Plan Review Details - Permit 13100137
Plan Review Stops For Permit 13100137
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-11-12 Cont ID  
Sent By skennedy Date 2013-11-12 Time 15:52 Rev Time 0.00
Received By skennedy Date 2013-11-12 Time 15:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By skennedy Date 2013-10-28 Time 09:04 Rev Time 0.00
Received By skennedy Date 2013-10-28 Time 09:04 Sent To  
Notes
2013-10-28 09:34:17PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE DESIGN CRITERIA LISTS THE WIND EXPOSURE AS "B,"
 THE ACTUAL EXPOSURE IS "C."
 2) DESIGN PRESSURES SHOULD BE CALCULATED AND PROVIDED
 WITH THE ENGINEERING SUBMITTAL.
 3) SHEET 2/3 OF THE ENGINEERING SUBMITTAL PROVIDES
 ANCHORING DETAILS FOR THE SDG'S ONLY. IT IS UNCLEAR IF
 THIS IS INTENDED FOR BUCKS, OR THE SGD FRAMES.
 4) PURSUANT TO FBC 107.3.4, THE SELECTED WINDOW AND SGD
 PRODUCT APPROVALS SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD FOR THIS
 INSTALLATION.
 5) ALTHOUGH THE INCLUDED CONTRACT IDENTIFIES THE SIZE
 AND TYPE OF SELECTED PRODUCTS, A SCHEDULE IS PREFERRED
 FOR THIS PURPOSE.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jgomez Date 2013-11-07 Time 16:59 Sent To  
Notes
2013-11-08 16:59:42SENT TO KENNEDY'S DESK FOR REVIEW. JG.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-08 Cont ID  
Sent By skennedy Date 2013-10-28 Time 09:34 Rev Time 0.00
Received By jgomez Date 2013-10-04 Time 11:27 Sent To  
Notes
2013-11-08 16:58:51ENTERED "N" STATUS TO CLOSE THIS STOP. REVIEW DONE ON
 10/28/13 BY STEVE KENNEDY. JG.
2013-10-28 09:35:23PLACED IN SMALL DENIED PLANS "C."
2013-10-04 11:28:09ROUTED TO MISC 1