Plan Review Details - Permit 13100124
Plan Review Stops For Permit 13100124
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2014-03-05 Cont ID  
Sent By skennedy Date 2014-03-05 Time 10:58 Rev Time 0.00
Received By tklarge Date 2014-10-20 Time 13:59 Sent To  
Notes
2014-10-20 14:13:441) SUBMIT COPIES OF THE APPLICABLE SIZING TABLES USED
 FOR THE SIZING OF THIS SYSYTEM. WPB AMEND. TO 2010 FBC
 SEC. 107.2.1.
 2) SHOW THE LONGEST LENGTH OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET AND SHOW THE TOTAL
 BTU LOAD ON THE SYSTEM. 2010 FGC SEC.402.4.1.
 3) IDENTIFY THE APPLIANCES ON THE SYSTEM.WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 4) SHOW THE PSI OF THE SYSTEM ON THE PLANWPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 5) SOME OF THE BTU LOADS ARE ILLEGIBLE.WPB AMEND. TO
 2010 FBC SEC. 107.2.1.
 6) SHOW THE CORRESPONDING EHD FOR THE CSST PIPING. WPB
 AMEND. TO 2010 FBC SEC. 107.2.1.
 7) SOME OF THE INFO ON THE TOP OF THE PIPNG PLAN IS CUT
 OFF.
 8) DETAILS # 1 & #2 - WHAT IS THE 75,000 BTU LOAD AT
 THE TOP OF THE PAGE FOR? THE PIPING PLAN SHOWS THE
 DETAILS AS 150,000 BTU'S.
 9) WHAT DOES DETAIL # 1 & # 2 REPRESENT? WHAT TYPE OF
 APPLIANCE IS THIS?
  
 PLUMBING PLAN REVIEW
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 561-805-6692
 [email protected]
  
  
2014-03-05 10:59:17RESTAMP
2014-02-25 14:13:082/25/2014
 THIS REVIEW WILL NOT CONTINUE:
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2014-01-18 Cont ID  
Sent By jwitmer Date 2014-01-18 Time 12:20 Rev Time 0.00
Received By jwitmer Date 2014-01-10 Time 10:23 Sent To  
Notes
2014-01-16 16:55:10BUILDING PLAN REVIEW
 PERMIT: 13100124
 ADD: 815 UPLAND RD
 CONT: MASTER PLAN INC
 TEL: (561) 683-9972
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: THURSDAY JAN. 16/ 2014
 ACTION: BUILDING PROVISO
  
 2010 EXISTING BUILDING CODE
 METHOD OF COMPLIANCE: DESIGNER OF RECORD HAS CHOSEN
 PRESCRIPTIVE
 PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE BUILT IN
 1930
  
 2010 FL EXST BLDG CODE 301.2.1 EXISTING MATERIALS.
 MATERIALS ALREADY IN USE IN A BUILDING IN COMPLIANCE
 WITH REQUIREMENTS OR APPROVALS IN EFFECT AT THE TIME OF
 THEIR ERECTION OR INSTALLATION SHALL BE PERMITTED TO
 REMAIN IN USE UNLESS DETERMINED BY THE CODE OFFICIAL TO
 BE DANGEROUS TO LIFE, HEALTH OR SAFETY. WHERE SUCH
 CONDITIONS ARE DETERMINED TO BE DANGEROUS TO LIFE,
 HEALTH OR SAFETY, THEY SHALL BE MITIGATED OR MADE SAFE.
  
 1929 BUILDING CODE CITY OF WEST PALM BEACH
 FIRE SEPERATION SEC 1300 H - OCCUPANCY HOTEL,
 APARTMENTS, ROOMING HOUSES & RESTARAUNTS (BETWEEN
 OCCUPANCIES)
 CHAP. XIII REQUIREMENTS FOR GROUP "H" OCCUPANCY ( SS)
 NOTE: SPECIAL SEPERATION
 TYPE V BUILD 2 STORY FRONTAGE ON ONE STREET 3600 SQ FT,
 CODE COMPLIANT,
 PARTIII DETAILED REGULATIONS CHAPTER 33 STAIRS AND
 EXITS (PAGE 87) THE NUMBER OF STAIRWAYS AND OR EXITS
 REQUIRED IN ANY BUILDING CLASSED IN GROUPS D,E,F,G AND
 I SHALL BE DETERMINED AS FOLLOW:
 NO REQUIREMENTS FOR TYPE H OCCUPANCY : HOTEL,
 APARTMENTS, ROOMING HOUSES & RESTARAUNTS FOR STAIRS OR
 EXITS IN REGARDS TO FIRE RATING.
 SECTION 3303. MINIMUM WIDTH OF STAIRS IS 34 INCHES IN
 GROUP- D,E,F,& G BUILDINGS. NO MIN FOR H OCCUPANCIES.
 CHAPTER 44 FIRE RESISTANCE STANDARDS, PROTECTION OF
 STRUCTURAL PARTS WOOD JOIST WITH FLOOR WITH DOUBLE
 BOARD ON TOP OF JOIST AND GYPSUM OR PORTLAND CEMENT
 PLASTER 3/4 HR
 IN THE 2010 FBC-B THE PRESCRIPTIVE FIRE RESISTANCE
 TABLE 720.1(3)13.1.1 THE SAME FLOOR CONFIGURATION WILL
 PROVIDE 7/8 HR PROTECTION.
  
