| 2013-12-05 07:17:53 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6724 |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1. OK |
| | |
| | 2. OK. |
| | |
| | 3. REVISE PLAN TO SHOW OCCUPANCY CLASSIFICATION AND |
| | OCCUPANT LOAD FOR THE EXISTING BUILDING AND EXTERIOR |
| | COURTYARD. IT APPEARS THAT THE COURTYARD AREA IS |
| | CURRENTLY USED AS STORAGE AND WILL NOW BE A2. 1300 |
| | SF/15 IS AN OCCUPANT LOAD OF 87 FOR THE COURTYARD. |
| | OCCUPANT LOAD OF EXISTING RESTAURANT NOT SHOWN AND |
| | CANNOT BE DETERMINED AS KITCHEN/BATHROOM/WAITING AREAS |
| | NOT SHOWN. |
| | |
| | PROVIDE A LIFE SAFETY PLAN, FBC CHAPTER 10. EXITING |
| | STRATEGY NOT CLEAR. A DOOR IS SHOWN AS "EMERGENCY |
| | EGRESS," EXIT SIGNS SHOWN, BUT EXITING PATH NOT SHOWN. |
| | SEE ALSO FBC 1008.1.2 AND 1008.1.10. INCLUDE ELEVATION |
| | CHANGES, IF ANY, WHICH EXIST THROUGHOUT THE PROPOSED |
| | MEANS OF EGRESS PATH. |
| | |
| | 2ND REVIEW - |
| | |
| | DOOR STILL REFERENCED AS "EMERGENCY EGRESS." PLEASE |
| | ADVISE AS TO WHERE THE DEFINITION OF "EMERGENCY EGRESS" |
| | IS LOCATED IN FBC CHAPTER 10. IT IS NOT CLEAR WHAT |
| | FUNCTION THIS SERVES IN THE LIFE SAFETY PLAN. FBC 107. |
| | |
| | COURTYARD IS SHOWN AS "EXISTING OCCUPANCY" WITH 50 MAX. |
| | BASED ON THE PHOTOGRAPH ON THE PLAN AS WELL AS AERIALS, |
| | THIS ISS STORAGE, NOW PROPOSED AS A2, SO HOW CAN THIS |
| | BE "EXISTING OCCUPANCY"? OCCUPANT LOAD CANNOT BE LESS |
| | THAN FBC TABLE 1004.1.1. |
| | |
| | PLAN NOTES THAT THE COURTYARD IS OPEN TO THE PARKING |
| | LOT, WITH NO FENCE OR WALL, BUT AERIALS AND THE |
| | PHOTOGRAPH ON THE PLAN SHOW A FENCE, SO PLAN IS NOT |
| | CONSISTENT WITH JOB CONDITIONS. SHOW FENCE ON THE PLAN, |
| | AND INDICATE WHETHER THIS WILL BE REMOVED OR REMAIN. |
| | NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO DETERMINE |
| | REQUIREMENTS FOR THIS AREA. |
| | |
| | ELEVATION CHANGES NOT SHOWN. |
| | |
| | 4. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD |
| | REQUIRED, FAC9N-3, FBC 107 (DOOR). INDICATE HARDWARE |
| | AND THRESHOLD OPTIONS, SEE FBC 1008.1, FBC 1008.1.10 |
| | AND FBC 2010 ACCESSIBILITY 404. |
| | |
| | 2ND REVIEW, NOT ADDRESSED. ARCHITECT'S RESPONSE IS THAT |
| | PRODUCT APPROVAL IS ATTACHED. |
| | |
| | PANIC DEVICE REQUIRED, BUT NOT FOUND IN THE PRODUCT |
| | APPROVAL. SEE FBC 1008.1.10 AND FBC 1008.1. THRESHOLD |
| | NOT INDICATED, SEE FBC 2010 ACCESSIBILITY 404. |
| | |
| | 5. PROVIDE A DETAIL FOR THE PROPOSED GATE. CODE |
| | REFERENCE AND REQUIREMENTS CANNOT BE PROVIDED AT THIS |
| | TIME, SEE ITEM 3. IF THERE ARE NO CODE REQUIREMENTS FOR |
| | THE GATE, THIS MAY NOT BE REQUIRED. |
| | |
| | NOT ADDRESSED. PHOTOGRAPH APPEARS TO SHOW A METAL |
| | SCREEN WITH MULTIPLE HINGES (3 PANELS). THE PHOTOGRAPH |
| | STATES "DECORATIVE ONLY - NO LOCK." INDICATE IN FBC |
| | CHAPTER 10 WHERE THIS IS PERMITTED. SEE FBC 1008.2. NOT |
| | ENOUGH INFORMATION PROVIDED TO DETERMINE CODE |
| | COMPLIANCE. |
| | |
| | 6. OK |
| | |
| | NOT ENOUGH ACCURATE INFORMATION PROVIDED TO PROVIDE A |
| | COMPLETE CHECKLIST. FBC 107 |
| | |
| | |
| | |
| | |
| | |