Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-12-20 Cont ID  
Sent By jwitmer Date 2013-12-20 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2013-12-20 Time 12:41 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-11-23 Cont ID  
Sent By jwitmer Date 2013-11-23 Time 09:15 Rev Time 0.00
Received By jwitmer Date 2013-11-23 Time 08:48 Sent To  
Notes
2013-11-23 09:09:07BUILDING PLAN REVIEW
 PERMIT: 13100473
 ADD: 1741 PALM BEACH LAKES BLVD (SHADE CANOPY
 STRUCTURES) / BROUGHT IN AS 1801 PBL
 CONT: EMJ CORP
 TEL: (423)464-1537
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: SAT. NOV. 23/ 2013
 ACTION: DENIED
  
 THE LISTED ITEMS ARE REQUIRED ON THE PLANS TO CLASSIFY
 THE STRUTURE AND OCCUPANCY:
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION,
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS;
 1A) MINIMUM BUILDING TYPE: 2010 FBC-B 3102.3
  
 1B) OCCUPANCY TYPE: A-3 ASSEMBLY USESRECREATION OR
 OTHER AMUSEMENTAND OR OTHER ASSEMBLY USES NOT
 CLASSIFIED ELSEWHERE.
  
 2) 2010 FBC-B 3102.3 TYPE OF CONSTRUCTION.
 NONCOMBUSTIBLE MEMBRANE STRUCTURES SHALL BE CLASSIFIED
 AS TYPE IIB CONSTRUCTION. NONCOMBUSTIBLE FRAME OR
 CABLE-SUPPORTED STRUCTURES COVERED BY AN APPROVED
 MEMBRANE IN ACCORDANCE WITH SECTION 3102.3.1 SHALL BE
 CLASSIFIED AS TYPE IIB CONSTRUCTION.
  
 FLORIDA BUILDING OFFICIALS ASSOCIATION REPORT 6027 /
 2004
 MAY OR MAY NOT REQUIRE SPRINKLERS IT WILL DEPEND ON
 WILL THERE BE KIOSK BE UNDER THE CANOPIES, WILL THERE
 BE SEATING WITH COMBUSTIBLE FURNATURE, WILL THERE BE
 AUTOMOBILES SHOWED IN UNDER THE VARIOUS KIOSK?
 NFPA 13, 8.15.7.5 STATES, "SPRINKLERES SHALL BE
 INSTALLED UNDER ROOFS, CANOPIES, OR PORTE-COCHERES OVER
 AREAS WHERE COMBUSTIBLES ARE STORED AND HANDLED. ALSO
 STATES IN CANOPIES UNDER WHICH MEALS ARE SERVED OR
 PEOPLE ARE SEATED, THE FURNIISHINGS MAY BE COMBUSTIBLE.
 ANY OF THE FORE GOING COULD TRIGGER THE REQUIREMENT FOR
 FIRE SPRINKLERS.
  
 3) COMPLIED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-01 Cont ID  
Sent By jwitmer Date 2013-11-01 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2013-11-01 Time 06:31 Sent To  
Notes
2013-11-01 07:44:47 
  
 BUILDING PLAN REVIEW
 PERMIT: 13100473
 ADD: 1741 PALM BEACH LAKES BLVD (SHADE CANOPY
 STRUCTURES) / BROUGHT IN AS 1801 PBL
 CONT: EMJ CORP
 TEL: (423)464-1537
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: FRI. NOV. 01/ 2013
 ACTION: DENIED
  
 1) 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION,
 107.3.5.1.1 MINIMUM PLAN REVIEW CRITERIA FOR COMMERCIAL
 BUILDINGS;
 1A) MINIMUM BUILDING TYPE: 2010 FBC-B 3102.3
  
 1B) OCCUPANCY TYPE: A-3 ASSEMBLY USESRECREATION OR
 OTHER AMUSEMENTAND OR OTHER ASSEMBLY USES NOT
 CLASSIFIED ELSEWHERE.
  
 2) 2010 FBC-B 3102.3 TYPE OF CONSTRUCTION.
 NONCOMBUSTIBLE MEMBRANE STRUCTURES SHALL BE CLASSIFIED
 AS TYPE IIB CONSTRUCTION. NONCOMBUSTIBLE FRAME OR
 CABLE-SUPPORTED STRUCTURES COVERED BY AN APPROVED
 MEMBRANE IN ACCORDANCE WITH SECTION 3102.3.1 SHALL BE
 CLASSIFIED AS TYPE IIB CONSTRUCTION.
  
 FLORIDA BUILDING OFFICIALS ASSOCIATION REPORT 6027 /
 2004
 MAY OR MAY NOT REQUIRE SPRINKLERS IT WILL DEPEND ON
 WILL THERE BE KIOSK BE UNDER THE CANOPIES, WILL THERE
 BE SEATING WITH COMBUSTIBLE FURNATURE, WILL THERE BE
 AUTOMOBILES SHOWED IN UNDER THE VARIOUS KIOSK?
 NFPA 13, 8.15.7.5 STATES, "SPRINKLERES SHALL BE
 INSTALLED UNDER ROOFS, CANOPIES, OR PORTE-COCHERES OVER
 AREAS WHERE COMBUSTIBLES ARE STORED AND HANDLED. ALSO
 STATES IN CANOPIES UNDER WHICH MEALS ARE SERVED OR
 PEOPLE ARE SEATED, THE FURNIISHINGS MAY BE COMBUSTIBLE.
 ANY OF THE FORE GOING COULD TRIGGER THE REQUIREMENT FOR
 FIRE SPRINKLERS.
  
 3) 2010 FBC-B 3105.3.1 FABRIC USED FOR AWNINGS OR
 FABRIC-COVERED FRAMES SHALL MEET THE FLAME PROPAGATION
 PERFORMANCE CRITERIA OF NFPA 701.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-23 Cont ID  
Sent By scaldero Date 2013-10-23 Time 14:27 Rev Time 0.00
Received By scaldero Date 2013-10-23 Time 14:26 Sent To  
Notes
2013-10-23 14:37:01PERMIT #13100473
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 ********PROVISO***********
 CANOPY MATERIAL MUST BE OF AN APPROVED FLAME RESISTANT
 PRODUCT. FLAME CERTIFICATE MUST BE PROVIDED AT TIME OF
 FIELD INSPECTION AND IS SUBJECT TO INSPECTOR'S
 APPROVAL.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-12-20 Cont ID  
Sent By jwitmer Date 2013-12-20 Time 12:41 Rev Time 0.00
Received By jwitmer Date 2013-12-16 Time 14:44 Sent To  
Notes
2013-12-17 14:44:33RESUBMITTAL SENT TO J. WITMER'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-16 Cont ID  
Sent By shill Date 2013-12-16 Time 12:55 Rev Time 0.00
Received By shill Date 2013-11-20 Time 10:10 Sent To  
Notes
2013-11-21 10:10:37SENT TO C21 SHELF FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-01 Cont ID  
Sent By jwitmer Date 2013-11-01 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2013-10-15 Time 17:42 Sent To  
Notes
2013-10-16 17:43:13INCOMING SENT TO C-07.JW

Review Stop POLICE POLICE
Rev No 1 Status N Date 2013-12-11 Cont ID  
Sent By eschneid Date 2013-12-11 Time 09:05 Rev Time 0.00
Received By eschneid Date   Time   Sent To  
Notes
2013-12-11 09:06:10PER OF. KELLY CARSILLO

Review Stop Z ZONING
Rev No 2 Status P Date 2013-12-10 Cont ID  
Sent By eschneid Date 2013-12-10 Time 14:28 Rev Time 0.50
Received By eschneid Date 2013-12-10 Time 14:28 Sent To  
Notes
2013-11-22 15:06:4311/22/13

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By eschneid Date 2013-10-28 Time 13:54 Rev Time 0.25
Received By eschneid Date 2013-10-28 Time 13:54 Sent To B
Notes
2013-10-28 14:12:22FAILED
  
 1) PROVIDE AN ELEVATION DIMENSION LINE SHOWING THE
 ENTIRE HEIGHT OF THE CANOPY STRUCTURE FROM GRADE TO THE
 TOP OF THE STRUCTURE.
  
 2) PROVIDE INFORMATION ON THE MATERIAL THAT WILL BE
 COVERING THE CANOPY STRUCTURES. THE ELEVATIONS APPROVED
 AS PART OF THE LATEST SITE PLAN APPROVAL CALL OUT A
 PTFE COATED FIBERGLASS SHADE, WHILE THE PERMIT PLANS
 GENERICALLY STATE "FABRIC CANOPIES" IN THE TITLE BLOCK.
  
 PLEASE CONTACT ERIC SCHNEIDER @ (561) 822-1446.