 AN UNDER COUNTER REFRIDGERATOR AND SMALL SINK.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-11-22 07:48:3111/22/13 - ZONING RECEIVED. SENT TO DK FOR REVIEW. LL

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-31 Cont ID  
Sent By dkittred Date 2013-10-31 Time 10:38 Rev Time 0.00
Received By mricard Date 2013-11-04 Time 11:26 Sent To  
Notes
2013-10-31 10:39:24SENT EMAIL TO APPLICANT REGARDING COMMENTS 10/31/13. DK
  
2013-10-31 10:37:39PLANNING AND ZONING COMMENTS: ***FAILED***
  
 10/31/2013
  
 1. APPEARS THAT RENOVATIONS WILL BE FOR AN ACCESSORY
 STRUCTURE IN THE REAR OF THE PROPERTY. PLEASE PROVIDE A
 SURVEY OR SITE PLAN INDICATING THE LOCATION OF THE
 PROPOSED STRUCTURE BEING RENOVATED.
  
 2. THE PROPERTY IS LOCATED IN THE SF14 ZONING DISTRICT.
 IF THE RENOVATION ARE TO CREATE AN ACCESSORY APARTMENT
 ON THE PROPERTY THEN THE APPLICANT MUST DEMONSTRATE
 COMPLIANCE WITH THE ADDITIONAL STANDARDS IN ZLDR
 SECTION 94-303. IT DOES NOT APPEAR THE PROPERTY WOULD
 MEET THE ADDITIONAL STANDARDS OF HAVING A MINIMUM LOT
 SIZE OF 6,000 SQ. FT. AND MINIMUM LOT DEPTH OF 60 FT.
 APPLICANT SHALL PROVIDE EVIDENCE THAT ALL ADDITIONAL
 STANDARDS IN ZLDR SECTION 94-303 CAN BE MEET IN ORDER
 TO HAVE AN ACCESSORY APARTMENT.
  
 3. IF APPLICANT CAN NOT MEET ALL THE ADDITIONAL
 STANDARDS THEN AN ACCESSORY APARTMENT WILL NOT BE
 PERMITTED AND AT MINIMUM THE APPLICANT WILL NEED TO
 REMOVE THE PROPOSED KITCHEN FACILITY FROM THE SUBMITTED
 PLANS IN ORDER FOR THE RENOVATION TO BE IN COMPLIANCE
 WITH THE ZONING CODE. ADDITIONALLY, THE DETACHED
 BEDROOM COULD ONLY BE ASSOCIATED WITH THE PRINCIPAL
 STRUCTURE AND WOULD NOT BE PERMITTED TO BE RENTED
 SEPARATELY.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  