Plan Review Details - Permit 13100023
Plan Review Stops For Permit 13100023
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-28 Cont ID  
Sent By albarran Date 2013-10-28 Time 17:06 Rev Time 0.00
Received By albarran Date 2013-10-28 Time 16:38 Sent To I
Notes
2013-10-28 17:07:32SEE NOTES IN THE INCOMING SECTIONS FOR A COMPLETE SET
 OF PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-09 Cont ID  
Sent By dharvey Date 2013-10-09 Time 10:30 Rev Time 0.00
Received By dharvey Date 2013-10-09 Time 10:06 Sent To FIRE
Notes
2013-10-09 10:29:581) NEED TO PROVIDE ALL LISTED DEVISES CUT SHEETS. FBC
 107.3.5 ELECTRICAL.
 2) NEED TO PROVIDE POWER LOAD CALCULATIONS. FBC 107.3.5
 ELECTRICAL.
 3) PROVIDE DOOR HARDWARE CUT SHEET. FBC 107.3.5
 BUILDING AND FBC 1008.1.10.
  
 REVIEWED BY WDS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2013-10-17 Cont ID  
Sent By lphilmor Date 2013-10-17 Time 11:16 Rev Time 0.00
Received By lphilmor Date 2013-10-17 Time 11:16 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-10-09 Cont ID  
Sent By scaldero Date 2013-10-09 Time 14:31 Rev Time 0.00
Received By scaldero Date 2013-10-09 Time 14:31 Sent To  
Notes
2013-10-09 14:45:25PERMIT # 13100023
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PLANS DO NOT SHOW REQUIRED SENSOR AND THE DOOR EXITING
 FROM VESTIBULE 103 DOES NOT OPEN IN THE DIRECTION OF
 EGRESS.
 PER NFPA 101, SECTION 7.2.1.6.2, ACCESS-CONTROLLED
 EGRESS DOORS ARE PERMITTED PROVIDED THAT ALL SEVEN OF
 THE FOLLOWING CRITERIA ARE MET:
 1. A SENSOR SHALL BE PROVIDED ON THE EGRESS SIDE,
 ARRANGED TO DETECT AN OCCUPANT APPROACHING DOORS THAT
 ARE ARRANGED TO UNLOCK IN THE DIRECTION OF EGRESS UPON
 DETECTION OF AN APPROACHING OCCUPANT OR LOSS OF POWER
 TO THE SENSOR.
 2. LOSS OF POWER TO THE PART OF THE ACCESS CONTROL
 SYSTEM THAT LOCKS THE DOORS SHALL AUTOMATICALLY UNLOCK
 THE DOORS IN THE DIRECTION OF EGRESS.
 3. THE DOORS SHALL BE ARRANGED TO UNLOCK IN THE
 DIRECTION OF EGRESS FROM A MANUAL RELEASE DEVICE
 LOCATED VERTICALLY 40 TO 48 INCHES ABOVE THE FLOOR AND
 WITHIN 60 INCHES HORIZONTALLY OF THE SECURED DOORS.
 4. THE MANUAL RELEASE DEVICE SHALL BE READILY
 ACCESSIBLE AND CLEARLY IDENTIFIED BY A SIGN THAT READS
 PUSH TO EXIT.
 5. WHEN OPERATED, THE MANUAL RELEASE DEVICE SHALL
 RESULT IN DIRECT INTERRUPTION OF POWER TO THE LOCK,
 INDEPENDENT OF THE ACCESS CONTROL SYSTEM ELECTRONICS,
 AND THE DOORS SHALL REMAIN UNLOCKED FOR NOT LESS THAN
 30 SECONDS.
 6. ACTIVATION OF THE BUILDING FIRE ALARM SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
 7. ACTIVATION OF THE BUILDING AUTOMATIC SPRINKLER
 SYSTEM OR AUTOMATIC DETECTION SYSTEM SHALL
 AUTOMATICALLY UNLOCK THE DOORS IN THE DIRECTION OF
 EGRESS, AND THE DOORS SHALL REMAIN UNLOCKED UNTIL THE
 FIRE ALARM SYSTEM HAS BEEN MANUALLY RESET.
  
 PLANS DO NOT SPECIFY IF BUILDING IS EQUIPPED WITH A
 FIRE SPRINKLER SYSTEM AND/OR FIRE ALARM SYSTEM.
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-28 Cont ID  
Sent By jlmitch Date 2013-10-28 Time 18:18 Rev Time 0.00
Received By jlmitch Date   Time   Sent To  
Notes
2013-10-28 17:06:14SOMEHOW THESE PLANS WERE MIXED UP. I THINK THAT BY
 ADDING PAGE 5 OF 6 TO THE ORIGINAL SUBMITTAL AND MAKING
 A COPY OF THE CUT SHEET A COMPLETE SET OF PLANS CAN BE
 SET UP.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-28 Cont ID  
Sent By jlmitch Date 2013-10-28 Time 18:18 Rev Time 0.00
Received By jlmitch Date 2013-10-15 Time 09:25 Sent To  
Notes
2013-10-17 09:26:09SENT TO FIRE SHELF FOR REVIEW. JG.