Plan Review Details - Permit 13100297
Plan Review Stops For Permit 13100297
Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2014-08-26 Cont ID  
Sent By jwitmer Date 2014-08-26 Time 12:27 Rev Time 0.00
Received By jwitmer Date 2014-08-23 Time 15:10 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2014-08-05 Cont ID  
Sent By jwitmer Date 2014-08-04 Time 16:20 Rev Time 0.00
Received By jwitmer Date 2014-08-04 Time 16:20 Sent To  
Notes
2014-08-04 16:25:58BUILDING PLAN REVIEW
 PERMIT: 13100297 BOILER BLDG VERTICAL
 ADD: 6651 N JOG RD
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 4TH REVIEW
 DATE: MONDAY AUGUST 04/ 2014
 ACTION: DENIED.
 REVIEWED BY BUILDING OFFICIAL BEFORE FINAL ACTION WAS
 TAKEN!!!!
  
 1) COMPLIED. SHEET 0647 -300-S6-000 THE WIND DESIGN
 STATES THAT IT IS DESIGNED TO THE 2010 FBC, THE PLANS
 DOES NOT STATE IF THE PRESSURES ARE LISTED AS VULT OR
 VASD? RESPONSE INDICATES THEY ARE VALT.
  
 2) THIS COMMENT IS DEALING WITH WALL PANELS NOT THE FL
 APPROVAL (FL 12760) WHICH DEALS WITH THE LITE PANEL.
 PRESSURES ARE LOW FOR THE INTERIOR ZONE # 4 AND END
 ZONE # 5. BOILER ELEVATION SHEET0648-300-S6-550
 PROVIDES THE SPACING OF THE GIRT/ PURLINS AVERAGE
 BETWEEN 4' & 5' WITH THE EXCEPTION OF THE AT ELEVATION
 169 TO 178 THE SPACING DROPS TO 3' BETWEEN PURLINS. THE
 BUTLER NOA 13-0923.07 BUTLER II WALL PANEL LIST THE
 INTERIOR WALL ZONES WITH A 5'-0" SPACING BETWEEN THE
 PURLINS, AND AT THE CORNER ZONES A 2'-6" SPACING.
 PLEASE SUBMIT THE DESIGN REVIEW FOR THE MULTILE SPANS,
 THIS PRODUCT APPROVAL ON SHEET # 7 HAS A 3 SPAN AND 4
 SPAN WITH ASSOCIATED PRESSURES WHICH ARE STILL LOWER
 THAN THE PRESSURES FOUND ON SHEET 0647-300-56-000.
  
 3) LITE PANEL. THE PRODUCT APPROVAL SUBMITTED BUTLER FL
 12760 BUTLER II LITE PANEL PRESSURES ARE A VASD +52.5/
 52.5. VIEW A INDICATES THAT INTERMEDIATE GIRTS MAY BE
 REQUIRED IF PRESSURES ARE HIGHER. 2010 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.41 COMPONENTS &
 CLADDING.
  
 4) COMPLIED.
  
 5) RESPONSE TO THE ROOFING NOA 10-0901IS THIS WAS THE
 WRONG PRODUCT APPROVAL SUBMITTED. PLEASE REMOVE THIS
 NOA FROM THE SUBMITTAL IF NOT TO BE INSTALLED. SHEET
 0123-300-S22-026 ROOF REFERANCE SHEET SHOWS THE GIRTS
 AT 5'-0" AND 4'-8" O. C. PLEASE REVIEW THE SUBMITTED
 PRODUCT APPROVAL FOR THE ROOF STEEL ROOF PANELS NOA
 10-0901.20 SEE SHEET 1 OF 6 THE MAXIMUM PURLIN SPANS
 ARE EXCEEDED , DEPENDING ON THE SPACING OF THE PURLINS
 THE PRESSURES MAY OR MAY NOT WORK. ALSO THE PRESSURES
 ARE LOW EVEN WHEN AND IF THE ASSUMED PRESSURES ARE VULT
 EVEN AT VASD THEY ARE LOW.
  
 6) UPDATE THE HEAVY STRUCTURES LETTER DATED 1-10-2014
 AND ALSO REMOVE THE REFERANCE TO THE ROOF PANEL BUTLER
 MANUFACTURING NOA 10-0901.20 FROM THE LETTER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2014-07-01 Time 09:30 Sent To  
Notes
2014-07-01 12:32:08BUILDING PLAN REVIEW
 PERMIT: 13100297 BOILER BLDG VERTICAL
 ADD: 6651 N JOG RD
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 3RD REVIEW
 DATE: TUES. JULY 01/ 2014
 ACTION: DENIED
  
 1) SHEET 0647 -300-S6-000 THE WIND DESIGN STATES THAT
 IT IS DESIGNED TO THE 2010 FBC, THE PLANS DOES NOT
 STATE IF THE PRESSURES ARE LISTED AS VULT OR VASD?
 PRODUCT APPROVALS ARE LISTED AS VASD. 107.2.1.3
 ADDITIONAL INFORMATION REQUIRED. FOR THE PURPOSE OF
 THIS REVIEW IT IS ASSUMED THE PRESSURES ARE VULT, IF
 NOT IT IS OF A GREATER CONCERN.
  