 1) 2010 FL EXST BLDG CODE 301.2.2 NEW AND REPLACEMENT
 MATERIALS.
 EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY THIS CODE,
 MATERIALS PERMITTED BY THE APPLICABLE CODE FOR NEW
 CONSTRUCTION SHALL BE USED. LIKE MATERIALS SHALL BE
 PERMITTED FOR REPAIRS AND ALTERATIONS, PROVIDED NO
 HAZARD TO LIFE, HEALTH OR PROPERTY IS CREATED.
 HAZARDOUS MATERIALS SHALL NOT BE USED WHERE THE CODE
 FOR NEW CONSTRUCTION WOULD NOT PERMIT THEIR USE IN
 BUILDINGS OF SIMILAR OCCUPANCY, PURPOSE AND LOCATION.
  
 1A) THE WINDOW AND DOOR OPENINGS (THE INFILL) THAT ARE
 BEING CLOSED IN WILL NEED TO COMPLY WITH THE 2010 FL
 BLDG CODE REQUIRING A 1 HR FIRE RATING PER SECTION
 709.1 GENERAL.
 THE FOLLOWING WALL ASSEMBLIES SHALL COMPLY WITH THIS
 SECTION. 1. WALLS SEPARATING DWELLING UNITS IN THE SAME
 BUILDING AS REQUIRED BY SECTION 438.2. 439.2 SEPARATION
 WALLS.
 WALLS SEPARATING DWELLING UNITS IN THE SAME BUILDING,
 WALLS SEPARATING SLEEPING UNITS IN THE SAME BUILDING
 AND WALLS SEPARATING DWELLING OR SLEEPING UNITS FROM
 OTHER OCCUPANCIES CONTIGUOUS TO THEM IN THE SAME
 BUILDING SHALL BE CONSTRUCTED AS FIRE PARTITIONS IN
 ACCORDANCE WITH SECTION 709. 709.3 FIRE-RESISTANCE
 RATING.
 FIRE PARTITIONS SHALL HAVE A FIRE-RESISTANCE RATING OF
 NOT LESS THAN 1 HOUR. PROVIDE UL
  
 1B) ANY NEW PENETRATION OF THE TENANT SEPERATION WALL
 OR FLOOR/ CEILING ASSEMBLY WILL ALSO REQUIRE COMPLIANCE
 WITH 713.3.1.2 THROUGH -PENETRATION FIRE STOP SYSTEMS.
  
 1C) ALL NEW TENANT ENTRY DOORS ARE TO BE 1 HOUR FIRE
 RATED AS PER 2010 FBC-B TABLE 715.4 AND AS REQUESTED BY
 THE DESIGNER OF RECORD.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  
  
  
  
  
  
 THIS REVIEW WILL CONTINUE 01/17/2014
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By jwitmer Date 2013-10-28 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 10:57 Sent To  
Notes
2013-10-28 11:21:58BUILDING PLAN REVIEW
 PERMIT: 13100124
 ADD: 815 UPLAND RD
 CONT: MASTER PLAN INC
 TEL: (561) 683-9972
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT 28/ 2013
 ACTION: DENIED
  
 1) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) 2010 FL EXISSTING BUILDING CODE, THE DESIGNER OF
 RECORD HAS NOT COMPLIED WITH 2010 FL EXT DLDG CODE
 101.5 COMPLIANCE METHODS.
 THE REPAIR, ALTERATION, CHANGE OF OCCUPANCY, ADDITION
 OR RELOCATION OF ALL EXISTING BUILDINGS SHALL COMPLY
 WITH ONE OF THE METHODS LISTED IN SECTIONS 101.5.1
 THROUGH 101.5.3 AS SELECTED BY THE APPLICANT.
 APPLICATION OF A METHOD SHALL BE THE SOLE BASIS FOR
 ASSESSING THE COMPLIANCE OF WORK PERFORMED UNDER A
 SINGLE PERMIT UNLESS OTHERWISE APPROVED BY THE CODE
 OFFICIAL. SECTIONS 101.5.1 THROUGH 101.5.3 SHALL NOT BE
 APPLIED IN COMBINATION WITH EACH OTHER.
  
 3) 107.3.5.1.1. MINIMUM PLAN REVIEW CRITERIA FOR
 COMMERCIAL BUILDINGS:
 OCCUPANCY TYPE ; R2 TRANSIENT OR NON-TRANSIENT
 BUILDING TYPE;
 FIRE SPRINKLERS:
 FIRE SEPERATION: TENANT WALLS & FLOOR CEILING
 ASSEMBLIES
 FIRE RATED DOORS;
 EXTERIOR STAIRS & REQUIREMENTS FOR FIRE RATED WINDOWS
 AND OR DOORS WITH-IN 10'-0" OF THE DOOR 2010 FBC-B
 1026.6
 EGRESS WINDOWS
  
 3) THE DESIGNER OF RECORD DID NOT INCLUDE A EXISTING
 FLOOR PLAN, WITHOUT A EXISTING FLOOR PLANS AND
 KNOWLEDGE OF COMPLIANCE METHOD A BUILDING PLAN REVIEW
 IS JUST GUESS WORK!!!!!
 THE INFORMATION ABOVE WILL HELP DEFINE WHAT WE ARE
 ACTUALLY LOOKING FOR FOR MINIMUM PLAN REVIEW, WHAT IS
 ACTUALLY THERE FOR FIRE RESISTANCE RATINGS AND WHAT WE
 CAN ASK FOR UNDER THE EXISTING BUILDING CODE.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2014-03-03 Cont ID  
Sent By albarran Date 2014-03-03 Time 19:23 Rev Time 0.00
Received By albarran Date 2014-03-03 Time 18:26 Sent To FIRE
Notes
2014-03-03 19:23:25PER NFPA 72, SECTION 4.4, THE DEDICATED FIRE ALARM
 CIRCUIT BREAKER SHALL BE MARKED IN RED AND IDENTIFIED
 AS ?FIRE ALARM CIRCUIT? AND BE MECHANICALLY PROTECTED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2014-02-10 Cont ID  
Sent By albarran Date 2014-02-10 Time 15:08 Rev Time 0.00
Received By albarran Date 2014-02-10 Time 14:22 Sent To FIRE
Notes
2014-02-10 15:12:14FOR DESERT LETS ADD THE FOLLOWING TO THE PLANS:
 1. THE DRAIN PUMP CIRCUIT AND CORRESPONDING LOAD SHALL
 BE INCLUDED IN TO PANEL H.
 THE WATER HEATER OVERFLOW AS WELL AS THE WASHING
 MACHINE DRAIN BELOW THE SEWER TAP AND THEREFORE NEEDS
 TO BE PUMPED UP FOR PROPER DRAINAGE.
 2. FACP DEDICATED CIRCUIT AND THE ASSOCIATED
 REQUIREMENTS ARE NOT ADDRESSED ON THE REVISED PLANS.
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH DEVELOPMENT SERVICES DEPARTMENT
 PH: (561) 805-6718, EMAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2014-01-29 Cont ID  
Sent By albarran Date 2014-01-29 Time 17:30 Rev Time 0.00
Received By albarran Date 2014-01-29 Time 15:06 Sent To I
Notes
2014-01-29 17:46:42THE FOLLOWING ITEMS SHALL BE ADDRESSED AND CORRECTED
 ACCORDINGLY:
 1. NOW THAT THE METHOD OF HEATING THE WATER HAS BEEN
 CLARIFIED, THE PRESSURIZATION AND DRAIN PUMP LOADS AND
 CIRCUITS SHALL BE INCLUDED IN PANEL H.
 2. HAVING THE COMMUNAL LAUNDRY FACILITIES IN THE
 BASEMENT BRING UP ADDITIONAL REQUIREMENTS FOR PROPER
 LIGHTING OF BOTH THE LAUNDRY ROOM AND THE STAIRS TO THE
 BASEMENT. THAT CIRCUIT HAS TO BE INCLUDED IN TO PANEL H
 AS WELL.
 3. THE FBC-ENERGY CONSERVATION CODE HAS SPECIFIC
 LIGHTING REQUIREMENTS, NOT OF WHICH ALL HAVE BEEN
 ADDRESSED. INCLUDE A LIGHTING DIAGRAM/SCHEMATIC
 INDICATING HOW THE HOUSE LIGHTS WILL BE CONTROLLED.
 INCLUDE THE ENTRY TO THE BASEMENT. IF THE BASEMENTS
 STAIR LIGHTING IS NOT ON AUTOMATIC SENSING, A MANUAL
 SWITCH SHALL BE PROVIDED PRIOR TO ENTERING THE STAIRS.
 4. PANEL H DOES NOT INCLUDE THE REQUIRED DEDICATED
 CIRCUIT FOR THE FIRE ALARM CONTROL PANEL, (FCP).
 5. BOTH THE FBC AND THE NFPA REQUIRE THAT THE FIRE
 ALARM CONTROL PANEL (FCP) BE PROTECTED WITH A SMOKE
 DETECTOR.
 6. ADDITIONAL FIRE ALARM RELATED COMMENTS MATCH THOSE
 ALREADY ADDRESSED BY THE FIRE REVIEW.
  
 FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE
 CONTACT:
 MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353
 CITY OF WEST PALM BEACH BLDG. DEPARTMENT
 (561) 805-6718
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-11-12 Cont ID  
Sent By albarran Date 2013-11-12 Time 11:06 Rev Time 0.00
Received By albarran Date 2013-11-12 Time 10:17 Sent To I
Notes
2013-11-12 11:34:23THE INTENT OF THE FOLLOWING LLIST IS NOT TO CREATE A
 "PUNCH :IST" FOR THE DESIGNER, NEVER THE LESS, THE
 BELOW MENTIONED ITEMS AMONG OTHERS SHALL BE ADDRESSED:
 1. FBC-R 303.8 REQUIRES THAT HEATING BE PROVIDED, NON
 OF WHICH IS REFLECTED ON EITHER THE ELECTRICAL PANEL
 SCHEDULE, ELECTRICAL LOAD CALCS, OR ON THE AIR
 CONDITIONING PAGE.
 2. THE PLANS DO NOT INDICATE IF THE WATER WILL BE
 HEATED WITH GAS OR ELECTRIC, THEREFORE THE ELECTRICAL
 LOAD CALC MAY NOT BE CORRECT.
 3. THE LEVEL OF ALTERATION DICTATES THE REQUIREMENT FOR
 HAVING TO PROVIDE LAUNDRY FACILITIES, BUT THE NEC DOES
 REQUIRE A LAUNDRY CKT BE INCLUDES IN THE LOAD CALCS.
 4. NEC 2008 SECTION 406.11 REQUIRE TAMPER-RESISTANT
 DEVICES
 5. NEC 2008 SECTION 210.12 REQUIRES ARC-FAULT
 PROTECTION
 6. THE SUBMITTED DRAWINGS SHOW THE AHU INSIDE AN
 ATTIC/CEILING, THIS WILL REQUIRE COMPLIANCE W/NEC
 110.33(B)
 7. FBC-R SECTIONS 314 & 315 HAVE SPECIFIC SMOKE AND
 CARBON MONOXIDE DETECTION REQUIREMENTS WHICH SHALL BE
 ADHERED TO.
  
 SENT TO SH DESK
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2014-03-04 Cont ID  
Sent By wjolin Date 2014-03-04 Time 13:20 Rev Time 0.00
Received By wjolin Date 2014-03-04 Time 13:07 Sent To B
Notes
2014-03-04 13:20:36815 UPLAND ROAD
 PERMIT #13100124
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 *****PROVISO - SUBMIT REVISION*****
  
 SHEET LS-1: THE PLANS SHOW WINDOW CALLOUT #1 AS A
 RESCUE/ESCAPE WINDOW; HOWEVER, NONE OF THE WINDOWS ON
 THE FLOOR PLAN ARE DESIGNATED AS A TYPE #1 ESCAPE
 WINDOW.
  
 SHEET E-2: PROVIDE A COMBINATION SMOKE ALARM/CO
 DETECTOR IN THE BASEMENT LAUNDRY ROOM.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
2014-02-10 15:12:57IN BIN C3

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2014-01-22 Cont ID  
Sent By wjolin Date 2014-01-22 Time 11:31 Rev Time 0.00
Received By wjolin Date 2014-01-21 Time 15:25 Sent To  
Notes
2014-01-22 11:30:59815 UPLAND ROAD
 PERMIT #13100124
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW
 EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE
 BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE
 ORDERED FROM WWW.KNOXBOX.COM.
  
