Plan Review Details - Permit 13100501
Plan Review Stops For Permit 13100501
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-20 Cont ID  
Sent By jwitmer Date 2013-11-20 Time 07:00 Rev Time 0.00
Received By jwitmer Date 2013-11-20 Time 06:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-18 Cont ID  
Sent By jwitmer Date 2013-10-18 Time 08:13 Rev Time 0.00
Received By jwitmer Date 2013-10-18 Time 07:12 Sent To  
Notes
2013-10-18 08:13:12BUILDING PLAN REVIEW
 PERMIT: 13100501
 ADD: 2707 OKEECHOBEE BLVD
 CONT: FLORIDA FILTRATION
 TEL: (561) 582-5543
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: OCT. 18/ 2013
 ACTION: DENIED
  
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
  
 1) THE PLANS DO NOT PROVIDE CODE COMPLIANCE FOR 2010
 FBC-B SECTION:
 1A) F] 416.2 SPRAY ROOMS.
 SPRAY ROOMS SHALL BE ENCLOSED WITH NOT LESS THAN 1-HOUR
 FIRE BARRIERS CONSTRUCTED IN ACCORDANCE WITH SECTION
 707 OR HORIZONTAL ASSEMBLIES CONSTRUCTED IN ACCORDANCE
 WITH SECTION 712, OR BOTH. FLOORS SHALL BE WATERPROOFED
 AND DRAINED IN AN APPROVED MANNER.
  
 1B) [F] 416.2.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAY ROOMS SHALL BE SMOOTH
 AND SHALL BE SO CONSTRUCTED TO PERMIT THE FREE PASSAGE
 OF EXHAUST AIR FROM ALL PARTS OF THE INTERIOR AND TO
 FACILITATE WASHING AND CLEANING, AND SHALL BE SO
 DESIGNED TO CONFINE RESIDUES WITHIN THE ROOM. ALUMINUM
 SHALL NOT BE USED.
  
 1C) [F] 416.3 SPRAYING SPACES.
 SPRAYING SPACES SHALL BE VENTILATED WITH AN EXHAUST
 SYSTEM TO PREVENT THE ACCUMULATION OF FLAMMABLE MIST OR
 VAPORS IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. WHERE SUCH SPACES ARE NOT SEPARATELY
 ENCLOSED, NONCOMBUSTIBLE SPRAY CURTAINS SHALL BE
 PROVIDED TO RESTRICT THE SPREAD OF FLAMMABLE VAPORS.
  
 1D) [F] 416.3.1 SURFACES.
 THE INTERIOR SURFACES OF SPRAYING SPACES SHALL BE
 SMOOTH AND CONTINUOUS WITHOUT EDGES; SHALL BE SO
 CONSTRUCTED TO PERMIT THE FREE PASSAGE OF EXHAUST AIR
 FROM ALL PARTS OF THE INTERIOR AND TO FACILITATE
 WASHING AND CLEANING; AND SHALL BE SO DESIGNED TO
 CONFINE RESIDUES WITHIN THE SPRAYING SPACE. ALUMINUM
 SHALL NOT BE USED.
  
 1E) [F] 416.4 SPRAY BOOTHS.
 SPRAY BOOTHS SHALL BE DESIGNED, CONSTRUCTED AND
 OPERATED IN ACCORDANCE WITH THE FLORIDA FIRE PREVENTION
 CODE.
  
 2) 2010 FBC-B 415.3 FIRE SEPARATION DISTANCE.
 GROUP H OCCUPANCIES SHALL BE LOCATED ON PROPERTY IN
 ACCORDANCE WITH THE OTHER PROVISIONS OF THIS CHAPTER.
 IN GROUPS H-2 AND H-3, NOT LESS THAN 25 PERCENT OF THE
 PERIMETER WALL OF THE OCCUPANCY SHALL BE AN EXTERIOR
 WALL.
  
