Plan Review Details - Permit 13100146
Plan Review Stops For Permit 13100146
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-23 Cont ID  
Sent By jwitmer Date 2013-11-23 Time 08:45 Rev Time 0.00
Received By jwitmer Date 2013-11-23 Time 08:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-23 Cont ID  
Sent By jwitmer Date 2013-10-23 Time 11:32 Rev Time 0.00
Received By jwitmer Date 2013-10-23 Time 10:56 Sent To  
Notes
2013-10-23 11:32:48BUILDING PLAN REVIEW
 PERMIT: 13100146
 ADD: 1751 PALM BEACH LAKES # E119
 CONT: TO BE DETERMINED
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. OCT. 23/ 2013
 ACTION: DENIED
  
 1) PB OUTLET MALLS: A LETTER FROM THE QUALIFIER OF BOTH
 THE SHELL CONTRACTOR (EMJ CORPORATION) AND TENANT
 BUILD-OUT CONTRACTOR MUST BE PROVIDED BEFORE TENANT
 BUILD-OUT PERMIT CAN BE ISSUED, IF THE TENANT BUILD-OUT
 CONTRACTOR WISHES TO START WORK BEFORE THE SHELL WORK
 HAS RECEIVED A CERTIFICATE OF COMPLETION, AGREEING THEY
 WILL WORK TOGETHER TO ACHIEVE CODE COMPLIANCE. THESE
 DOCUMENTS WILL NEED TO BE SIGNED BY THE QUALIFIER AND
 NOTARIZED.
  
 2) COVER SHEET:
  
 2A) CODE ANALYSIS: INDICATES THIS PROJECT WAS DESIGNED
 TO THE 2009 IBC, IPC & IMC, THE CURRENT FAMILY OF CODES
 WERE ADOPTED STATEWIDE IN FLORIDA MARCH 15/ 2012, 2010
 FLORIDA BUILDING CODE, BUILDING, PLUMBING, MECHANICAL &
 FIRE PREVENTION CODE.
  
 2B) CODE ANALYSIS INDICATES THE OCCUPANT LOAD IS A
 TOTAL OF 203, IN BOTH CASES THE MERCANTILE AND
 STOCKROOM THE ACTUAL NUMBER OF OCCUPANTS WAS ROUNDED
 DOWN, YOU CAN'T ONLY HAVE A PORTION OF A OCCUPANT,
 ALWAYS ROUND UP, 2010 FBC-B 1004.1.1 , TALBE L004.1.1
 AND FL BOAF INFORMAL INTERPRETATION # 5479.
  
 3) THE PLANS LACK A LIFE SAFETY SHEET, SHEET A-1
 INDICATES 2 EGRESS DOORS, ONE EXIT PATH WILL BE THROUGH
 THE STOCK ROOM PLEASE SHOW COMPLIANCE WITH:
 2010 FBC-B 2010 FBC-B 1014.2 EGRESS THROUGH INTERVENING
 SPACES
 1014.2.4. EGRESS SHALL NOT PASS THROUGH KITCHENS,
 STORAGE ROOMS, CLOSETS OR SPACES USED FOR SIMILAR
 PURPOSES. EXCEPTIONS:
 2. MEANS OF EGRESS ARE NOT PROHIBITED THROUGH
 STOCKROOMS IN GROUP M OCCUPANCIES WHEN ALL OF THE
 FOLLOWING ARE MET:
  
 2.1. THE STOCK IS OF THE SAME HAZARD CLASSIFICATION AS
 THAT FOUND IN THE MAIN RETAIL AREA;
  
 2.2. NOT MORE THAN 50 PERCENT OF THE EXIT ACCESS IS
 THROUGH THE STOCKROOM;
  
 2.3. THE STOCKROOM IS NOT SUBJECT TO LOCKING FROM THE
 EGRESS SIDE; AND
  
 2.4. THERE IS A DEMARCATED, MINIMUM 44-INCH-WIDE (1118
 MM) AISLE DEFINED BY FULL- OR PARTIAL-HEIGHT FIXED
 WALLS OR SIMILAR CONSTRUCTION THAT WILL MAINTAIN THE
 REQUIRED WIDTH AND LEAD
 DIRECTLY FROM THE RETAIL AREA TO THE EXIT WITHOUT
 OBSTRUCTIONS.
  
 4) PLANS DO NOT INCLUDE ANY DETAILS OF A CASH WRAP THAT
 IS ACCESSBILE 2010 FL ACCESSIBILITY CODE 904.4 SALES
 AND SERVICE COUNTERS.
 SALES COUNTERS AND SERVICE COUNTERS SHALL COMPLY WITH
 904.4.1 OR 904.4.2. THE ACCESSIBLE PORTION OF THE
 COUNTER TOP SHALL EXTEND THE SAME DEPTH AS THE SALES OR
 SERVICE COUNTER TOP.
  
 EXCEPTION: IN ALTERATIONS, WHEN THE PROVISION OF A
 COUNTER COMPLYING WITH 904.4 WOULD RESULT IN A
 REDUCTION OF THE NUMBER OF EXISTING COUNTERS AT WORK
 STATIONS OR A REDUCTION OF THE NUMBER OF EXISTING MAIL
 BOXES, THE COUNTER SHALL BE PERMITTED TO HAVE A PORTION
 WHICH IS 24 INCHES (610 MM) LONG MINIMUM COMPLYING WITH
 904.4.1 PROVIDED THAT THE REQUIRED CLEAR FLOOR OR
 GROUND SPACE IS CENTERED ON THE ACCESSIBLE LENGTH OF
 THE COUNTER.
  
  
 5) SHEET A-1 INDICATE WITHIN THE ACCESSIBLE DRESSING
 ROOM A HANGING RACK BUT NO HEIGHT DIMENSIONS. 2010 FL
 ACCESSIBLITY CODE, REACH RANGES AND 803.5 COAT HOOKS
 AND SHELVES.
 COAT HOOKS PROVIDED WITHIN THE ROOM SHALL BE LOCATED
 WITHIN ONE OF THE REACH RANGES SPECIFIED IN 308.
 SHELVES SHALL BE 40 INCHES (1015 MM) MINIMUM AND 48
 INCHES (1220 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 6) PLEASE PROVIDE CODE COMPLIANCE WITH 2010 FBC-B 713.6
 FIRE WALLS, FIRE BARRIERS, FIRE PARTITIONS, SMOKE
 BARRIERS AND SMOKE PARTITIONS OR ANY OTHER WALL
 REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: ?FIRE
 AND SMOKE BARRIER ? PROTECT ALL OPENINGS.?
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-05 Cont ID  
Sent By skennedy Date 2013-12-05 Time 09:13 Rev Time 0.00
Received By skennedy Date 2013-12-05 Time 09:13 Sent To  
Notes
2013-12-05 09:13:52RESTAMP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-12 Cont ID  
Sent By albarran Date 2013-11-12 Time 15:58 Rev Time  
Received By albarran Date 2013-11-12 Time 15:00 Sent To I
Notes
2013-11-12 15:59:19SENT TO SH DESK

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-11-26 Cont ID  
Sent By scaldero Date 2013-11-26 Time 09:42 Rev Time 0.00
Received By scaldero Date 2013-11-26 Time 09:42 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-10-09 Cont ID  
Sent By scaldero Date 2013-10-09 Time 16:13 Rev Time 0.00
Received By scaldero Date 2013-10-09 Time 16:13 Sent To  
Notes
2013-10-09 16:21:30PERMIT #13100146
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL FIRE RATED
 WALLS, EXIT SIGNS, EMERGENCY LIGHTING, TRAVEL
 DISTANCES, COMMON PATH OF TRAVEL, LOCATION OF FIRE
 EXTINGUISHERS, ETC.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected])
 ([email protected]) OR IN WRITING (FAX: 561-804-4774) AND
 APPROVED BY THE OFFICE OF THE FIRE MARSHAL LOCATED AT
 500 NORTH DIXIE HIGHWAY.
  
 ENTRY DOORS: THUMB-TURN LOCK TO BE EQUIPPED WITH A
 LOCK/UNLOCK INDICATOR.
  
 EACH FIRE BARRIER SHALL BE PERMANENTLY IDENTIFIED WITH
 SIGNS OR STENCILING READING FIRE BARRIER-PROTECT ALL
 OPENINGS. CHARACTERS SHALL BE AT LEAST 4-INCHES IN
 HEIGHT AND HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE
 SPACED NOT MORE THAN 15 FEET ON CENTER.
  
 PROVIDE 44 INCH WIDE STRIPING (DEMARCATION) IN
 STOREROOM TO ENSURE EGRESS PATH REQUIREMENTS ARE
 MAINTAINED AT ALL TIMES.
  