 2) BOILER ELEVATION SHEET0648-300-S6-550 PROVIDES THE
 SPACING OF THE GIRT/ PURLINS AVERAGE BETWEEN 4' & 5'
 WITH TTHTE EXCEPTION OF THE
 AT ELEVATION 169 TO 178 THE SPACING DROPS TO 3' BETWEEN
 PURLINS. THE BUTLER NOA 13-0923.07 BUTLER II WALL PANEL
 LIST THE INTERIOR WALL ZONES WITH A 5'-0" SPACING
 BETWEEN THE PURLINS, AND AT THE CORNER ZONES A 2'-6"
 SPACING. ALSO THE PRESSURES ARE LOW EVEN WHEN AND IF
 THE ASSUMED PRESSURES ARE VULT EVEN AT VASD THEY ARE
 LOW.
  
 3) THE PRODUCT APPROVAL SUBMITTED BUTLER FL 12760
 BUTLER II LITE PANEL PRESSURES ARE A VASD +52.5/ 52.5
 VIEW A INDICATES THAT INTERMEDIATE GIRTS MAY BE
 REQUIRED IF PRESSURES ARE HIGHER.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
  
 4) SHEET 0590 300-A2-101 SHOWS WALL LOUVERS, TO DATE NO
 PRODUCT APPROVALS WERE SUBMITTED FOR THE STORM PROOF
 LOUVERS.
 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING. FLORIDA DEPARTMENT OF COMMUNITY
 AFFAIRS RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF
 PRODUCTS OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE
 PRODUCT APPROVALS:
 (31)(A) (C) WALL LOUVERS,
  
 5) SHEET 0123-300-S22-026 ROOF REFERANCE SHEET SHOWS
 THE GIRTS AT 5'-0" AND 4'-8" O. C. PLEASE REVIEW THE
 SUBMITTED PRODUCT APPROVAL FOR THE ROOF STEEL ROOF
 PANELS NOA 10-0901.20 SEE SHEET 1 OF 6 THE MAXIMUM
 PURLIN SPANS ARE EXCEEDED , DEPENDING ON THE SPACING OF
 THE PURLINS THE PRESSURES MAY OR MAY NOT WORK. ALSO THE
 PRESSURES ARE LOW EVEN WHEN AND IF THE ASSUMED
 PRESSURES ARE VULT EVEN AT VASD THEY ARE LOW.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-04-25 Cont ID  
Sent By jwitmer Date 2014-04-25 Time 17:03 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 12:37 Sent To  
Notes
2014-04-25 17:03:51STEVE, I TELEPHONED MIKE ON 4/16/2014 THAT HE HAD
 ISSUES WITH THE EXTERIOR VERTICAL PRODUCT APPROVALS AS
 WELL AS THE ROOFING FRAMING MEMBERS, THERE WAS NO ROOF
 FRAMING PLANS. I'M COPYING MIKE SINCE I'VE NOT HEARD
 FROM HIM ON THIS REVISION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 DEVELOPMENT SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-14 Cont ID  
Sent By jwitmer Date 2013-11-14 Time 09:28 Rev Time 0.00
Received By jwitmer Date 2014-04-16 Time 12:36 Sent To  
Notes
2013-11-14 09:28:27BUILDING PLAN REVIEW
 PERMIT: 13100297 BOILER BLDG VERTICAL
 ADD: 6651 N JOG RD
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. NOV. 14/ 2013
 ACTION: DENIED
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) , WALL LOUVERS, PANEL WALLS
 (D) ROOFING PRODUCTS AND ASSEMBLIES, ROOF VENTS, ROOF
 HATCHES
  
