| 2013-10-21 06:59:44 | BUILDING PLAN REVIEW |
| | PERMIT: 13100071 |
| | ADD: 1649 FORUM PLACE # 2 |
| | CONT: CASTO HOMES |
| | TEL: (561)626-3444 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: MON. OCT 21/2013 |
| | ACTION: DENIED |
| | |
| | 1) NEITHER THE ARCHITECTURAL SHEETS NOR THE ELECTRICAL |
| | SHEET SHOW EXIT DIRECTIONAL, EXIT, OR EXIT TACTILE |
| | SIGNAGE PLEASE SEE 2010 FBC 1006.3.4. |
| | |
| | 2) NEITHER TTHTE ARCHITECTURAL SHEETS NOR THE |
| | ELECTRICAL SHEET PROVIDE COMPLIANCE WITH 2010 FBC-B |
| | 1006.1.2 BATTERY-OPERATED ELECTRIC LIGHTS FOR EXITING. |
| | |
| | 3) SHEET A-1: |
| | 3A) THE DIRETORS OFFICE # 114 IS MISSING THE REQUIRED |
| | 18" AT THE LATCH SIDE OF THE DOOR, 2010 |
| | FBC-ACCESSIBILITY CODE 404.2.4 AND FIGURE 404.2.4.1(A). |
| | |
| | 3B) MISSING A DRINKING FOUNTAIN THAT WILL NEED TO BE IN |
| | COMPLIANCE WITH2010 ACCESSIBILITY CODE 211, 602.4 & |
| | 602.7. |
| | |
| | 3C) THE NEW STAFF LOUNGE DOES NOT SHOW COMPLIANCE WITH |
| | 2010 ACCESSIBILITY CODE 606.1-5. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |