Plan Review Details - Permit 13090969
Plan Review Stops For Permit 13090969
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2013-12-05 Cont ID  
Sent By shill Date 2013-12-05 Time 06:26 Rev Time 0.00
Received By shill Date 2013-12-05 Time 06:26 Sent To Z
Notes
2013-12-05 07:17:53****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FROM PREVIOUS LIST:
  
 1. OK
  
 2. OK.
  
 3. REVISE PLAN TO SHOW OCCUPANCY CLASSIFICATION AND
 OCCUPANT LOAD FOR THE EXISTING BUILDING AND EXTERIOR
 COURTYARD. IT APPEARS THAT THE COURTYARD AREA IS
 CURRENTLY USED AS STORAGE AND WILL NOW BE A2. 1300
 SF/15 IS AN OCCUPANT LOAD OF 87 FOR THE COURTYARD.
 OCCUPANT LOAD OF EXISTING RESTAURANT NOT SHOWN AND
 CANNOT BE DETERMINED AS KITCHEN/BATHROOM/WAITING AREAS
 NOT SHOWN.
  
 PROVIDE A LIFE SAFETY PLAN, FBC CHAPTER 10. EXITING
 STRATEGY NOT CLEAR. A DOOR IS SHOWN AS "EMERGENCY
 EGRESS," EXIT SIGNS SHOWN, BUT EXITING PATH NOT SHOWN.
 SEE ALSO FBC 1008.1.2 AND 1008.1.10. INCLUDE ELEVATION
 CHANGES, IF ANY, WHICH EXIST THROUGHOUT THE PROPOSED
 MEANS OF EGRESS PATH.
  
 2ND REVIEW -
  
 DOOR STILL REFERENCED AS "EMERGENCY EGRESS." PLEASE
 ADVISE AS TO WHERE THE DEFINITION OF "EMERGENCY EGRESS"
 IS LOCATED IN FBC CHAPTER 10. IT IS NOT CLEAR WHAT
 FUNCTION THIS SERVES IN THE LIFE SAFETY PLAN. FBC 107.
  
 COURTYARD IS SHOWN AS "EXISTING OCCUPANCY" WITH 50 MAX.
 BASED ON THE PHOTOGRAPH ON THE PLAN AS WELL AS AERIALS,
 THIS ISS STORAGE, NOW PROPOSED AS A2, SO HOW CAN THIS
 BE "EXISTING OCCUPANCY"? OCCUPANT LOAD CANNOT BE LESS
 THAN FBC TABLE 1004.1.1.
  
 PLAN NOTES THAT THE COURTYARD IS OPEN TO THE PARKING
 LOT, WITH NO FENCE OR WALL, BUT AERIALS AND THE
 PHOTOGRAPH ON THE PLAN SHOW A FENCE, SO PLAN IS NOT
 CONSISTENT WITH JOB CONDITIONS. SHOW FENCE ON THE PLAN,
 AND INDICATE WHETHER THIS WILL BE REMOVED OR REMAIN.
 NOT ENOUGH INFORMATION HAS BEEN PROVIDED TO DETERMINE
 REQUIREMENTS FOR THIS AREA.
  
 ELEVATION CHANGES NOT SHOWN.
  
 4. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD
 REQUIRED, FAC9N-3, FBC 107 (DOOR). INDICATE HARDWARE
 AND THRESHOLD OPTIONS, SEE FBC 1008.1, FBC 1008.1.10
 AND FBC 2010 ACCESSIBILITY 404.
  
 2ND REVIEW, NOT ADDRESSED. ARCHITECT'S RESPONSE IS THAT
 PRODUCT APPROVAL IS ATTACHED.
  
 PANIC DEVICE REQUIRED, BUT NOT FOUND IN THE PRODUCT
 APPROVAL. SEE FBC 1008.1.10 AND FBC 1008.1. THRESHOLD
 NOT INDICATED, SEE FBC 2010 ACCESSIBILITY 404.
  
 5. PROVIDE A DETAIL FOR THE PROPOSED GATE. CODE
 REFERENCE AND REQUIREMENTS CANNOT BE PROVIDED AT THIS
 TIME, SEE ITEM 3. IF THERE ARE NO CODE REQUIREMENTS FOR
 THE GATE, THIS MAY NOT BE REQUIRED.
  
 NOT ADDRESSED. PHOTOGRAPH APPEARS TO SHOW A METAL
 SCREEN WITH MULTIPLE HINGES (3 PANELS). THE PHOTOGRAPH
 STATES "DECORATIVE ONLY - NO LOCK." INDICATE IN FBC
 CHAPTER 10 WHERE THIS IS PERMITTED. SEE FBC 1008.2. NOT
 ENOUGH INFORMATION PROVIDED TO DETERMINE CODE
 COMPLIANCE.
  
 6. OK
  
 NOT ENOUGH ACCURATE INFORMATION PROVIDED TO PROVIDE A
 COMPLETE CHECKLIST. FBC 107
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-19 Cont ID  
Sent By shill Date 2013-10-19 Time 10:12 Rev Time 0.00
Received By shill Date 2013-10-17 Time 07:09 Sent To FIRE
Notes
2013-10-19 10:49:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 1. SIGNAGE TO BE SUBMITTED SEPARATELY (ADVISORY ONLY).
  