 EXCEPTIONS:
  
 2.1. LIQUID USE, DISPENSING AND MIXING ROOMS HAVING A
 FLOOR AREA OF NOT MORE THAN 500 SQUARE FEET (46.5 M2)
 NEED NOT BE LOCATED ON THE OUTER PERIMETER OF THE
 BUILDING WHERE THEY ARE IN ACCORDANCE WITH THE FLORIDA
 FIRE PREVENTION CODE AND NFPA 30.
  
 2.2. LIQUID STORAGE ROOMS HAVING A FLOOR AREA OF NOT
 MORE THAN 1,000 SQUARE FEET (93 M2) NEED NOT BE LOCATED
 ON THE OUTER PERIMETER WHERE THEY ARE IN ACCORDANCE
 WITH THE FLORIDA FIRE PREVENTION CODE. AND NFPA 30.
  
 2.3. SPRAY PAINT BOOTHS THAT COMPLY WITH THE FLORIDA
 FIRE PREVENTION CODE NEED NOT BE LOCATED ON THE OUTER
 PERIMETER.
  
 3) SHEET B1 NOTES INDICATE STORAGE OF FLAMMABLE,
 LIQUIDS, PLEASE PORVIDE TYPES OF FLAMMABLE LIQUIDS,
 (1A, 1B AND OR 1C) AND QUANITIES TO BE STORED, AND SHOW
 COMPLIANCE WITH 2010 FBC-B TABLE 307.1(1)
  
 4) SHEET B3 INDICATES THE EXHAUST THROUGH THE ROOF, THE
 PLANS DO NOT INDICATE TYPE OF ROOF FRAMING OR ROOF DECK
 AND IF THERE WILLBE ANY EXTRA FRAMING REQUIRED. PLANS
 ARE ALSO MISSING THE WIND DESIN CRITERIA FOR THE
 EXHAUST DUCT ASSEMBLY.
 2010 FBC-B 1609.1.1 DETERMINATION OF WIND DESIGN-
 CHAPTER 6 OF ASCE 7-10.
 1609.3 BASIC WIND SPEED FIGURE 1609.A-C
 1609.3 WIND SPEED CONVERSION
 4.1) THE BASIC WIND SPEED, VU, SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.3.1 & ASCE 7-10
  
 4.2) AN IMPORTANCE FACTOR, FIGURE 1609 A-C, ASCE 7-10.
  
 4.3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN
 ACCORDANCE WITH 1609.4 & ASCE 7-10
  
 4.4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, *
 SHALL BE DETERMINED FROM TABLE 1609.7.2. ASCE 7-10.
  
 4.5) COMPONENTS & CLADDING PRESSURES POSITVE & NEGATIVE
 TABLE 1609.2(2) .
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-22 Cont ID  
Sent By albarran Date 2013-11-22 Time 18:03 Rev Time 0.00
Received By albarran Date 2013-11-22 Time 18:03 Sent To I
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-04 Cont ID  
Sent By albarran Date 2013-11-04 Time 15:25 Rev Time 0.00
Received By albarran Date 2013-11-04 Time 14:25 Sent To I
Notes
2013-11-04 15:30:08I AM UNCERTAIN FROM THE EXPLANATION IF THIS IS A
 SELF-CONTAINED/MANUFACTURED UNIT NEEDING ONLY THE
 SUPPLY CONNECTIONS OR IT THIS IS A SITE-BUILT PAINT
 BOOTH BEING WIRED IN ITS ENTIRETY ON SITE. PLEASE
 ADVISE IF THIS IS A MANUFACTURED UNIT OR IF SITE-BUILT.
 REGARDLESS, THE FEEDERS ARE NOT ADEQUATE FOR THE LOAD
 SERVED. RECALCULATE THE DEMANDS AS PER NEC REQUIREMENTS
 AND SUBMIT FOR APPROVAL.
 SENT TO SH DESK

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-11-19 Cont ID  
Sent By scaldero Date 2013-11-19 Time 13:39 Rev Time 0.00
Received By scaldero Date 2013-11-19 Time 13:39 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-10-23 Cont ID  
Sent By scaldero Date 2013-10-23 Time 15:27 Rev Time 0.00
Received By scaldero Date 2013-10-23 Time 15:18 Sent To  
Notes
2013-10-23 15:27:08PERMIT #13100501
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET B1: PLEASE PROVIDE TYPES AND QUANTITIES OF
 FLAMMABLE LIQUIDS TO BE STORED.
  
 SHEETS B2 & B3: PER NFPA 33, CHAPTER 5: 5.1.4 IF WALLS
 OR CEILING ASSEMBLIES ARE CONSTRUCTED OF SHEET METAL,
 SINGLE-SKIN ASSEMBLIES SHALL BE NO THINNER THAN 1.2 MM
 (0.0478 IN.), AND EACH SHEET OF DOUBLE-SKIN ASSEMBLIES
 SHALL BE NO THINNER THAN 0.9 MM (0.0359 IN.).
 PLEASE INDICATE THE THICKNESS OF THE SINGLE-SKIN WALLS.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-25 Cont ID  
Sent By shill Date 2013-11-25 Time 12:51 Rev Time 0.00
Received By shill Date 2013-11-08 Time 13:40 Sent To  
Notes
2013-11-12 14:04:16C14

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-05 Cont ID  
Sent By shill Date 2013-11-05 Time 19:41 Rev Time 0.00
Received By shill Date 2013-10-15 Time 12:58 Sent To  
Notes
2013-10-16 12:59:57INCOMING SENT TO C-20 BOX. JWITMER

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-23 Cont ID  
Sent By mricard Date 2013-10-23 Time 13:13 Rev Time 0.00
Received By mricard Date 2013-10-23 Time 12:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2013-11-18 Cont ID  
Sent By dkittred Date 2013-11-18 Time 08:33 Rev Time 0.00
Received By dkittred Date 2013-11-18 Time 08:28 Sent To  
Notes
2013-11-18 08:33:15PLANNING & ZONING COMMENTS:
  
 11/18/13
  
 THE PAINT BOOTH FACILITY HAS BEEN APPROVED. A CLASS B
 SPECIAL USE PERMIT WAS ISSUED WITH THE FOLLOWING
 CONDITIONS:
 A. THE PAINT BOOTH FACILITY AT 2707 OKEECHOBEE
 BOULEVARD SHALL BE LIMITED TO 809 SQUARE FEET.
 B. THE PROPOSED PAINT BOOTH FACILITY SHALL ONLY BE USED
 AS PART OF THE RECONDITIONING OPERATION ON THE SITE TO
 PREPARE VEHICLES FOR RESALE AND SHALL NOT BE OPEN TO
 THE PUBLIC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
  
  
2013-11-13 16:57:5411/13/13
 ZBA APPROVED A CLASS B SPECIAL USE PERMIT FOR A PAINT
 BOOTH FACILITY ON THE SUBJECT PROPERTY ON NOV. 7, 2013.
 PLANNING IS IN THE PROCESS OF GETTING THE FINAL ORDER
 SIGNED AND WILL GRANT ZONING APPROVAL ONCE THIS IS
 COMPLETE. DK
2013-11-13 14:17:0511/13/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By dkittred Date 2013-10-18 Time 4:45 Rev Time 0.00
Received By dkittred Date 2013-10-18 Time 15:45 Sent To  
Notes
2013-10-18 16:24:07PLANNING AND ZONING COMMENTS: ***FAILED***
  
 CLASS B SPECIAL USE PERMIT REQUIRED FOR PROPOSED PAINT
 BOOTH IN THE GC ZONING DISTRICT. APPLICATION PENDING
 WITH PLANNING AND ZBA HEARING SCHEDULED FOR 11/7/13.
 PLANNING APPROVAL PENDING APPROVAL OF THE CLASS B
 SPECIAL USE PERMIT.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  