 AN APPROVED WRITTEN EMERGENCY PLAN FOR THE EMERGENCY
 EGRESS OF OCCUPANTS IS REQUIRED PRIOR TO OCCUPANCY. ALL
 EMPLOYEES SHALL BE INSTRUCTED AND PERIODICALLY DRILLED
 WITH RESPECT TO THEIR DUTIES UNDER THE PLAN.
  
 EMPLOYEES SHALL BE PERIODICALLY TRAINED OR INSTRUCTED
 IN THE USE OF PORTABLE FIRE EXTINGUISHERS.
  
 SUB-PERMITS REQUIRED FOR ALL WORK DONE RELATED TO THE
 FIRE ALARM AND SPRINKLER SYSTEM.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 SUE ELLEN CALDERON
 FIRE INSPECTOR & INVESTIGATOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-05 Cont ID  
Sent By skennedy Date 2013-12-05 Time 09:14 Rev Time 0.00
Received By skennedy Date 2013-11-19 Time 13:04 Sent To  
Notes
2013-11-19 14:25:40C04
2013-11-19 13:04:52INCOMING SENT TO S. KENNEDYS DESK. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-12 Cont ID  
Sent By shill Date 2013-11-12 Time 16:48 Rev Time 0.00
Received By shill Date 2013-10-04 Time 08:06 Sent To  
Notes
2013-10-05 08:08:29C08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By mricard Date 2013-10-28 Time 16:42 Rev Time 0.00
Received By mricard Date 2013-10-28 Time 15:42 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-12-04 Cont ID  
Sent By lwagner Date 2013-12-04 Time 14:14 Rev Time 0.00
Received By lwagner Date 2013-12-04 Time 13:47 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-10-22 Cont ID  
Sent By lwagner Date 2013-10-22 Time 13:06 Rev Time 0.00
Received By lwagner Date 2013-10-22 Time 12:44 Sent To  
Notes
2013-10-22 13:04:10FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 CITY OF WEST PALM BEACH LOCAL ADMENDMENTS TO THE FBC
 2010 CHAPTER 1 ADMINISTRATION 107.3.5.1.3 #13 A RISER
 DIAGRAM IS REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop POLICE POLICE
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-10-30 Time   Rev Time 0.00
Received By ktucker Date 2013-10-30 Time 10:14 Sent To  
Notes
2013-10-30 10:14:48CRIME PREVENTION THROUGH ENVIRONMENTAL DESIGN
 THE CITY OF WEST PALM BEACH HAS RECOGNIZED THAT
 TRADITIONAL CRIME PREVENTION STRATEGIES ARE NOT ENOUGH
 IN TODAY?S SOCIETY AND A NEW APPROACH IS NEEDED. THE
 NAME OF THIS APPROACH IS CRIME PREVENTION THROUGH
 ENVIRONMENTAL DESIGN (CPTED). CPTED ACKNOWLEDGES THE
 MANNER IN WHICH PHYSICAL SPACE IS DESIGNED OR USED HAS
 A DIRECT BEARING ON CRIME AND SECURITY.
 THE PHYSICAL ENVIRONMENT HAS A DRAMATIC EFFECT ON OUR
 OWN BEHAVIOR AND THE WAY IN WHICH WE VIEW THE BEHAVIOR
 OF OTHERS. CPTED IS A CONCEPT SUPPORTED BY A SERIES OF
 OVERLAPPING PRINCIPLES BASED ON THE RELATIONSHIP OF THE
 BUILT ENVIRONMENT TO THE PRESENCE OR ABSENCE OF
 UNDESIRABLE BEHAVIOR. THE CPTED CONCEPT IS: ?THE PROPER
 DESIGN AND EFFECTIVE USE OF THE BUILT ENVIRONMENT CAN
 LEAD TO A REDUCTION IN THE INCIDENCE AND FEAR OF CRIME
 AND IMPROVEMENT IN THE QUALITY OF LIFE BY INCORPORATING
 ACCESS CONTROL, NATURAL SURVEILLANCE AND TERRITORIAL
 DEFENSIVE TACTICS.?
 CPTED THEORY IS BASED UPON THE CONTENTION THAT
 PLANNERS, DESIGNERS, ARCHITECTS, LANDSCAPERS AND LAW
 ENFORCEMENT CAN COOPERATIVELY CREATE A ?SAFE? CLIMATE
 WITHIN A BUILT ENVIRONMENT ? RIGHT FROM THE BEGINNING.
 SAFETY STRIKES AT THE VERY CORE OF WHAT IS GENERALLY
 REFERRED TO IN A COMMUNITY AS ?QUALITY OF LIFE.? A SAFE
 ENVIRONMENT IS ONE THAT REGULAR USERS PERCEIVE AS SAFE
 AND NON-USERS (CRIMINALS) PERCEIVE AS HIGHLY RISKY TO
 FREQUENT AND IN WHICH TO COMMIT CRIMES.
 THE WEST PALM BEACH POLICE DEPARTMENT HAS OUTLINED
 GUIDELINES WE WOULD LIKE TO SEE FOLLOWED. IN ADDITION
 TO THE GUIDELINES, WE ENCOURAGE YOU TO PLEASE ADOPT
 THESE MINIMUM STANDARDS:
  
 (1) A FULLY FUNCTIONING AND OPERATIONAL CCTV SYSTEM
 CAPABLE OF RECORDING AND RETRIEVING ON SITE, AN
 IDENTIFIABLE IMAGE TO ASSIST IN OFFENDER IDENTIFICATION
 AND APPREHENSION. MONITORS FOR THE SYSTEM SHOULD BE
 PLACED IN A MANAGER?S OFFICE OR BACK ROOM, WITH A
 MONITOR IN PUBLIC VIEW FROM THE SALES FLOOR.
 (2) CAMERA COVERAGE SHOULD BE AT SENSITIVE LOCATIONS:
 (A) DOORS THAT LEADS TO THE BACK OF HOUSE (B) HALLWAYS
 THAT LEAD TO REAR EXITS (C) SALES FLOOR (D) REGISTERS
 (LOW FOR FACIAL RECOGNITION) (E) FRONT ENTRY.
 (3) DOOR THAT LEADS TO THE BACK OF HOUSE AND EXITING
 REAR DOORS SHOULD BE ALARMED WITH A SENSOR AND VIEW
 FINDER.
 (4) SILENT PANIC ALARM UNDER EACH REGISTER, ONE IN THE
 BACK OF HOUSE WORK AREA
 (5) A SECURED DROP SAFE OR CASH MANAGEMENT DEVICE FOR
 RESTRICTED ACCESS TO MONEY/CASH RECEIPTS AT THE
 REGISTER AND A SECURED DROP SAFE OR CASH MANAGEMENT
 DEVICE IN THE STORAGE AREA.
 (6) CASH OUT AREA SHOULD BE IN THE FRONT OF THE STORE,
 CLOSE TO THE ENTRANCE.
 (7) SECURE THE REGISTERS TO THE COUNTER.
 (8) INSTALL ANTI-THEFT DEVICES INCLUDING SECURITY
 TOWERS AT ENTRANCES.
 (9) USE CONVEX MIRRORS IN CORNERS AND ANTI-THEFT TAGS
 ON MERCHANDISE.
 (10) HEIGHT MARKERS AT THE ENTRANCE AND EXIT.
 (11) EMPLOYEE ACCESS CONTROL ON ALL DOORS THAT LEAD
 INTO THE BACK.
 (12) WHERE WINDOW(S) ARE PRESENT, A CLEAR AND
 UNOBSTRUCTED VIEW FROM OUTSIDE THE STORE AND IN A
 NORMAL LINE OF SIGHT OF THE CASH REGISTER AND SALES
 TRANSACTION AREA
 (13) IF INSTALLING SWING GATE AT REGISTERS THEY SHOULD
 HAVE SIMPLE ACCESS CONTROL.
 (14) ALL SHOWCASES SHOULD HAVE LOCKS AND IN THE
 EXPENSIVE SHOWCASES, CONSIDER AN ALARM.
 (15) INTERIOR SHELVING AND DISPLAYS SHOULD BE NO HIGHER
 THAN FIVE FEET, EVEN LESS IN FRONT OF WINDOWS.
  
  
 OFFICER K. TUCKER-CARSILLO
 CRIME PREVENTION UNIT
 WEST PALM BEACH POLICE DEPT
 600 BANYAN BLVD
 WEST PALM BEACH, FL 33401
 (561) 822-1620 OFFICE
 (561) 822-1648 FAX
 [email protected]
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-10-23 Cont ID  
Sent By eschnied Date 2013-10-23 Time 16:16 Rev Time 0.25
Received By eschneid Date 2013-10-23 Time 16:16 Sent To  
Notes
2013-10-09 13:33:5110/9/13