Plan Review Details - Permit 13100413
Plan Review Stops For Permit 13100413
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-29 Cont ID  
Sent By rmcdouga Date 2014-01-29 Time 13:19 Rev Time 0.00
Received By rmcdouga Date 2014-01-23 Time 09:33 Sent To  
Notes
2014-01-29 14:35:25APPROVED WITH EXCEPTION.
  
 1) PRODUCT APPROVALS ARE REQUIRED FOR ALL OF THE
 WINDOWS AND DOORS THAT WERE INSTALLED WITHOUT PERMITS
 OR INSPECTIONS AND ALL OF THE ONES THAT ARE PROPOSED TO
 BE INSTALLED. SOME OF THE MIAMI DADE NOAS THAT WERE
 SUBMITTED FOR THE DOORS AND WINDOWS WERE EXPIRED, BUT
 HAVE CURRENT NOAS FOR THE SAME PRODUCT. THE NEW NOAS
 WERE PRINTED AND ATTACHED TO THE OLD ONES FOR THESE
 PRODUCTS. IF THERE IS NOT A CURRENT PRODUCT APPROVAL
 FOR THE ITEM AND YOU CAN LOCATE AN EXPIRED ONE, YOU
 HAVE THE OPTION OF APPLYING FOR A LOCAL PRODUCT
 APPROVAL BY SUBMITTING TWO SETS OF THE EXPIRED PRODUCT
 APPROVAL ALONG WITH A SIGNED AND SEALED RATIONAL
 ANALYSIS SHOWING THAT THE PRODUCT COMPLIES WITH THE
 2010 FLORIDA BUILDING CODE REQUIREMENTS FOR THE PRODUCT
 FOR REVIEW BY THE BUILDING OFFICIAL. ANOTHER OPTION
 WOULD BE TO REMOVE THE WINDOW OR DOOR AND REPLACE IT
 WITH ONE THAT HAS A CURRENT PRODUCT APPROVAL MEETING
 THE WIND PRESSURES AND AND IMPACT REQUIREMENTS OF THE
 2010 FBC, THE STRUCTURAL INSPECTOR WILL VERIFY IN THE
 FIELD THAT THE PRODUCTS AND INSTALLATIONS COMPLY WITH
 THE PRODUCT APPROVALS AND THE BUILDING CODES.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-20 Cont ID  
Sent By rmcdouga Date 2013-11-20 Time 13:25 Rev Time 0.00
Received By rmcdouga Date 2013-11-19 Time 18:49 Sent To  
Notes
2013-11-20 11:52:062010 FBC EXISTING BUILDING
 LEVEL 1 ALTERATION
  
 NOTE: THE PERMIT FOR THIS PROJECT HAS BEEN APPLIED FOR
 UNDER THE OWNER BUILDER EXEMPTION OF CHAPTER 489
 CONTRACTING. THESE ONE AND TWO FAMILY RESIDENCES ARE
 REQUIRED TO BE FOR THE OCCUPANCY OR USE OF THE OWNER
 AND CAN NOT BE OFFERED FOR SALE OR LEASE FOR ONE YEAR
 AFTER THE COMPLETION OF THE CONSTRUCTION.
  
  
 DENIED BY BUILDING
  
 1) SMOKE ALARMS ARE REQUIRED IN ALL 3 DWELLING UNITS.
 R314.3.1 ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 2) SUBMIT TWO COPIES OF PRODUCT APPROVALS AS REQUIRED
 BY DCA RULE 9N-3 FOR THE NEW SLIDING GLASS DOORS AND
 STRUCTURAL CONNECTORS.
  
 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. CITY
 AMENDMENTS 107.2.1
  
 4) SPECIFY THE WATER PROOFING SYSTEM (SUBMIT 2 COPIES
 OF PRODUCT APPROVALS) THAT WILL BE USED ON THE BALCONY
 AND PROVIDE A WALL TO DECK FLASHING DETAIL. CITY
 AMENDMENTS 107.2.1
  
 5) THE ELEVATIONS OF THE REAR BUILDING ON SHEET A-6 OF
 THE PLANS SHOW A PARTIALLY ENCLOSED PORCH THAT APPEARS
 TO BE CANTILEVERED. HAVE THIS CONDITION EVALUATED BY AN
 ENGINEER AND SUBMIT A SIGNED AND SEALED LETTER STATING
 THAT IT'S CONSTRUCTION WILL SAFELY SUPPORT ALL LIVE
 LOADS, DEAD LOADS, FLOOR LOADS, ROOF LOADS AND WIND
 LOADS AS REQUIRED BY THE FLORIDA BUILDING CODE. FBC
 R301.1
  
 6) CLARIFY THE ATTACHMENT OF THE EXISTING CONCRETE
 FOOTING TO THE NEW REINFORCED BLOCK FOUNDATION
 EXTENSION WALL SHOWN IN DETAIL 2 ON SHEET S-1. FBC R404
  
 7) THERE IS NO TIE BEAM WITH HORIZONTAL REINFORCEMENT
 SHOWN AT THE TOP OF THE 8" BLOCK RETAINING WALL IN
 DETAIL 6 ON SHEET S-1. PLEASE CLARIFY. FBC R404
  
 8) THE REPAIRED WALLS AND CEILINGS FORMING THE BUILDING
 ENVELOPE SHALL BE INSULATED AND THE REPLACED COMPONENTS
 (SUCH AS WATER HEATERS) ARE REQUIRED TO COMPLY WITH
 CHAPTER 402 OF THE FLORIDA BUILDING CODE ENERGY
 CONSERVATION.
  
