Plan Review Details - Permit 13100292
Plan Review Stops For Permit 13100292
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2014-10-02 Time 15:19 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2014-08-26 Cont ID  
Sent By jwitmer Date 2014-08-26 Time 11:45 Rev Time 0.00
Received By jwitmer Date   Time   Sent To  
Notes
2014-08-26 11:25:23BUILDING PLAN REVIEW
 PERMIT: 13100292
 ADD: 6651 N JOG RD
 CONT:
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2ND REVIEW
 DATE: YUES. AUG. 26/2014
 ACTION: DENIED
  
 FIRE WATER TANK
 1) 1ST TIME COMMENT, SHEET 1230-1 REV #5 THERE SEEMS TO
 BE A DISCREPANCY IN THE WIND DESIGN CRITERIA FOR THE
 FIRE WATER TANK.
 THIS PERMIT IS UNDER THE 2010 FBC, THE PLANS INDICATE A
 140 MPH 3 SECOND GUST BUT NOT MENTIONED IF THIS IS VULT
 OR VASD.
 THE SECOND ISSUE THAT COMPLACATES THINGS IS THE
 IMPORTANCE FACTOR CATEGORY I BUILDINGS AND STRUCTURES
 WITH A CATEGORY I CLASSIFICATION ARE DERATED INTHE WIND
 SPEED MAPS BUT A IMPORTANCE FACTOR OF 1.15. IS WHAT IS
 USED FOR TYPE III OR IV STRUCTURES ESSENTIAL FACILITIES
 LIKE FIRE FIGHTING EQUIPMENT & STRUTURES SEE TABLE
 1604.5 RISK CATEGORIES FOR BUILDINGS AND STRUCTURES.
  
 SINCE THIS TANK IS FOR THE FIRE WATER STORAGE TANK THE
 BUILDING RISK CATEGORY SHOULD BE RISK CATEGORY III THE
 IMPORTANCE FACTOR OF 1.15 IS BUILT INTO THE THE
 DETERMINATION OF WIND LOADS 1609.1.1 AND FIGURE 1609.B,
 THE VULT 180 MPH 3 SECOND GUST SHOULD BE THE WIND
 DESIGN CRITERIA FOR THE FIRE WATER STORAGE TANK. PLEASE
 CORRECT PLANS.
  
  
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-11-14 Cont ID  
Sent By jwitmer Date 2013-11-14 Time 07:45 Rev Time 0.00
Received By jwitmer Date 2013-11-14 Time 07:28 Sent To  
Notes
2013-11-14 07:47:11PLEASE SEE FIRE REVIEWERS COMMENTS, THE BUILDING CODE
 REFERS TO THE FIRE PREVENTION CODE.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-08-12 Cont ID  
Sent By wjolin Date 2014-08-12 Time 17:28 Rev Time 0.00
Received By wjolin Date 2014-08-12 Time 10:47 Sent To  
Notes
2014-08-12 17:12:306651 NORTH JOG ROAD - 500,000 GALLON FIRE WATER TANK
 TRACKING #13100293
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 NOTE: DRAWING 700-FP-12 SHOWS THE FIRE PUMP, PUMP
 CONTROLLERS, SUCTION PIPING, ETC; HOWEVER, A SEPARATE
 PERMIT WILL BE NEEDED FOR THIS EQUIPMENT PACKAGE.
 SHEET 700-FP-12: PER NFPA 20 SECTION 5.14.6.3.2, ELBOWS
 AND TEES WITH A CENTERLINE PLANE PARALLEL TO A
 HORIZONTAL SPLIT-CASE PUMP SHAFT SHALL NOT BE PERMITTED
 UNLESS THE DISTANCE BETWEEN THE FLANGES OF THE PUMP
 SUCTION INTAKE AND THE ELBOW AND TEE IS GREATER THAN 10
 TIMES THE SUCTION PIPE DIAMETER.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-13 Cont ID  
Sent By wjolin Date 2013-11-13 Time 11:02 Rev Time 0.00
Received By jwitmer Date 2013-11-14 Time 07:28 Sent To  
Notes
2013-11-13 12:44:546651 NORTH JOG ROAD - 500,000 GALLON FIRE WATER TANK
 TRACKING #13100293
 PERMIT #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE APC BUILDING MAY CONSTITUTE A FIRE EXPOSURE TO FIRE
 WATER HOLDING TANK. PER NFPA 22: LOCATION OF TANKS.
 4.2.1 THE LOCATION OF TANKS SHALL BE SUCH THAT THE TANK
 AND STRUCTURE ARE NOT SUBJECT TO FIRE EXPOSURE.
 4.2.1.1 IF LACK OF YARD ROOM MAKES THIS IMPRACTICABLE,
 THE EXPOSED STEEL WORK SHALL BE SUITABLY FIREPROOFED OR
 SHALL BE PROTECTED BY OPEN SPRINKLERS.
 4.2.1.2 FIREPROOFING SHALL BE PROVIDED FOR STEELWORK
 WITHIN 20 FEET OF EXPOSURES, BUILDINGS OR WINDOWS, AND
 DOORS FROM WHICH FIRE MIGHT ISSUE.
  
