Plan Review Details - Permit 13100472
Plan Review Stops For Permit 13100472
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-10-21 Cont ID  
Sent By jwitmer Date 2013-10-21 Time 09:08 Rev Time 0.00
Received By jwitmer Date 2013-10-21 Time 07:03 Sent To  
Notes
2013-10-21 07:46:42BUILDING PLAN REVIEW
 PERMIT: 13100472 SAKS 5TH AVENUE
 ADD: 1793 PALM BEACH LAKES # W413
 CONT: TO BE DETERMINED
 TEL: (618)514-2128
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MONDAY OCT. 21/2013
 ACTION: PROVISO
  
 PB OUTLET MALLS:
 BUILDING PROVISO:
 A LETTER FROM THE QUALIFIER OF BOTH THE SHELL
 CONTRACTOR (EMJ CORPORATION) AND TENANT BUILD-OUT
 CONTRACTOR MUST BE PROVIDED BEFORE TENANT BUILD-OUT
 PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) A401 BETWEEN THE DRESSING ROOMS AND SALES FLOOR THE
 PLANS ARE MISSING THE DIRECTIONAL EXIT LIGHTS AS WELL
 AS THE BATTERY BACK UP LIGHTING. 2010 FBC-B 1006.3.1 &
 1006.1.2.
  
 2) THE PLANS ARE ALSO MISSING COMPLIANCE WITH 2010
 FBC-B 907.2.7 OR SHOW COMPLIANCE WITH EXCEPTIONS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-07 Cont ID  
Sent By albarran Date 2013-11-07 Time 15:37 Rev Time 0.00
Received By albarran Date 2013-11-07 Time 14:32 Sent To I
Notes
2013-11-07 15:38:00SENT TO SH DESK

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-18 Cont ID  
Sent By scaldero Date 2013-10-18 Time 13:58 Rev Time 0.00
Received By scaldero Date 2013-10-18 Time 13:41 Sent To  
Notes
2013-10-18 13:58:21PERMIT #13100472
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-07 Cont ID  
Sent By shill Date 2013-11-07 Time 17:29 Rev Time 0.00
Received By shill Date 2013-10-17 Time 14:47 Sent To  
Notes
2013-10-18 16:49:57****EXPEDITED****
  
 10/17 ROUTED EXPEDITED REQUEST TO C40
  
2013-10-17 14:47:24ROUTED TO ZONING
2013-10-16 18:10:09INCOMING SENT TO C-40. JW

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By mricard Date 2013-10-31 Time 14:07 Rev Time 0.00
Received By mricard Date 2013-10-31 Time 13:34 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By lwagner Date 2013-10-28 Time 15:54 Rev Time 0.00
Received By lwagner Date 2013-10-28 Time 15:09 Sent To  
Notes
2013-10-28 15:41:27***PROVISO***
 PLUMBING PERMIT, APPLICATION, ISOMETRIC DRAWING FOR
 SANITARY, HOT AND COLD WATER, AND LOCATION OF WATER
 HEATER IS REQUIRED.
 CITY OF WEST PALM BEACH
 LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION
 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 107.3.5.1.3 PLUMBING

Review Stop Z ZONING