 SHEET A-4, STAIR DETAIL: COMBINATION STAIR
 GUARD/HANDRAIL IS ONLY 34-INCHES ABOVE THE STAIR TREAD.
 GUARDS, AT LEAST 42-INCHES TALL (MEASURED FROM THE
 LEADING EDGE OF THE STAIR TREAD), SHALL BE PROVIDED AT
 THE OPEN SIDES OF MEANS OF EGRESS (STAIRS, MEZZANINE,
 ETC.) THAT EXCEED 30-INCHES ABOVE THE FLOOR.
  
 SHEET LS-1: PLANS ONLY SHOW ONE MEANS OF EGRESS FROM
 THE DWELLING UNITS (INTERNAL EXIT STAIR); HOWEVER, TWO
 MEANS OF EGRESS ARE REQUIRED PER NFPA 101 SECTION
 31.2.4.1. ESCAPE/RESUCE WINDOWS CAN BE USED AS A SECOND
 MEANS OF ESCAPE IS SO DESIRED AND MUST BE SHOWN ON THE
 PLANS AND MEET THE FOLLOWING CRITERIA:
 (1) SUCH WINDOWS SHALL BE OPERABLE FROM THE INSIDE
 WITHOUT THE USE OF TOOLS AND SHALL PROVIDE A CLEAR
 OPENING OF NOT LESS THAN 20-INCHES IN WIDTH, 24-INCHES
 IN HEIGHT, AND 5.7 SQ.FT. IN AREA.
 (2) THE BOTTOM OF THE OPENING SHALL BE NOT MORE THAN
 44-INCHES ABOVE THE FLOOR.
 (3) THE CLEAR OPENING SHALL ALLOW A RECTANGULAR SOLID,
 WITH A WIDTH AND HEIGHT THAT PROVIDES NOT LESS THAN THE
 REQUIRED 5.7 SQ.FT. OPENING AND A DEPTH OF NOT LESS
 THAN 20-INCHES TO PASS FULLY THROUGH THE OPENING.
 (4) WINDOWS MUST NOT BE LOCATED MORE THAN 20 FEET FROM
 THE GROUND LEVEL.
  
 SHEET LS-1: THE EXISTING INTERNAL CORRIDORS RESULT IN A
 DEAD-END CORRIDOR EXCEEDING 50 FEET AND A COMMON PATH
 OF TRAVEL EXCEEDING 35 FEET WHICH IS PROHIBITED IN
 EXISTING APARTMENT BUILDINGS PER NFPA 101 SECTION
 31.2.5.3.1 AND SECTION 31.2.5.4. REALIZING THE EXISTING
 FIRE CODE VIOLATIONS CANNOT BE READILY REMEDIED, I
 PROPOSE INSTALLING COMBINATION SMOKE/CARBON MONOXIDE
 DETECTORS (TIED INTO THE EXISTING FIRE ALARM SYSTEM)
 THROUGHOUT THE TWO CORRIDORS AND BASEMENT LAUNDRY AREA.
 THESE ADDITIONAL DETECTION DEVICES WILL PROVIDE
 OCCUPANTS WITH EARLY WARNING SHOULD A FIRE OCCUR.
  
 FIRE ALARM - ADDITIONAL SIGNAGE NEEDED: A PERMANENT,
 WEATHERPROOF SIGN SHALL BE PROVIDED AT EACH MANUAL FIRE
 ALARM PULL BOX READING "LOCAL ALARM ONLY - IN CASE OF
 FIRE CALL 911" .THE LETTERING AND NUMBERS ON APPROVED
 SIGNS SHALL HAVE A MINIMUM HEIGHT OF 1/2-INCH, WITH A
 MINIMUM 1/8-INCH STROKE WIDTH, AND SHALL BE WHITE IN
 COLOR ON RED BACKGROUND LOCATED NO HIGHER THAN 4-INCHES
 DIRECTLY ABOVE THE MANUAL FIRE ALARM BOX.
  
 FIRE ALARM: A COMBINATION VISUAL AND AUDIBLE
 NOTIFICATION DEVICE IS NEEDED ON THE OUTSIDE WALL
 (ADDRESS SIDE).
  
 FIRE ALARM: THE EXISTING FIRE ALARM CONTROL PANEL
 APPEARS TO BE NON-FUNCTIONAL AS WAS OBSERVED ON A FIELD
 INSPECTION (01/21/14). PROVIDE DRAWING NOTE INDICATING,
 "FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY."
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 FIRE INVESTIGATOR & INSPECTOR
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-11-12 Cont ID  
Sent By wjolin Date 2013-11-12 Time 15:01 Rev Time 0.00
Received By wjolin Date 2013-11-12 Time 14:43 Sent To  
Notes
2013-11-12 15:01:34815 UPLAND ROAD
 PERMIT #13100124
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS SHOW NEW WORK; HOWEVER, NO EXISTING FLOOR
 PLANS HAVE BEEN PROVIDED. THE PLANS APPEAR TO BE
 ENCLOSING APARTMENT UNIT DOORS (EGRESS DOORS) THAT WERE
 LEADING TO A COMMON CORRIDOR.
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL FIRE RATED
 WALLS, ESCAPE WINDOWS, EXIT SIGNS, EMERGENCY LIGHTING,
 TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
 A COMPLETE AND THOROUGH PLAN REVIEW CANNOT BE PERFORMED
 AT THIS TIME DUE TO LACK OF PLAN INFORMATION.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730
  

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2014-10-20 Cont ID  
Sent By tklarge Date 2014-10-20 Time 14:29 Rev Time 0.00
Received By tklarge Date 2014-10-20 Time 14:29 Sent To  
Notes
2014-10-20 14:29:011) SUBMIT COPIES OF THE APPLICABLE GAS SIZING TABLES
 FOR THE PIPE MATERIAL FROM THE 2010 FGC.
 2) SHOW THE TOTAL DISTANCE OF PIPING FROM THE POINT OF
 DELIVERY TO THE MOST REMOTE OUTLET PER THE 2010 FGC
 SEC.402.4.1.
 3) SHOW THE TOTAL BTU LOAD ON THE SYSTEM. WPB AMEND. TO
 2010 FGC SEC. 107.2.1.
 4)IDENTIFY ALL THE APPLIANCES ON THE GAS DRAWING. WPB
 AMEND. TO 2010 FGC SEC. 107.2.1.
 5) INDICATE THE OPERATING PRESSURE (PSI) OF THE SYSTEM.
 WPB AMEND. TO 2010 FGC SEC. 107.2.1.
 6) SOME OF THE BTU LOADS ARE HARD TO READ.
 7) SHOW THE CORRESPONDING EHD FOR THE DIFFERENT SIZE OF
 THE CSST.
 8) PART OF THE INFO ON THE TOP OF THE GAS PIPING
 DRAWING IS CUT OFF.
 9) DETAILS # 1& #2 - WHAT ARE THE 3/4" CAPPED OFF LINES
 FOR ON THE GAS PIPING DRAWING.
 10) WHAT IS THE 75,000 BTU LOAD SHOWN AT THE TOP OF THE
 PAGE FOR DETAILS #1 & # 2 ? THE PIPING PLAN SHOWS THE
 APPLIANCE AS 150,000 BTU'S.
 11) WHAT TYPE OF APPLIANCE IS DETAIL #1 & DETAIL #2.
 THIS DRAWING IS CONFUSION.
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2014-01-18 Cont ID  
Sent By jwitmer Date 2014-01-18 Time 14: Rev Time 0.00
Received By jwitmer Date 2014-01-18 Time 14:02 Sent To  
Notes
2014-01-18 14:28:53GAS PROVISO:
 THE WATER HEATER IS ELECTRIC AND NOT GAS PUTTING ON A
 GREATER DEMAND. IN REVIEWING THE SIZING THE GAS DRYER
 AT 22,000 BTU THIS IS LOW, THE AVERAGE DOMESTIC DRYER
 (TYPE1) IS
 35,000 BTU/H, EVEN AT THAT RATE THE SIZING IS ADEQUITE.
 2010 FBC-G TABLE 402.2.
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2014-01-18 Cont ID  
Sent By jwitmer Date 2014-01-18 Time 13:59 Rev Time 0.00
Received By jwitmer Date 2014-01-18 Time 13:59 Sent To  
Notes
2014-01-18 14:00:48NO GAS REVIEW ON 1ST ROUND OF COMMENTS. JW

Review Stop HIST HISTORICAL
Rev No 1 Status N Date 2013-10-25 Cont ID  
Sent By fmittner Date 2013-10-25 Time 15:00 Rev Time 0.00
Received By fmittner Date 2013-10-25 Time 15:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-03-05 Cont ID  
Sent By skennedy Date 2014-03-05 Time 10:59 Rev Time 0.00
Received By skennedy Date 2014-02-06 Time 16:35 Sent To  
Notes
2014-02-07 16:35:362-6/14 RESUBMITTAL SENT TO C3 SHELF FOR REVIEW. JG.
  