 4.2.2 FIREPROOFING, WHERE REQUIRED, SHALL HAVE A FIRE
 RESISTANCE RATING OF NOT LESS THAN 2 HOURS.
  
 4.5.2 APPROVAL OF LAYOUTS.
 4.5.2.1 COMPLETE INFORMATION REGARDING THE TANK PIPING
 ON THE TANK SIDE OF THE CONNECTION TO THE YARD OR
 SPRINKLER SYSTEM SHALL BE SUBMITTED TO THE AUTHORITY
 HAVING JURISDICTION FOR APPROVAL.
 4.5.2.2 THE INFORMATION SUBMITTED SHALL INCLUDE THE
 FOLLOWING:
 (1) SIZE AND ARRANGEMENT OF ALL PIPES
 (2) SIZE, LOCATION, AND TYPE OF ALL VALVES, AND OTHER
 ACCESSORIES
 (3) STEAM PRESSURES AVAILABLE AT THE HEATER
 (4) ARRANGEMENT OF, AND FULL INFORMATION REGARDING, THE
 STEAM SUPPLY AND RETURN SYSTEM TOGETHER WITH PIPE SIZES
 (5) DETAILS OF CONSTRUCTION OF THE FROSTPROOF CASING
 (6) WHERE HEATING IS REQUIRED, HEAT LOSS CALCULATIONS
 (7) STRUCTURAL DRAWINGS AND CALCULATIONS
 (8) SEISMIC BRACING DETAILS AND CALCULATIONS
 (9) OPERATIONAL SETTINGS AND SEQUENCE OF OPERATION
 (10) MONITORING EQUIPMENT AND CONNECTIONS
 (11) UNDERGROUND DETAILS INCLUDING FOUNDATIONS,
 COMPACTION,
 AND BACKFILL DETAILS AND CALCULATIONS
  
 4.8 LIGHTNING PROTECTION. TO PREVENT LIGHTNING DAMAGE
 TO TANKS, PROTECTION SHALL BE INSTALLED IN ACCORDANCE
 WITH SECTION 4.4 OF NFPA 780.
  
 14.2.12 CONTROLLING VALVES.
 14.2.12.1 A LISTED GATE VALVE SHALL BE PLACED IN THE
 DISCHARGE PIPE ON THE YARD SIDE OF THE CHECK VALVE
 BETWEEN THE CHECK VALVE AND ANY CONNECTION OF THE TANK
 DISCHARGE TO OTHER PIPING.
  
