Plan Review Details - Permit 13100140
Plan Review Stops For Permit 13100140
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By jgomez Date 2013-10-31 Time 11:08 Rev Time 0.00
Received By jgomez Date 2013-10-31 Time 11:02 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By albarran Date 2013-10-31 Time 16:28 Rev Time 0.00
Received By albarran Date 2013-10-31 Time 15:46 Sent To I
Notes
2013-10-31 16:38:04THE ELECTRICAL PORTION OF THIS PERMIT HAS BEEN APPROVED
 WITH THE FOLLOWING NOTATIONS:
 1. THE SUBMITTED DRAWING FAIL TO INCLUDE THE OUTLET
 REQUIRED IN NEC 210.52(C)(2), IN THE ISLAND KITCHEN.
 2. BECAUSE YOU HAS FOSSIL FUEL BURNING (GAS)
 APPLIANCES, FBC REQUIRES THAT YOU INSTALL CARBON
 MONOXIDE DETECTORS WITHIN 10' OF ANY SLEEPING AREA.
 3. ACCORDING TO THE SUBMITTED DRAWING, THE SPACING OF
 THE EXISTING ELECTRICAL OUTLETS IS NOT COMPLIANT WITH
 CODE STANDARDS.
 3. THIS IS A LEVEL 2 ALTERATION AS PER THE FBC-EXISTING
 BUILDING, AND THEREFORE YOU WILL NOT BE REQUIRED TO
 COME INTO COMPLIANCE WITH THE SPACING UNLESS YOU OPEN
 AND/OR ALTER THE WALL IN QUESTION.
 4. ALL WORK SHALL COMPLY WITH THE 2008 EDITION OF THE
 NEC.
  
 SENT TO SH DESK

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-06 Cont ID  
Sent By llouie Date 2013-12-06 Time 07:38 Rev Time 0.00
Received By llouie Date 2013-12-05 Time 16:37 Sent To  
Notes
2013-12-05 16:38:22PLAN SUBMITTED TO DEMONSTRATE LANDSCAPE COMPLIANCE.
 SENT TO ZONING BOX. (DK)

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-02 Cont ID  
Sent By shill Date 2013-11-02 Time 08:20 Rev Time 0.00
Received By shill Date 2013-10-04 Time 06:39 Sent To  
Notes
2013-10-05 06:40:24R08

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2014-02-26 Cont ID  
Sent By skennedy Date 2014-02-26 Time 11:49 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-10-31 Cont ID  
Sent By jgomez Date 2013-10-31 Time 11:38 Rev Time 0.00
Received By jgomez Date 2013-10-31 Time 11:38 Sent To  
Notes
2013-10-31 11:39:24SEPARATE GAS PERMIT REQUIRED. JG.

Review Stop Z ZONING
Rev No 2 Status P Date 2013-12-05 Cont ID  
Sent By dkittred Date 2013-12-05 Time 16:41 Rev Time 0.00
Received By dkittred Date 2013-12-05 Time 16:37 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-18 Cont ID  
Sent By dkittred Date 2013-10-18 Time 16:37 Rev Time 0.00
Received By dkittred Date 2013-10-18 Time 15:44 Sent To  
Notes
2013-10-18 16:37:22PLANNING AND ZONING COMMENTS: ***FAILED***
  
 10/18/13
 1. THE VALUE OF THE CONSTRUCTION ($29,000) EXCEEDS 50%
 OF THE STRUCTURE'S VALUE ($50,325) ACCORDING TO THE
 P.B.C. PROPERTY APPRAISER'S OFFICE; THEREFORE, PURSUANT
 TO SECTION 94-441(C)(2) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDR), THE LANDSCAPE ON THE
 SITE SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDR. IF THE
 SITE CONFORMS TO ARTICLE XIV, THEN TWO (2) COPIES OF A
 LANDSCAPE PLAN DEMONSTRATING COMPLIANCE SHALL BE
 INCLUDED WITH THE PERMIT RE-SUBMITTAL. IF THE SITE DOES
 NOT CONFORM TO ARTICLE XIV, THEN PRIOR TO THE ZONING
 APPROVAL OF THIS PERMIT A SEPARATE LANDSCAPE PERMIT AND
 IRRIGATION PERMIT SHALL BE SUBMITTED SHOWING MATERIAL
 TO BRING THE SITE INTO CONFORMITY. (NOTE: ZLDR SEC.
 94-442(B)(2)A. ? FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHADE, FLOWERING, OR FRUIT TREE SHALL BE
 PLANTED FOR EACH 1,200 SQUARE FEET OF OPEN SPACE OR
 PORTION THEREOF. FOR SINGLE-FAMILY DWELLING UNITS, AT
 LEAST ONE SHRUB SHALL BE PLANTED FOR EACH 500 SQUARE
 FEET OF OPEN SPACE OR PORTION THEREOF.)
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-10-18 13:03:1510/18/13