 2. NEW FIXTURES SHOWN. NO ELECTRICAL REVIEW HAS BEEN
 DONE AT THIS TIME BUT PLEASE BE ADVISED THAT A SEPARATE
 ELECTRICAL PERMIT (WITH PLANS) WILL BE REQUIRED
 (ADVISORY ONLY).
  
 3. REVISE PLAN TO SHOW OCCUPANCY CLASSIFICATION AND
 OCCUPANT LOAD FOR THE EXISTING BUILDING AND EXTERIOR
 COURTYARD. IT APPEARS THAT THE COURTYARD AREA IS
 CURRENTLY USED AS STORAGE AND WILL NOW BE A2. 1300
 SF/15 IS AN OCCUPANT LOAD OF 87 FOR THE COURTYARD.
 OCCUPANT LOAD OF EXISTING RESTAURANT NOT SHOWN AND
 CANNOT BE DETERMINED AS KITCHEN/BATHROOM/WAITING AREAS
 NOT SHOWN.
  
 PROVIDE A LIFE SAFETY PLAN, FBC CHAPTER 10. EXITING
 STRATEGY NOT CLEAR. A DOOR IS SHOWN AS "EMERGENCY
 EGRESS," EXIT SIGNS SHOWN, BUT EXITING PATH NOT SHOWN.
 SEE ALSO FBC 1008.1.2 AND 1008.1.10. INCLUDE ELEVATION
 CHANGES, IF ANY, WHICH EXIST THROUGHOUT THE PROPOSED
 MEANS OF EGRESS PATH.
  
 4. PRODUCT APPROVALS REVIEWED BY DESIGNER OF RECORD
 REQUIRED, FAC9N-3, FBC 107 (DOOR). INDICATE HARDWARE
 AND THRESHOLD OPTIONS, SEE FBC 1008.1.10 AND FBC 2010
 ACCESSIBILITY 404.
  
 5. PROVIDE A DETAIL FOR THE PROPOSED GATE. CODE
 REFERENCE AND REQUIREMENTS CANNOT BE PROVIDED AT THIS
 TIME, SEE ITEM 3. IF THERE ARE NO CODE REQUIREMENTS FOR
 THE GATE, THIS MAY NOT BE REQUIRED.
  
 6. TWO COMPLETE SETS OF PERMIT DOCUMENTS REQUIRED, FBC
 107. ONLY ONE SET OF PLANS PROVIDED. THE CRA
 INFORMATION IS NOT REQUIRED FOR PERMITTING.
  
  
  
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2013-12-19 Cont ID  
Sent By lphilmor Date 2013-12-19 Time 15:40 Rev Time 0.00
Received By lphilmor Date 2013-12-19 Time 15:38 Sent To  
Notes
2013-12-19 15:40:28427 NORTHWOOD ROAD
 PERMIT #13090969
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
  
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-10-22 Cont ID  
Sent By lphilmor Date 2013-10-22 Time 11:01 Rev Time 0.00
Received By lphilmor Date 2013-10-22 Time 10:44 Sent To  
Notes
2013-10-22 10:48:21427 NORTHWOOD ROAD
 PERMIT #13090969
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE TWO STAMPED SET OF PLANS FOR REVIEW.
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
 PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING
 ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE
 ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN
 HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE
 BACKGROUND.
 PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY TYPES,
 OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, EMERGENCY
 LIGHTING, TRAVEL DISTANCES, COMMON PATH OF TRAVEL ETC.
 PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS
 SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE
 TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY.
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-26 Cont ID  
Sent By shill Date 2013-12-26 Time 17:29 Rev Time 0.00
Received By shill Date 2013-11-21 Time   Sent To  
Notes
2013-12-05 07:18:3112/5 TO ZONING
  
2013-11-21 15:42:27MISC 1
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-22 Cont ID  
Sent By shill Date 2013-10-22 Time 11:04 Rev Time 0.00
Received By shill Date 2013-09-30 Time 08:02 Sent To  
Notes
2013-10-01 08:03:13SENT TO ZONING BOX

Review Stop Z ZONING
Rev No 2 Status P Date 2013-12-10 Cont ID  
Sent By llouie Date 2013-12-10 Time 08:32 Rev Time 0.00
Received By llouie Date 2013-12-10 Time 08:32 Sent To FIRE
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-08 Cont ID  
Sent By llouie Date 2013-10-08 Time 10:58 Rev Time 0.00
Received By llouie Date 2013-10-08 Time 10:58 Sent To B
Notes
2013-10-08 11:00:20** FAILED **
  
 PLEASE ADDRESS THE FOLLOWING. RESPOND TO THE COMMENTS
 IN WRITING AND/OR ON THE PLANS WHERE APPLICABLE:
  
 1.) TWO (2) SETS OF PLANS ARE REQUIRED FOR THE
 SUBMITTAL. ONLY ONE (1) SET OF PLANS HAVE BEEN
 SUBMITTED WITH THE PERMIT PACKAGE.
  
 2.) A SEPARATE SIGN PERMIT IS REQUIRED FOR THE APPROVAL
 OF SIGNAGE. PROVIDE COMPLETE DIMENSIONS FOR THE
 PROPOSED SIGNAGE WITH THE SUBMITTAL OF THE SIGN PERMIT.
  
 PLEASE CONTACT LINDA LOUIE @ (561) 822-1442 IF YOU HAVE
 ANY QUESTIONS.
  