Plan Review Details - Permit 13090955
Plan Review Stops For Permit 13090955
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-10-23 Cont ID  
Sent By jwitmer Date 2013-10-23 Time 09:53 Rev Time 0.00
Received By jwitmer Date 2013-10-23 Time 09:22 Sent To  
Notes
2013-10-23 10:33:21BUILDING PLAN REVIEW
 MASTER PERMIT: 12040784
 REVISION # 13090955 PHASED WORK TRANSFORMER ROOM
 ADD: 6651 N JOG RDFCONT: KBR
 TEL: (561
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 1ST REVIEW
 DATE: WED. OCT. 23/ 2013
 ACTION: BUILDING PROVISO:
 MISSING PRODUCT APPROVALS FOR NEW BUILDING A REVISION
 IS REQUIRED.
  
 1) 2010 FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 2) 010 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.41 COMPONENTS & CLADDING
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B), WALL LOUVERS,
 (C) ROOFING PRODUCTS AND ASSEMBLIES
  
 3) 11/14/2013 THIS ROOM IS A INTERIOR ROOM THE ABOVE
 PRODUCT APPROVALS IS NOT REQUIRED, THE CITY'S CHIEF
 ELECTRICAL INSPECTOR & PLANS EXAMINER HAS REVIEWED THIS
 PLANS, THE SIZE OF THE TRANSFORMERS AND DECLARED IT A
 TRANSFORMER VAULT, THAT REQUIRES 3 HR FIRE RATED
 FLOORS, WALLS & CEILINGS WITH 2 HOUR OPENING
 PROTECTIVES, PLEASE PROVIDE THE 2 HOUR OPENING
 PROTECTIVES FOR OPENINGS AND PROVIDE HOW THE STEEL
 BEAMS AND COLUMNS THAT MAKE UP THE ENCLOSURE WILL BE
 FIRE RATED TO THE 3 HOUR REQUIREMENT. ALSO SEE FIRE
 COMMENTSAND REQUIREMENTS FOR A TRANSFORMER VAULT.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-12 Cont ID  
Sent By albarran Date 2013-11-12 Time 10:09 Rev Time 0.00
Received By albarran Date 2013-11-12 Time 09:29 Sent To  
Notes
2013-11-12 10:10:37THE ELECTRICAL SCOPE OF THIS PERMIT IS LIMITED TO THE
 INSTALLATION OF THE ITEMS DESCRIBED HEREIN.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-11-13 Cont ID  
Sent By wjolin Date 2013-11-13 Time 10:35 Rev Time 0.00
Received By wjolin Date 2013-11-13 Time 09:44 Sent To  
Notes
2013-11-13 10:34:396651 NORTH JOG ROAD - TRANSFORMER ROOM/VAULT
 TRACKING #13090955
 MASTER #12040748
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PER NFPA 70 - ARTICL 450: PART III. TRANSFORMER VAULTS
  
 450.42 WALLS, ROOFS, AND FLOORS. THE WALLS AND ROOFS OF
 VAULTS SHALL BE CONSTRUCTED OF MATERIALS THAT HAVE
 ADEQUATE STRUCTURAL STRENGTH FOR THE CONDITIONS WITH A
 MINIMUM FIRE RESISTANCE OF 3 HOURS. THE FLOORS OF
 VAULTS IN CONTACT WITH THE EARTH SHALL BE OF CONCRETE
 THAT IS NOT LESS THAN 4-INCHES THICK, BUT WHERE THE
 VAULT IS CONSTRUCTED WITH A VACANT SPACE OR OTHER
 STORIES BELOW IT, THE FLOOR SHALL HAVE ADEQUATE
 STRUCTURAL STRENGTH FOR THE LOAD IMPOSED THEREON AND A
 MINIMUM FIRE RESISTANCE OF 3 HOURS. FOR THE PURPOSES OF
 THIS SECTION, STUDS AND WALLBOARD CONSTRUCTION SHALL
 NOT BE ACCEPTABLE.
 EXCEPTION: WHERE TRANSFORMERS ARE PROTECTED WITH
 AUTOMATIC SPRINKLER, WATER SPRAY, CARBON DIOXIDE, OR
 HALON, CONSTRUCTION OF 1-HOUR RATING SHALL BE
 PERMITTED.
  
 (A) TYPE OF DOOR. EACH DOORWAY LEADING INTO A VAULT
 FROM THE BUILDING INTERIOR SHALL BE PROVIDED WITH A
 TIGHT-FITTING DOOR THAT HAS A MINIMUM FIRE RATING OF 3
 HOURS. THE AUTHORITY HAVING JURISDICTION SHALL BE
 PERMITTED TO REQUIRE SUCH A DOOR FOR AN EXTERIOR WALL
 OPENING WHERE CONDITIONS WARRANT.
 EXCEPTION: WHERE TRANSFORMERS ARE PROTECTED WITH
 AUTOMATIC SPRINKLER, WATER SPRAY, CARBON DIOXIDE, OR
 HALON, CONSTRUCTION OF 1-HOUR RATING SHALL BE
 PERMITTED.
  
 (B) SILLS. A DOOR SILL OR CURB THAT IS OF SUFFICIENT
 HEIGHT TO CONFINE THE OIL FROM THE LARGEST TRANSFORMER
 WITHIN THE VAULT SHALL BE PROVIDED, AND IN NO CASE
 SHALL THE HEIGHT BE LESS THAN 4-INCHES.
  
 (C) LOCKS. DOORS SHALL BE EQUIPPED WITH LOCKS, AND
 DOORS SHALL BE KEPT LOCKED, ACCESS BEING ALLOWED ONLY
 TO QUALIFIED PERSONS. PERSONNEL DOORS SHALL SWING OUT
 AND BE EQUIPPED WITH PANIC BARS, PRESSURE PLATES, OR
 OTHER DEVICES THAT ARE NORMALLY LATCHED BUT OPEN UNDER
 SIMPLE PRESSURE.
  
 WESLEY JOLIN
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 805-6730

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-11-23 Cont ID  
Sent By rregueir Date 2013-11-23 Time 12:48 Rev Time 0.00
Received By rregueir Date 2013-10-02 Time 16:13 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-23 Cont ID  
Sent By rregueir Date 2013-11-23 Time 12:48 Rev Time 0.00
Received By rregueir Date 2013-11-23 Time 12:48 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-12-18 Cont ID  
Sent By rregueir Date 2013-12-18 Time 15:13 Rev Time 0.00
Received By rregueir Date 2013-12-06 Time 15:12 Sent To  
Notes
***NONE***