Plan Review Details - Permit 13100553
| Plan Review Stops For Permit 13100553 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-12-06 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-12-06 |
Time |
14:12 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-12-06 |
Time |
14:12 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-11-02 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-11-02 |
Time |
08:17 |
Sent To |
|
|
| Notes |
| 2013-11-02 08:17:33 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | 1. FBC 1609, THE FASTENER DIAMETER AND LENGTH (OR | | | MINIMUM EMBEDMENT) AS WELL AS FASTENER SPACING WAS NOT | | | INCLUDED ON THE PLAN. | | | | | | 2. COVER SHEET OF PLAN STATES THAT ENGINEERING IS | | | INCLUDED. PLEASE PROVIDE FBC 107. | | | | | | 3. STRUCTURAL PLAN TO INCLUDE WIND DESIGN CRITERIA | | | FBC1603.1.4. IF PLANS ARE NOT SIGNED AND SEALED BY AN | | | ARCHITECT OR ENGINEER, INCLUDE THE PRINTED NAME AND | | | SIGNATURE OF THE INDIVIDUAL TAKING RESPONSIBILITY FOR | | | THE DESIGN, AND CALCULATIONS MAY BE REQUIRED. | | | | | | 4. PROVIDE A COPY OF A VERIFIABLE CONTRACT FOR THIS | | | JOB, FBC 109. VALUE IS TO BE INCLUDE LABOR, MATERIALS, | | | AND ENGINEERING. IF SIGNS ARE PROVIDED BY OTHERS, | | | PLEASE HAVE THEM PROVIDE THE CONTRACT OR WORK ORDER FOR | | | THE MATERIALS FBC 109. | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-10-31 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-10-31 |
Time |
19:04 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-10-31 |
Time |
19:00 |
Sent To |
I |
|
| Notes |
| 2013-10-31 19:05:54 | THE SCOPE OF THIS PERMIT REVIEW IS LIMITED TO THE NEC | | | COMPLIANCE OF THE SIGN ITSELF, BUT EXCLUDES ANY | | | ELECTRICAL INSTALLATION FOR SUCH | | | | | | THIS WAS SUBMITTED IN CONJUNCTION W/A SEPARATE PERMIT |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-12-20 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-12-20 |
Time |
18:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-11-02 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-11-02 |
Time |
08:17 |
Rev Time |
|
| Received By |
shill |
Date |
2013-10-16 |
Time |
|
Sent To |
|
|
| Notes |
| 2013-10-16 14:23:22 | ZONING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2013-12-13 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2013-12-13 |
Time |
14:35 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2013-12-13 |
Time |
14:35 |
Sent To |
|
|
| Notes |
| 2013-12-13 14:36:33 | 12/13/13- GIVEN TO SH FOR PROCESSING |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2013-10-28 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2013-10-28 |
Time |
20:48 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2013-10-21 |
Time |
08:31 |
Sent To |
|
|
| Notes |
| 2013-10-28 20:57:37 | 10/28/13- DENIED- THE SIGNS ON THE TOWER ARE EXPOSED | | | FROM THE EXTERIOR OF THE OUTLETS. AS PER THE DESIGN | | | GUIDELINES AND SITE PLAN APPROVALS, ALL EXTERIOR SIGNS | | | SQ. FOOTAGE MUST BE SHOWN IN A TABULAR FORMAT IN | | | RELATIONSHIP TO THE SIGNAGE APPROVED FOR THAT | | | ELEVATION. | | | | | | ANGELLA VANN | | | 561-822-1441 | | | [email protected] | | | | | 2013-10-21 08:32:34 | 10/21/13 - ZONING RECEIVED. SENT TO ES FOR REVIEW. LL |
|
|
|