Plan Review Details - Permit 13100553
Plan Review Stops For Permit 13100553
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-06 Cont ID  
Sent By shill Date 2013-12-06 Time 14:12 Rev Time 0.00
Received By shill Date 2013-12-06 Time 14:12 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-02 Cont ID  
Sent By shill Date 2013-11-02 Time 08:17 Rev Time 0.00
Received By shill Date 2013-11-02 Time 08:17 Sent To  
Notes
2013-11-02 08:17:33****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. FBC 1609, THE FASTENER DIAMETER AND LENGTH (OR
 MINIMUM EMBEDMENT) AS WELL AS FASTENER SPACING WAS NOT
 INCLUDED ON THE PLAN.
  
 2. COVER SHEET OF PLAN STATES THAT ENGINEERING IS
 INCLUDED. PLEASE PROVIDE FBC 107.
  
 3. STRUCTURAL PLAN TO INCLUDE WIND DESIGN CRITERIA
 FBC1603.1.4. IF PLANS ARE NOT SIGNED AND SEALED BY AN
 ARCHITECT OR ENGINEER, INCLUDE THE PRINTED NAME AND
 SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR
 THE DESIGN, AND CALCULATIONS MAY BE REQUIRED.
  
 4. PROVIDE A COPY OF A VERIFIABLE CONTRACT FOR THIS
 JOB, FBC 109. VALUE IS TO BE INCLUDE LABOR, MATERIALS,
 AND ENGINEERING. IF SIGNS ARE PROVIDED BY OTHERS,
 PLEASE HAVE THEM PROVIDE THE CONTRACT OR WORK ORDER FOR
 THE MATERIALS FBC 109.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By albarran Date 2013-10-31 Time 19:04 Rev Time 0.00
Received By albarran Date 2013-10-31 Time 19:00 Sent To I
Notes
2013-10-31 19:05:54THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE NEC
 COMPLIANCE OF THE SIGN ITSELF, BUT EXCLUDES ANY
 ELECTRICAL INSTALLATION FOR SUCH
  
 THIS WAS SUBMITTED IN CONJUNCTION W/A SEPARATE PERMIT

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-20 Cont ID  
Sent By shill Date 2013-12-20 Time 18:52 Rev Time 0.00
Received By shill Date   Time   Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-02 Cont ID  
Sent By shill Date 2013-11-02 Time 08:17 Rev Time  
Received By shill Date 2013-10-16 Time   Sent To  
Notes
2013-10-16 14:23:22ZONING

Review Stop Z ZONING
Rev No 2 Status P Date 2013-12-13 Cont ID  
Sent By ajones Date 2013-12-13 Time 14:35 Rev Time 0.00
Received By ajones Date 2013-12-13 Time 14:35 Sent To  
Notes
2013-12-13 14:36:3312/13/13- GIVEN TO SH FOR PROCESSING

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By eschneid Date 2013-10-28 Time 20:48 Rev Time 0.00
Received By ajones Date 2013-10-21 Time 08:31 Sent To  
Notes
2013-10-28 20:57:3710/28/13- DENIED- THE SIGNS ON THE TOWER ARE EXPOSED
 FROM THE EXTERIOR OF THE OUTLETS. AS PER THE DESIGN
 GUIDELINES AND SITE PLAN APPROVALS, ALL EXTERIOR SIGNS
 SQ. FOOTAGE MUST BE SHOWN IN A TABULAR FORMAT IN
 RELATIONSHIP TO THE SIGNAGE APPROVED FOR THAT
 ELEVATION.
  
 ANGELLA VANN
 561-822-1441
 [email protected]
  
2013-10-21 08:32:3410/21/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL