| 2013-10-03 07:30:31 | BUILDING PLAN REVIEW | | | PERMIT: 13100086 | | | ADD: 1707 OKEECHOBEE RD | | | CONT: TO BE DETERMINED | | | TEL: (561) | | | | | | 2010 FLORIDA BUILDING CODE W | | | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 2010 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | DATE: OCT. 03/ 2013 | | | ACTION: DENIED | | | | | | 1) SHEET A1: | | | 1A) PLANS INDICATE A MIXED USE OCCUPANCY BUILDING, | | | WAREHOUSE AND MERCANTILE. PLEASE PROVIDE IF THE | | | WAREHOUSE IS S1 OR S2 STORAGE PLEASE REVIEW | | | 2010 FBC-B TABLE 508.4 DEPENDING ON THE TYPE OF | | | OCCUPANCY THE HOUR RATING REQUIRED FOR THIS WALL. | | | | | | 1B) SHEET A1 ALSO INDICATES THE INSULATION LAYING | | | DIRECTLY ON THE CEILING GRID. 2010 FBC-ENERGY 502.2.1.2 | | | CEILING INSULATION. | | | INSULATION INSTALLED ON A SUSPENDED CEILING WITH | | | REMOVABLE CEILING TILES SHALL NOT BE CONSIDERED PART OF | | | THE MINIMUM THERMAL RESISTANCE OF THE ROOF INSULATION | | | UNLESS THE ROOF/CEILING CAVITY IS SEALED FROM THE | | | EXTERIOR ENVIRONMENT. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2013-12-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-04 |
Time |
14:54 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
2013-12-04 |
Time |
14:54 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2013-10-23 |
|
|
Cont ID |
|
| Sent By |
albarran |
Date |
2013-10-23 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
albarran |
Date |
2013-10-23 |
Time |
16:24 |
Sent To |
I |
|
| Notes |
| 2013-10-23 16:38:16 | SENT TO SH DESK | | 2013-10-23 16:37:38 | NEEDS TO REFERENCE3 AND COMPLY WITH THE FBC 2010 | | | FBC-ENERGY AND THE NEC 2008 EDITION. | | | THIS IS IN A BLDG LARGER THAN 5000 SQ. FT. THEREFORE | | | COMPLIANCE WITH THE FBC-ENERGY IS REQUIRED | | | NEED TO PROVIDE BETTER ELECTRICAL DESCRIPTION OF WORK | | | ON THE PLANS AS WELL |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
P |
Date |
2013-10-07 |
|
|
Cont ID |
|
| Sent By |
scaldero |
Date |
2013-10-07 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
scaldero |
Date |
2013-10-07 |
Time |
13:44 |
Sent To |
|
|
| Notes |
| 2013-10-07 13:49:17 | | | | | | | PERMIT #13100086 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | ***PROVISO COMMENT*** | | | PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION | | | SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND | | | RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION | | | SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A | | | 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A | | | FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED | | | BY EMAIL ([email protected]) OR IN WRITING (FAX: | | | 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE | | | MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.? | | | | | | IF APPLICABLE, SEPARATE PLANS AND PERMITS WILL BE | | | REQUIRED FOR MODIFICATION OF THE FIRE SPRINKLER SYSTEM | | | AND/OR FIRE ALARM SYSTEM. | | | | | | SUE ELLEN CALDERON | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 804-4751 | | | | | | | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-12-04 |
|
|
Cont ID |
|
| Sent By |
skennedy |
Date |
2013-12-04 |
Time |
14:55 |
Rev Time |
0.00 |
| Received By |
skennedy |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-10-24 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2013-10-24 |
Time |
10:48 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2013-10-02 |
Time |
18:30 |
Sent To |
|
|
| Notes |
| 2013-10-02 18:30:24 | INCOMING SENT TO B36 BOX. JW |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
P |
Date |
2013-11-30 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2013-11-30 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2013-11-30 |
Time |
08:46 |
Sent To |
|
|
| Notes |
|
|
|