Plan Review Details - Permit 13100296
Plan Review Stops For Permit 13100296
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-03-13 Cont ID  
Sent By jwitmer Date 2014-03-13 Time 18:58 Rev Time 0.00
Received By jwitmer Date 2014-03-13 Time 18:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-14 Cont ID  
Sent By jwitmer Date 2013-11-14 Time 08:46 Rev Time 0.00
Received By jwitmer Date 2013-11-14 Time 08:02 Sent To  
Notes
2013-11-14 08:46:56BUILDING PLAN REVIEW
 PERMIT: 13100296
 ADD: 6651 N JOG RD
 CONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: THURS. NOV. 14/ 2013
 ACTION: DENIED
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
  
 JAMES WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL 561-805-6715
 E-MAIL: JWITMER @WPB.ORG
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-12-19 Cont ID  
Sent By albarran Date 2013-12-19 Time 15:02 Rev Time 0.00
Received By albarran Date 2013-12-19 Time 11:21 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-03-04 Cont ID  
Sent By wjolin Date 2014-03-04 Time 16:49 Rev Time 0.00
Received By wjolin Date 2014-02-27 Time 14:23 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-26 Cont ID  
Sent By wjolin Date 2013-11-26 Time 15:19 Rev Time 0.00
Received By wjolin Date 2013-11-26 Time 14:37 Sent To  
Notes
2013-11-26 15:19:506651 NORTH JOG ROAD - REFUSE BUILDING
 TRACKING #13100296
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 COULD NOT LOCATE A LIFE SAFETY PLAN FOR THE CONTROL
 ROOM.
  
 PER NFPA 101 SECTION 40.2.5.1 ANCILLARY FACILITIES: NEW
 ANCILLARY FACILITIES SHALL BE ARRANGED TO ALLOW TRAVEL
 IN INDEPENDENT DIRECTIONS AFTER LEAVING THE ANCILLARY
 FACILITY SO THAT BOTH MEANS OF EGRESS PATHS DO NOT
 BECOME COMPROMISED BY THE SAME FIRE OR SIMILAR
 EMERGENCY.
  
 A.40.2.5.1.1 ANCILLARY FACILITIES LOCATED WITHIN
 INDUSTRIAL OCCUPANCIES MIGHT INCLUDE ADMINISTRATIVE
 OFFICE, CONTROL, AND EMPLOYEE SERVICE FACILITIES THAT
 ARE INCIDENTAL TO THE PREDOMINANT INDUSTRIAL FUNCTION
 AND ARE OF SUCH SIZE THAT SEPARATE OCCUPANCY
 CLASSIFICATION IS NOT WARRANTED.
  
 40.2.5.1.2 NEW ANCILLARY FACILITIES IN SPECIAL-PURPOSE
 INDUSTRIAL OCCUPANCIES WHERE DELAYED EVACUATION IS
 ANTICIPATED SHALL HAVE NOT LESS THAN A 2-HOUR FIRE
 RESISTANCE?RATED SEPARATION FROM THE PREDOMINANT
 INDUSTRIAL OCCUPANCY, AND SHALL HAVE ONE MEANS OF
 EGRESS THAT IS SEPARATED FROM THE PREDOMINANT
 INDUSTRIAL OCCUPANCY BY 2-HOUR FIRE RESISTANCE-RATED
 CONSTRUCTION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-03-13 Cont ID  
Sent By jwitmer Date 2014-03-13 Time 18:59 Rev Time 0.00
Received By jwitmer Date 2014-02-06 Time 16:49 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-12-26 Cont ID  
Sent By shill Date 2013-12-26 Time 11:17 Rev Time 0.00
Received By shill Date 2013-10-11 Time 14:42 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-12 Cont ID  
Sent By rregueir Date 2013-11-12 Time 14:43 Rev Time 0.00
Received By rregueir Date 2013-11-12 Time 14:43 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-11-19 Cont ID  
Sent By lwagner Date 2013-11-19 Time 09:54 Rev Time 0.00
Received By lwagner Date 2013-11-19 Time 09:35 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2014-04-07 Cont ID  
Sent By skennedy Date 2014-04-07 Time 10:46 Rev Time 0.00
Received By skennedy Date 2014-04-04 Time 10:46 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status P Date 2013-11-18 Cont ID  
Sent By eschneid Date 2013-11-18 Time 13:30 Rev Time 0.50
Received By eschneid Date 2013-11-18 Time 13:30 Sent To  
Notes
2013-11-18 13:30:18THE ELEVATION SHANGE SHALL BE REFLECTED ON THE
 "AS-BUILT" MINOR SITE PLAN
 AMENDMENT PRIOR TO THE C.O.
2013-11-13 14:30:5511/13/13