Plan Review Details - Permit 13100028
Plan Review Stops For Permit 13100028
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2013-11-14 Cont ID  
Sent By shill Date 2013-11-14 Time 07:33 Rev Time 0.00
Received By shill Date 2013-11-14 Time 07:32 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-10-18 Cont ID  
Sent By shill Date 2013-10-18 Time 12:48 Rev Time 0.00
Received By shill Date 2013-10-18 Time 12:48 Sent To  
Notes
2013-10-18 12:53:36****CORRECTIONS****
 (2ND COMMENTS SENT VIA EMAIL ON 10/17)
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 COMMENTS FROM PREVIOUS LIST:
  
 FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING:
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2ND REVIEW, SUSPENDED CEILING INCLUDED ON TEST. ALSO
 PRODUCT TESTED IS NOT THE SAME AS THE PRODUCT TESTED
 FOR FLAME SPREAD (SEE ALSO COMMENT #3).
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2ND REVIEW, SUSPENDED CEILING INCLUDED ON TEST. ALSO
 PRODUCT TESTED IS NOT THE SAME AS THE PRODUCT TESTED
 FOR FLAME SPREAD (SEE ALSO COMMENT #3).
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
 2ND REVIEW: FLAME SPREAD TEST DOES NOT REFER TO A
 PRODUCT, ONLY "SAMPLES OF PADDING INSULATION." PRODUCT
 TESTED IS NOT CLEAR.
  
 FLAME SPREAD WAS DONE FOR MIDWEST PADDING, LLC. SOUND
 TESTS WERE FOR BELLAWOOD UNDERLAYMENT, MP GLOBAL
 PRODUCTS LLC. PRODUCT PROPOSED IS NOT CLEAR.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-16 Cont ID  
Sent By shill Date 2013-10-16 Time 07:45 Rev Time 0.00
Received By shill Date 2013-10-16 Time 07:45 Sent To  
Notes
2013-10-16 07:47:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 FBC FLORIDA BUILDING CODE 2010
  
 FOR THE FLOORING UNDERLAYMENT, PROVIDE THE FOLLOWING:
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2013-11-14 Cont ID  
Sent By shill Date 2013-11-14 Time 07:33 Rev Time 0.00
Received By shill Date 2013-10-31 Time 17:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-18 Cont ID  
Sent By shill Date 2013-10-18 Time 12:48 Rev Time 0.00
Received By shill Date 2013-10-18 Time 12:48 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-16 Cont ID  
Sent By shill Date 2013-10-16 Time 07:47 Rev Time 0.00
Received By shill Date 2013-10-01 Time 10:43 Sent To  
Notes
2013-10-02 10:44:36SENT TO BUILDING UNDER $5000 BOX


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved