| 2013-10-18 08:13:12 | BUILDING PLAN REVIEW |
| | PERMIT: 13100501 |
| | ADD: 2707 OKEECHOBEE BLVD |
| | CONT: FLORIDA FILTRATION |
| | TEL: (561) 582-5543 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: OCT. 18/ 2013 |
| | ACTION: DENIED |
| | |
| | 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING |
| | CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | |
| | 1) THE PLANS DO NOT PROVIDE CODE COMPLIANCE FOR 2010 |
| | FBC-B SECTION: |
| | 1A) F] 416.2 SPRAY ROOMS. |
| | SPRAY ROOMS SHALL BE ENCLOSED WITH NOT LESS THAN 1-HOUR |
| | FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION |
| | 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE |
| | WITH SECTION 712, OR BOTH. FLOORS SHALL BE WATERPROOFED |
| | AND DRAINED IN AN APPROVED MANNER. |
| | |
| | 1B) [F] 416.2.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH |
| | AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE |
| | OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO |
| | FACILITATE WASHING AND CLEANING, AND SHALL BE SO |
| | DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM |
| | SHALL NOT BE USED. |
| | |
| | 1C) [F] 416.3 SPRAYING SPACES. |
| | SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST |
| | SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR |
| | VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, |
| | MECHANICAL. WHERE SUCH SPACES ARE NOT SEPARATELY |
| | ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE |
| | PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS. |
| | |
| | 1D) [F] 416.3.1 SURFACES. |
| | THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE |
| | SMOOTH AND CONTINUOUS WITHOUT EDGES; SHALL BE SO |
| | CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR |
| | FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE |
| | WASHING AND CLEANING; AND SHALL BE SO DESIGNED TO |
| | CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM |
| | SHALL NOT BE USED. |
| | |
| | 1E) [F] 416.4 SPRAY BOOTHS. |
| | SPRAY BOOTHS SHALL BE DESIGNED, CONSTRUCTED AND |
| | OPERATED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION |
| | CODE. |
| | |
| | 2) 2010 FBC-B 415.3 FIRE SEPARATION DISTANCE. |
| | GROUP H OCCUPANCIES SHALL BE LOCATED ON PROPERTY IN |
| | ACCORDANCE WITH THE OTHER PROVISIONS OF THIS CHAPTER. |
| | IN GROUPS H-2 AND H-3, NOT LESS THAN 25 PERCENT OF THE |
| | PERIMETER WALL OF THE OCCUPANCY SHALL BE AN EXTERIOR |
| | WALL. |
| | |
| | EXCEPTIONS: |
| | |
| | 2.1. LIQUID USE, DISPENSING AND MIXING ROOMS HAVING A |
| | FLOOR AREA OF NOT MORE THAN 500 SQUARE FEET (46.5 M2) |
| | NEED NOT BE LOCATED ON THE OUTER PERIMETER OF THE |
| | BUILDING WHERE THEY ARE IN ACCORDANCE WITH THE FLORIDA |
| | FIRE PREVENTION CODE AND NFPA 30. |
| | |
| | 2.2. LIQUID STORAGE ROOMS HAVING A FLOOR AREA OF NOT |
| | MORE THAN 1,000 SQUARE FEET (93 M2) NEED NOT BE LOCATED |
| | ON THE OUTER PERIMETER WHERE THEY ARE IN ACCORDANCE |
| | WITH THE FLORIDA FIRE PREVENTION CODE. AND NFPA 30. |
| | |
| | 2.3. SPRAY PAINT BOOTHS THAT COMPLY WITH THE FLORIDA |
| | FIRE PREVENTION CODE NEED NOT BE LOCATED ON THE OUTER |
| | PERIMETER. |
| | |
| | 3) SHEET B1 NOTES INDICATE STORAGE OF FLAMMABLE, |
| | LIQUIDS, PLEASE PORVIDE TYPES OF FLAMMABLE LIQUIDS, |
| | (1A, 1B AND OR 1C) AND QUANITIES TO BE STORED, AND SHOW |
| | COMPLIANCE WITH 2010 FBC-B TABLE 307.1(1) |
| | |
| | 4) SHEET B3 INDICATES THE EXHAUST THROUGH THE ROOF, THE |
| | PLANS DO NOT INDICATE TYPE OF ROOF FRAMING OR ROOF DECK |
| | AND IF THERE WILLBE ANY EXTRA FRAMING REQUIRED. PLANS |
| | ARE ALSO MISSING THE WIND DESIN CRITERIA FOR THE |
| | EXHAUST DUCT ASSEMBLY. |
| | 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN- |
| | CHAPTER 6 OF ASCE 7-10. |
| | 1609.3 BASIC WIND SPEED FIGURE 1609.A-C |
| | 1609.3 WIND SPEED CONVERSION |
| | 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.3.1 & ASCE 7-10 |
| | |
| | 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10. |
| | |
| | 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4 & ASCE 7-10 |
| | |
| | 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10. |
| | |
| | 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE |
| | TABLE 1609.2(2) . |
| | |