 14.2.12.3 A LISTED INDICATING CONTROL VALVE SHALL BE
 PLACED IN THE DISCHARGE PIPE ON THE TANK SIDE OF THE
 CHECK VALVE.
  
 14.2.13 ANTI-VORTEX PLATE ASSEMBLY.
 14.2.13.1 WHERE A TANK IS USED AS THE SUCTION SOURCE
 FOR A FIRE PUMP, THE DISCHARGE OUTLET SHALL BE EQUIPPED
 WITH AN ASSEMBLY THAT CONTROLS VORTEX FLOW.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-10-02 Cont ID  
Sent By jwitmer Date 2014-10-02 Time 15:19 Rev Time 0.00
Received By jwitmer Date 2014-09-24 Time 15:15 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-08-27 Cont ID  
Sent By cpuell Date 2014-08-27 Time 09:29 Rev Time 0.00
Received By cpuell Date 2014-07-29 Time 05:14 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-27 Cont ID  
Sent By rregueir Date 2013-11-27 Time 14:18 Rev Time 0.00
Received By rregueir Date 2013-10-11 Time 10:57 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-27 Cont ID  
Sent By rregueir Date 2013-11-27 Time 14:16 Rev Time 0.00
Received By rregueir Date 2013-11-27 Time 14:16 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 3 Status F Date 2015-03-03 Cont ID  
Sent By skennedy Date 2015-03-03 Time 13:36 Rev Time 0.00
Received By skennedy Date 2015-02-27 Time 16:49 Sent To  
Notes
2015-03-03 13:37:02SEE PREVIOUS COMMENTS.

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 2 Status F Date 2015-02-05 Cont ID  
Sent By skennedy Date 2015-02-05 Time 08:49 Rev Time 0.00
Received By skennedy Date 2015-02-04 Time 16:54 Sent To  
Notes
2015-02-05 09:00:432ND REVIEW: FBC 2010
  
 PEDDS HAVE NOT BEEN SUBMITTED FOR THE FOLLOWING SHEETS
 BY ERECTED STEEL PRODUCTS, 551.4, SCANNED IMAGE FOR
 THEIN WIN, PE 65772, PEDDS HAVE NOT BEEN SUBMITTED FOR
 THE FOLLOWING SHEETS BY ERECTED STEEL PRODUCTS, 551,
 550, HOWEVER PAPER COPIES FHAVE BEEN SUBMITTED AND
 INCLUDE A SIGNED RAISED SEAL FROM AN ALABAMA ENGINEER
 AND ARE NOT THEREFORE ACCEPTABLE.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status F Date 2015-01-05 Cont ID  
Sent By skennedy Date 2015-01-05 Time 11:18 Rev Time 0.00
Received By skennedy Date 2014-12-31 Time 19:00 Sent To  
Notes
2015-01-05 11:19:34THERE IS NO SIGNATURE REPORT FOR JAMES HENRY WILLIAMS,
 PE. ADDITIONALLY, THERE ARE NO PEDDS SUBMITTED FOR 3
 SHEETS BY ERECTED STEEL PRODUCTS.
  
 STEVEN KENNEDY, CBO
 CHIEF PLANS EXAMINER
 (561) 805-6710
 [email protected]
  

Review Stop Z ZONING
Rev No 2 Status P Date 2014-08-20 Cont ID  
Sent By eschneid Date 2014-08-20 Time 08:48 Rev Time 0.25
Received By eschneid Date 2014-08-18 Time 16:48 Sent To  
Notes
2014-08-18 16:48:48SITE PLAN SUBMITTED

Review Stop Z ZONING
Rev No 1 Status F Date 2013-11-18 Cont ID  
Sent By eschneid Date 2013-11-18 Time 12:45 Rev Time 0.25
Received By eschneid Date 2013-11-18 Time 12:45 Sent To  
Notes
2013-11-18 12:50:11FAILED
  
 1) PROVIDE A SITE PLAN SHOWING THE LOCATION OF THE FIRE
 WATER STORARE TANK.
  
 2) PLANS ARE OKAY FOR ZONING OTHERWISE.
2013-11-13 14:36:0411/13/13