| 2013-10-17 15:19:15 | BUILDING PLAN REVIEW |
| | PERMIT: 13100441 |
| | ADD: 3310 WESTVIEW AVE |
| | CONT: T. H. MOTTLEY CONSTRCUCTION / CCC1327647 |
| | TEL: (561)502-1980 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: THURS., OCT. 17/2013 |
| | ACTION: BUILDING PROVISO |
| | |
| | PITCH: 3 1/2 / 12 |
| | |
| | PROVIDE COMPLIANCE WITH: 2010 FBC-R R905.2.7 |
| | UNDERLAYMENT APPLICATION. |
| | FOR ROOF SLOPES FROM TWO UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (17-PERCENT SLOPE), UP TO FOUR UNITS |
| | VERTICAL IN 12 UNITS HORIZONTAL (33-PERCENT SLOPE), TWO |
| | LAYERS OF UNDERLAYMENT COMPLYING WITH ASTM D 226 TYPE I |
| | OR TYPE II, ASTM D 4869 TYPE I OR TYPE II, OR ASTM D |
| | 6757 SHALL BE APPLIED IN THE FOLLOWING MANNER: |
| | |
| | 1. APPLY A MINIMUM 19-INCH-WIDE (483 MM) STRIP OF |
| | UNDERLAYMENT FELT PARALLEL WITH AND STARTING AT THE |
| | EAVES. |
| | |
| | 2. STARTING AT THE EAVE, APPLY 36-INCH-WIDE (914 MM) |
| | SHEETS OF UNDERLAYMENT OVERLAPPING SUCCESSIVE SHEETS 19 |
| | INCHES (483 MM). DISTORTIONS IN THE UNDERLAYMENT SHALL |
| | NOT INTERFERE WITH THE ABILITY OF THE SHINGLES TO SEAL. |
| | |
| | 3. END LAPS SHALL BE OFFSET BY 6 FEET (1829 MM). |
| | |
| | 4. CORROSION RESISTANT FASTENERS ARE TO BE APPLIED |
| | ALONG THE OVERLAP AT A MAXIMUM SPACING OF 36 INCHES |
| | (914 MM) ON CENTER. |
| | |
| | FOR ROOF SLOPES OF FOUR UNITS VERTICAL IN 12 UNITS |
| | HORIZONTAL (33-PERCENT SLOPE) OR GREATER, ONE LAYER OF |
| | UNDERLAYMENT COMPLYING WITH ASTM D 226 TYPE I OR TYPE |
| | II, ASTM D 4869 TYPE I OR TYPE II, OR ASTM D 6757 SHALL |
| | BE APPLIED IN THE FOLLOWING MANNER: |
| | |
| | 1. UNDERLAYMENT SHALL BE APPLIED SHINGLE FASHION, |
| | PARALLEL TO AND STARTING FROM THE EAVE AND LAPPED 2 |
| | INCHES (51 MM). |
| | |
| | 2. END LAPS SHALL BE OFFSET BY 6 FEET (1829 MM). |
| | |
| | 3. CORROSION RESISTANT FASTENERS ARE TO BE APPLIED |
| | ALONG THE OVERLAP AT A MAXIMUM SPACING OF 36 INCHES |
| | (914 MM) ON CENTER. |
| | |