Plan Review Details - Permit 13100435
Plan Review Stops For Permit 13100435
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-11-13 Cont ID  
Sent By skennedy Date 2013-11-13 Time 09:17 Rev Time 0.00
Received By skennedy Date 2013-11-13 Time 09:17 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-13 Cont ID  
Sent By skennedy Date 2013-11-13 Time 09:20 Rev Time 0.00
Received By skennedy Date 2013-10-31 Time 17:46 Sent To  
Notes
2013-11-07 21:10:3511/7 ON SH DESK
2013-11-06 07:51:3511/6 TO SK DESK
  
2013-10-31 17:46:47INCOMING SENT TO <$5K MECHANICAL BOX .JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-31 Cont ID  
Sent By jwitmer Date 2013-10-21 Time 17:45 Rev Time 0.00
Received By jwitmer Date 2013-10-15 Time 09:10 Sent To  
Notes
2013-10-15 09:10:55ROUTED TO MECHANICAL

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-11-04 Cont ID  
Sent By mricard Date 2013-11-04 Time 09:47 Rev Time 0.00
Received By mricard Date 2013-11-04 Time 09:47 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-11-13 Cont ID  
Sent By mricard Date 2013-10-21 Time   Rev Time 0.00
Received By skennedy Date 2013-10-21 Time 14:07 Sent To  
Notes
2013-11-13 09:19:38COMPLETED THE STATUS AS MRICARD HAD LEFT BLANK ON
 10/21/13.
2013-10-21 14:24:24INFORMATION SHEETS ARE ALSO REQUIRED FOR DUCT SMOKE
 DETECTORS, CO2 DETECTOR,
2013-10-21 14:12:16PROVIDE CUT SHEETS FOR THE EQUIPMENT, DAMPERS, PIPING
 ISOMETRIC, ACCESS PANEL/DOORS