 9) HOW WILL THE FOUNDATION WALLS AND CONCRETE FLOOR
 SLAB BE WATER-PROOFED TO PREVENT THE EXCAVATED AREAS
 FROM FILLING WITH WATER. FBC R406.2
  
 10) SHOW COMPLIANCE WITH FBC R408.4 FOR ACCESS TO UNDER
 FLOOR SPACE.
  
 11) SHOW COMPLIANCE WITH FBC R408.1 FOR UNDER FLOOR
 SPACE VENTILATION.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2014-01-25 Cont ID  
Sent By rmcdouga Date 2014-01-25 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2014-01-25 Time 07:11 Sent To  
Notes
2014-01-25 11:48:02PASSED WITH EXCEPTION. PLANS WERE RED-LINED. ALL
 ELECTRICAL WORK IS SUBJECT TO THE ELECTRICAL FIELD
 INSPECTOR'S APPROVAL.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-05 Cont ID  
Sent By albarran Date 2013-11-05 Time 16:34 Rev Time 0.00
Received By albarran Date 2013-11-05 Time 16:12 Sent To  
Notes
2013-11-05 16:47:50THE FLORIDA BUILDING CODE CHARACTERIZES ALTERATIONS AND
 REPAIRS TO BASICALLY THREE LEVELS, AND THESE ARE
 ACCORDING TO THE EXTENT OF WORK BEING DONE. EACH OF
 THOSE LEVELS HAS DIFFERENT REQUIREMENTS AND THEREFORE
 THE LEVEL OF ALTERATION HAS TO BE INDICATED ON THE
 PLANS. FURTHERMORE, REGARDLESS, OF THE EXTENT OR LEVEL
 OF ALTERATION, A SERVICE LOAD CALCULATION AND PANEL
 SCHEDULE NEED TO BE PROVIDED. YOU WILL ALSO NEED TO
 COMPLY WITH THE SMOKE DETECTOR REGULATIONS.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2013-11-18 Cont ID  
Sent By fmittner Date 2013-11-18 Time 16:35 Rev Time 0.00
Received By fmittner Date 2013-11-18 Time 16:35 Sent To  
Notes
2013-11-18 16:52:18AFTER REVIEWING PHOTOGRAPHS, EXTERIOR WORK IS NOT
 VISIBLE FROM PUBLIC ROW AND COMPATIBLE.
2013-11-18 16:37:05EXTERIOR ALTERATIONS MUST COMPLY WITH THE HISTORIC
 PRESERVATION SECTION OF THE ZLDRS. THESE PLANS DO NOT
 CLEARLY DEPICT THE BEFRORE AND AFTER EXTERIO WORK. A
 CERTIFICATE OF APPROPRIATENESS FORM NEEDS TO BE
 SUBMITTED. QUESTIONS CONTACT FRIEDERIKE MITTNER, CITY
 HISTORIC PRESERVATION PLANNER AT 822-1457.
  
2013-10-18 13:17:0210/18/13

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-01-29 Cont ID  
Sent By rmcdouga Date 2014-01-29 Time 13:20 Rev Time 0.00
Received By rmcdouga Date 2014-01-03 Time 13:52 Sent To  
Notes
2014-01-04 13:53:13BLDG RESUB TO RM DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-25 Cont ID  
Sent By rmcdouga Date 2014-01-25 Time 11:45 Rev Time 0.00
Received By rmcdouga Date 2013-12-18 Time 15:40 Sent To  
Notes
2013-12-18 15:40:48SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-20 Cont ID  
Sent By rmcdouga Date 2013-11-20 Time 13:25 Rev Time 0.00
Received By rmcdouga Date 2013-10-11 Time 10:47 Sent To  
Notes
2013-10-12 10:51:45PLANS WERE ROUTED TO R17 BOX FOR PLAN REVIEW.
2013-10-12 10:49:54R17

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2014-01-25 Cont ID  
Sent By rmcdouga Date 2014-01-25 Time 11:42 Rev Time 0.00
Received By rmcdouga Date 2014-01-25 Time 07:12 Sent To  
Notes
2014-01-25 11:44:15NO MECHANICAL PLANS WERE SUBMITTED. A SEPARATE PERMIT
 APPLICATION, PLANS AND REVIEW IS REQUIRED FOR A
 MECHANICAL PERMIT.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-11-20 Cont ID  
Sent By mricard Date 2013-11-04 Time 10:36 Rev Time 0.00
Received By rmcdouga Date 2013-11-04 Time 10:36 Sent To P
Notes
2013-11-20 15:15:422010 FBC
  
 DENIED BY MECHANICAL
  
 THE AIR HANDLER AND CONDENSING UNIT THE SECOND FLOOR
 DWELLING UNIT IN THE REAR BUILDING WERE REPLACED
 WITHOUT PERMITS. A MECHANICAL SUB- PERMIT FOR AN A/C
 CHANGE OUT IS REQUIRED WITH TWO COPIES OF THE AC CHANGE
 OUT FORM.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2014-01-25 Cont ID  
Sent By rmcdouga Date 2014-01-25 Time 11:44 Rev Time 0.00
Received By rmcdouga Date 2014-01-25 Time 11:44 Sent To  
Notes
2014-01-25 11:45:05PLANS WERE RED-LINED TO SHOW CODE COMPLIANCE.

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-11-05 Cont ID  
Sent By rmcdouga Date 2013-11-20 Time 15:10 Rev Time 0.00
Received By lwagner Date 2013-11-05 Time 08:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-11-18 Cont ID  
Sent By fmittner Date 2013-11-18 Time 16:48 Rev Time 0.00
Received By fmittner Date 2013-11-18 Time 16:48 Sent To B
Notes
***NONE***