 2/12/14 ANOTHER RESUBMITTAL SUBMITTED IN THE MIDDLE OF
 REVIEW. SENT TO C3 SHELF FOR REVIEW. JG.
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-01-31 Cont ID  
Sent By skennedy Date 2014-01-31 Time 09:24 Rev Time 0.00
Received By skennedy Date 2013-12-23 Time 08:42 Sent To  
Notes
2014-01-29 17:47:30SENT TO SH DESK
2013-12-26 08:42:52C26
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-12 Cont ID  
Sent By wjolin Date 2013-11-12 Time 15:01 Rev Time 0.00
Received By wjolin Date 2013-10-03 Time 09:15 Sent To  
Notes
2013-10-05 09:15:59C15

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 3 Status N Date 2014-03-05 Cont ID  
Sent By skennedy Date 2014-03-05 Time 10:59 Rev Time 0.00
Received By skennedy Date   Time   Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2014-01-18 Cont ID  
Sent By jwitmer Date 2014-01-18 Time 14:01 Rev Time 0.00
Received By jwitmer Date 2014-01-18 Time 14:01 Sent To  
Notes
***NONE***

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By jwitmer Date 2013-10-28 Time 11:22 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 11:22 Sent To  
Notes
2013-10-28 11:22:46NOT ENOUGH INFORMATION FOR REVIEW.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2014-01-29 Cont ID  
Sent By hmoser Date 2014-01-29 Time 07:18 Rev Time 0.00
Received By hmoser Date 2014-01-29 Time 06:38 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By mricard Date 2013-10-28 Time 14:41 Rev Time 0.00
Received By mricard Date 2013-10-28 Time 14:28 Sent To  
Notes
2013-10-28 14:38:10FMC 301.2 PROVIDE ENERGY AND LOAD CALC FOR THE
 EQUIPMENT TO BE INSTALLED.
 FMC 304.1 PROVIDE MANUFACTURES PRODUCT INFO.

Review Stop P PLUMBING
Rev No 3 Status P Date 2014-03-05 Cont ID  
Sent By skennedy Date 2014-03-05 Time 09:38 Rev Time 0.00
Received By skennedy Date 2014-03-05 Time 09:38 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status F Date 2014-01-18 Cont ID  
Sent By jwitmer Date 2014-01-18 Time 13:33 Rev Time 0.00
Received By jwitmer Date 2014-01-18 Time 12:33 Sent To  
Notes
2014-01-18 12:37:54PLUMBING PLAN REVIEW
 PERMIT: 13100124
 ADD: 815 UPLAND RD
 CONT: MASTER PLAN INC
 TEL: (561) 683-9972
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: SATURDAY JAN. 17/ 2014
 ACTION: DENIED
  
 2010 EXISTING BUILDING CODE
 METHOD OF COMPLIANCE: DESIGNER OF RECORD HAS CHOSEN
 PRESCRIPTIVE
 PALM BEACH COUNTY PROPERTY APPRAISERS OFFICE BUILT IN
 1930
  
 2010 FL EXST BLDG CODE 301.2.1 EXISTING MATERIALS.
 MATERIALS ALREADY IN USE IN A BUILDING IN COMPLIANCE
 WITH REQUIREMENTS OR APPROVALS IN EFFECT AT THE TIME OF
 THEIR ERECTION OR INSTALLATION SHALL BE PERMITTED TO
 REMAIN IN USE UNLESS DETERMINED BY THE CODE OFFICIAL TO
 BE DANGEROUS TO LIFE, HEALTH OR SAFETY. WHERE SUCH
 CONDITIONS ARE DETERMINED TO BE DANGEROUS TO LIFE,
 HEALTH OR SAFETY, THEY SHALL BE MITIGATED OR MADE SAFE.
 THE DEMOLITION PLANS SHOW THE LOCATION OF THE PLUMBING
 FIXTURES, WHEN THEY ARE MOVED IT NO LONGER IS EXISTING
 BUT CONSIDERED NEW WORK AND NEEDS TO COMPLY WITH THE
 2010 FBC-PLUMBING.
  
 2010 FL EXST BLDG CODE 301.2.2 NEW AND REPLACEMENT
 MATERIALS.
 EXCEPT AS OTHERWISE REQUIRED OR PERMITTED BY THIS CODE,
 MATERIALS PERMITTED BY THE APPLICABLE CODE FOR NEW
 CONSTRUCTION SHALL BE USED. LIKE MATERIALS SHALL BE
 PERMITTED FOR REPAIRS AND ALTERATIONS, PROVIDED NO
 HAZARD TO LIFE, HEALTH OR PROPERTY IS CREATED.
 HAZARDOUS MATERIALS SHALL NOT BE USED WHERE THE CODE
 FOR NEW CONSTRUCTION WOULD NOT PERMIT THEIR USE IN
 BUILDINGS OF SIMILAR OCCUPANCY, PURPOSE AND LOCATION.
  