 3) ROOF TOP STAIRS AND GAURDRAILS, 2010 FBC-B 1009.13,
 1012, HANDRAILS & 1013.3 GAURDRAILS.
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL 561-805-6715
 E-MAIL: JWITMER @WPB.ORG
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-23 Cont ID  
Sent By albarran Date 2013-12-23 Time 08:58 Rev Time 0.00
Received By albarran Date 2013-12-20 Time 10:08 Sent To  
Notes
2013-12-23 08:59:30CONDITIONALLY APPROVED BY ELECTRIC PURSUANT TO THE
 ATTACHED PROVISIOS
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-05-21 Cont ID  
Sent By wjolin Date 2014-05-21 Time 16:40 Rev Time 0.00
Received By wjolin Date 2014-05-21 Time 16:40 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-04-17 Cont ID  
Sent By wjolin Date 2014-04-17 Time 11:26 Rev Time 0.00
Received By wjolin Date 2014-04-17 Time 09:53 Sent To  
Notes
2014-04-17 11:26:166651 NORTH JOG ROAD - BOILER BUILDING
 TRACKING #13100297
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 RESPONSE COMMENT: COULD NOT LOCATE LIFE SAFETY PLANS AS
 INDICATED IN THE RESPONSE LETTER. PROVIDE PLANS
 INDICATING THE FIRE RESISTANCE RATING OF THE VERTICAL
 SHAFTS (EXIT STAIRS, ELEVATORS). A DOOR SCHEDULE HAS
 BEEN PROVIDED; HOWEVER, NO FLOOR PLANS INDICATING A
 DOOR TAG COULD BE LOCATED. PROVIDE PLANS INDICATING THE
 TRAVEL DISTANCE TO EXIT STAIRS.
  
 ORIGINAL COMMENT: PROVIDE A LIFE SAFETY PLAN SHOWING
 ALL EXITS, EXIT SIGNS, FIRE RATED WALLS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVE, FIRE
 EXTINGUISHERS,L ETC.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-26 Cont ID  
Sent By wjolin Date 2013-11-26 Time 14:34 Rev Time 0.00
Received By wjolin Date 2013-11-26 Time 10:32 Sent To  
Notes
2013-11-26 14:34:266651 NORTH JOG ROAD - BOILER BUILDING
 TRACKING #13100297
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A1-100 IS THE ROOF PLAN; HOWEVER, THERE DO NOT
 APPEAR TO BE ANY ARCHITECTURAL FLOOR/PLATFORM PLANS
 PROVIDED BELOW THE ROOF LEVEL. PROVIDE A LIFE SAFETY
 PLAN SHOWING ALL EXITS, EXIT SIGNS, FIRE RATED WALLS,
 EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF
 TRAVE, FIRE EXTINGUISHERS,L ETC.
  
 CONFIRM BOILER FURNACES ARE NOT OIL-FIRED; OTHERWISE
 PER NFPA 850 SECTION 7.5.1.1 BOILER-FURNACES WITH
 MULTIPLE OIL-FIRED BURNERS OR THAT USE OIL FOR IGNITION
 SHOULD BE PROTECTED WITH AUTOMATIC SPRINKLER, WATER
 SPRAY, FOAM, FOAM-WATER SPRINKLER SYSTEMS, OR
 COMPRESSED AIR FOAM SYSTEMS COVERING THE BURNER FRONT
 OIL HAZARD.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 16:52 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 14:09 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2014-08-26 Cont ID  
Sent By jwitmer Date 2014-08-26 Time 12:28 Rev Time 0.00
Received By jwitmer Date 2014-08-18 Time 07:57 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2014-08-05 Cont ID  
Sent By jwitmer Date 2014-08-05 Time 12:11 Rev Time 0.00
Received By jwitmer Date 2014-07-24 Time 10:52 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-01 Cont ID  
Sent By jwitmer Date 2014-07-01 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2014-06-03 Time 07:44 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-04-25 Cont ID  
Sent By jwitmer Date 2014-04-25 Time 17:03 Rev Time 0.00
Received By jwitmer Date 2014-03-19 Time 07:56 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-26 Cont ID  
Sent By shill Date 2013-12-23 Time 11:16 Rev Time 0.00
Received By shill Date 2013-10-11 Time 14:49 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-09-10 Cont ID  
Sent By skennedy Date 2014-09-10 Time 16:51 Rev Time 0.00
Received By skennedy Date 2014-09-10 Time 16:51 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-12 Cont ID  
Sent By rregueir Date 2013-11-12 Time 14:49 Rev Time 0.00
Received By rregueir Date 2013-11-12 Time 14:49 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-11-19 Cont ID  
Sent By lwagner Date 2013-11-19 Time 09:32 Rev Time 0.00
Received By lwagner Date 2013-11-19 Time 09:25 Sent To  
Notes
2013-11-19 09:32:57NO PLUMBING FOUND ON PLANS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-09-29 Cont ID  
Sent By skennedy Date 2014-09-29 Time 14:05 Rev Time 0.00
Received By skennedy Date 2014-09-26 Time 16:00 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-11-18 Cont ID  
Sent By eschenid Date 2013-11-18 Time 12:37 Rev Time 0.50
Received By eschneid Date 2013-11-18 Time 12:37 Sent To  
Notes
2013-11-13 14:37:3011/13/13