Plan Review Details - Permit 13100071
Plan Review Stops For Permit 13100071
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-26 Cont ID  
Sent By JWITMER Date 2013-10-26 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2013-10-26 Time 07:02 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-21 Cont ID  
Sent By jwitmer Date 2013-10-21 Time 06:43 Rev Time 0.00
Received By jwitmer Date 2013-10-21 Time 06:33 Sent To  
Notes
2013-10-21 06:59:44BUILDING PLAN REVIEW
 PERMIT: 13100071
 ADD: 1649 FORUM PLACE # 2
 CONT: CASTO HOMES
 TEL: (561)626-3444
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. OCT 21/2013
 ACTION: DENIED
  
 1) NEITHER THE ARCHITECTURAL SHEETS NOR THE ELECTRICAL
 SHEET SHOW EXIT DIRECTIONAL, EXIT, OR EXIT TACTILE
 SIGNAGE PLEASE SEE 2010 FBC 1006.3.4.
  
 2) NEITHER TTHTE ARCHITECTURAL SHEETS NOR THE
 ELECTRICAL SHEET PROVIDE COMPLIANCE WITH 2010 FBC-B
 1006.1.2 BATTERY-OPERATED ELECTRIC LIGHTS FOR EXITING.
  
 3) SHEET A-1:
 3A) THE DIRETORS OFFICE # 114 IS MISSING THE REQUIRED
 18" AT THE LATCH SIDE OF THE DOOR, 2010
 FBC-ACCESSIBILITY CODE 404.2.4 AND FIGURE 404.2.4.1(A).
  
 3B) MISSING A DRINKING FOUNTAIN THAT WILL NEED TO BE IN
 COMPLIANCE WITH2010 ACCESSIBILITY CODE 211, 602.4 &
 602.7.
  
 3C) THE NEW STAFF LOUNGE DOES NOT SHOW COMPLIANCE WITH
 2010 ACCESSIBILITY CODE 606.1-5.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2013-10-25 Cont ID  
Sent By rmcdouga Date 2013-10-25 Time 14:02 Rev Time 0.00
Received By rmcdouga Date 2013-10-25 Time 14:02 Sent To  
Notes
2013-10-25 14:03:26ELECTRIC IS UNDER A SEPARATE PERMIT #13100542 WITH
 SEPARATE PLANS

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status N Date 2013-10-26 Cont ID  
Sent By SCALDERO Date 2013-10-26 Time 07:06 Rev Time 0.00
Received By rmcdouga Date 2013-10-26 Time 07:06 Sent To  
Notes
2013-10-25 14:05:23NEW PLANS SUBMITTED DID NOT AFFECT FIRE, SHEETS WITH
 FIRE APPROVAL STAMP ARE INCLUDED WITH NEW PLAN SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-11 Cont ID  
Sent By scaldero Date 2013-10-11 Time 14:25 Rev Time 0.00
Received By scaldero Date 2013-10-11 Time 14:25 Sent To  
Notes
2013-10-11 14:29:49PERMIT # 13100071
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SHEET A-3 INDICATES LOCATION OF FIRE ALARM PULL
 STATION. SEPARATE PLANS AND PERMITS ARE REQUIRED FOR
 THE INSTALLATION OR MODIFICATION OF THE FIRE ALARM
 SYSTEM.
  
 PROVIDE DRAWING NOTE INDICATING, ?FIRE PROTECTION
 SYSTEMS SHALL REMAIN ACTIVE DURING DEMOLITION AND
 RENOVATION ACTIVITIES. IN THE EVENT A FIRE PROTECTION
 SYSTEM IS OUT OF SERVICE FOR MORE THAN 4-HOURS IN A
 24-HOUR PERIOD, THE BUILDING SHALL BE PLACED UNDER A
 FIRE WATCH. ALL FIRE WATCH REQUESTS MUST BE SUBMITTED
 BY EMAIL ([email protected]) OR IN WRITING (FAX:
 561-804-4774) AND APPROVED BY THE OFFICE OF THE FIRE
 MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.?
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-26 Cont ID  
Sent By jwitmer Date 2013-10-26 Time 07:25 Rev Time 0.00
Received By jwitmer Date 2013-10-25 Time 14:04 Sent To  
Notes
2013-10-25 14:04:59B33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-25 Cont ID  
Sent By rmcdouga Date 2013-10-25 Time 14:03 Rev Time 0.00
Received By rmcdouga Date 2013-10-02 Time 17:49 Sent To  
Notes
2013-10-18 17:10:49****EXPEDITED****
  
 10/16 ROUTED EXPEDITED REQUEST TO B33
  
2013-10-02 17:49:45INCOMING SENT TO B-33 BOX. JW

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-11-22 Cont ID  
Sent By skennedy Date 2013-11-22 Time 12:21 Rev Time 0.00
Received By skennedy Date 2013-11-22 Time 12:21 Sent To  
Notes
2013-11-22 12:25:55SUB APPLIED, NO REVIEW WAS ASSOCIATED WITH MASTER,
 HOWEVER, MY REVIEW OF PLAN ON FILE INDICATES A PLUMBING
 PLAN REVIEW SHOULD HAVE BEEN CONDUCTED WITH ORIGINAL
 REVIEW.

Review Stop Z ZONING
Rev No 1 Status P Date 2013-10-09 Cont ID  
Sent By ajones Date 2013-10-09 Time 13:44 Rev Time 0.00
Received By ajones Date 2013-10-09 Time 13:44 Sent To  
Notes
***NONE***