 1) 2ND REQUEST, PLEASE PROVIDE THE LOCATION OF THE
 WATER HEATER THE ELECTRICAL PLANS INDICATE THE USE OF
 INGIT OR WATER HEATER, LOCATION, SIZE, GAS OR ELECTRIC?
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010:
 107.3.5.1.3 PLUMBING ,
 (1) MINIMUM PLUMBING FACILITIES
 (2) FIXTURE REQUIREMENTS
 (5) WATER HEATERS
  
 2) SHEET P-5 SHOWS THEAUTOMATIC CLOTHES WASHER WASTE
 BEING PUMPED INTO THE BUILDING DRAIN BY USE OF A SUMP
 PUMP. THERE ARE TWO ISSUES:
 2A) PLEASE PROVIDE THE MANUFACTURERS SPECIFICATION FOR
 THIS SUMP PUMP FOR SIZE AND FLOW RATE CAPACITY AS WELL
 AS THE CLOTHES WASHER PUMP DISCHARGE FLOW RATE TO
 VERIFY THE SIZING OF THE SUMP PUMP WILL HAVE ENOUGH
 CAPACITY TO ACCEPT THE DISCHARGE. P 712.3.1 SUMP PUMP
 CAPACITY AND HEAD SHALL BE APPROPRIATE TO ANTIIPATE USE
 REQUIREMENTS.
  
 2B) SHEET P-5 NOTE ON THIS SHEET " SUMP PUMP TO CONNECT
 TO THE EXISTING SANITARY LINE, CONTRACTOR TO VERIFY THE
 SIZE & LOCATION AT SITE. THERE ARE STRICT REQUIREMENTS
 FOR THE TIEING INTO THE BUILDING SEWER OR BUILDING
 DRAIN. 2010 FBC-P 712.3.5 EJECTOR CONNECTION TO THE
 DRAINAGE SYSTEM.
 PUMPS CONNECTED TO THE DRAINAGE SYSTEM SHALL CONNECT TO
 THE BUILDING SEWER OR SHALL CONNECT TO A WYE FITTING IN
 THE BUILDING DRAIN A MINIMUM OF 10 FEET (3048 MM) FROM
 THE BASE OF ANY SOIL STACK, WASTE STACK OR FIXTURE
 DRAIN. WHERE THE DISCHARGE LINE CONNECTS INTO
 HORIZONTAL DRAINAGE PIPING, THE CONNECTOR SHALL BE MADE
 THROUGH A WYE FITTING INTO THE TOP OF THE DRAINAGE
 PIPING.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-10-29 Cont ID  
Sent By lwagner Date 2013-10-29 Time 12:03 Rev Time 0.00
Received By lwagner Date 2013-10-29 Time 08:53 Sent To  
Notes
2013-10-29 12:03:30FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1. SHEET P-1 & P-2: THE 2ND FLOOR SOIL STACK IS RUNNING
 THROUGH THE FIRST FLOOR WET VENT. PLEASE SHOW THE SOIL
 STACK DOWNSTREAM OF THE WET VENT.
 909.1 HORIZONTAL WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL IS PERMITTED TO BE
 VENTED BY A HORIZONTAL WET VENT. THE WET VENT SHALL BE
 CONSIDERED THE VENT FOR THE FIXTURES AND SHALL EXTEND
 FROM THE CONNECTION OF THE DRY VENT ALONG THE DIRECTION
 OF THE FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM
 FIXTURE DRAIN CONNECTION TO THE HORIZONTAL BRANCH
 DRAIN. EACH WET-VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT. ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL
 FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE HORIZONTAL
 WET VENT.
  
 2. A DRAWING OF THE HOT AND COLD WATER WILL BE REQUIRED
 WITH THE LOCATION OF THE WATER HEATER/S.
 107.3.5.1.3 PLUMBING
 (1)MINIMUM PLUMBING FACILITIES
 (2.) FIXTURE REQUIREMENTS
 (3.) WATER SUPPLY PIPING
 (5.) WATER HEATERS
 ...
  
 3. PLEASE INDICATE THE LOCATION OF THE AUTOMATIC
 CLOTHES WASHER CONNECTION/S.
 TABLE 403.1
 MINIMUM NUMBER OF REQUIRED PLUMBING FIXTURES (R-2)
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  

Review Stop Z ZONING
Rev No 1 Status P Date 2013-10-25 Cont ID  
Sent By fmittner Date 2013-10-25 Time 15:00 Rev Time 0.00
Received By fmittner Date 2013-10-25 Time 15:00 Sent To  
Notes
2013-10-09 13:30:3610/9/13