Plan Review Details - Permit 13090924
Plan Review Stops For Permit 13090924
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-10-18 Cont ID  
Sent By jwitmer Date 2013-10-18 Time 15:57 Rev Time 0.00
Received By jwitmer Date 2013-10-18 Time 15:57 Sent To  
Notes
2013-10-18 16:02:23BUILDING PLAN REVIEW
 PERMIT: 13090924
 ADD: 2480 PRESIDENTIAL WAY SUITE # 1402
 CONT: SUNBEC LLC
 TEL: (561)929-0577
  
 2010 FLORIDA BUILDING CODE W
 * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: FRIDAY OCT. 18/ 2013
 ACTION: BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 PLEASE PROVIDE COMPLIANCE FOR THE FOLLOWING:
 1A) FBC-B 2010 1207.3 STRUCTURE-BORNE SOUND.
 FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR
 BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA
 WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION
 CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD
 TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492.
 1B) FBC-B 2010 603.2 EXCEPTION (1) TILE FLOORING
 FLOOR INSULATION PLACED BETWEEN TWO LAYERS OF
 NONCOMBUSTIBLE MATERIALS WITHOUT AN INTERVENING
 AIRSPACE SHALL BE ALLOWED TO HAVE A FLAME SPREAD INDEX
 OF NOT MORE THAN 100.
  
 FBC-B 2010
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-11-13 Cont ID  
Sent By albarran Date 2013-11-13 Time 19:23 Rev Time 0.00
Received By albarran Date 2013-11-13 Time 18:56 Sent To I
Notes
2013-11-13 19:24:31SEE CORRECTION NOTE 25 ON PAGE E1
  
 SENT TO SH DESK

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-24 Cont ID  
Sent By albarran Date 2013-10-24 Time 19:28 Rev Time  
Received By albarran Date   Time   Sent To I
Notes
2013-10-24 19:39:52THE NEC HAS SPECIFIC LIGHTING REQUIREMENTS FOR
 RESIDENTIAL APPLICATIONS WHETHER EXISTING OR NEW, THEY
 ARE NOT REFLECTED ON THE SUBMITTED DRAWINGS. THE 2008
 EDITION OF THE NEC REQUIRES AN OUTLET ON THE BALCONY IF
 GREATER THAN 20 SQ. FT. NEC 406.11 REQUIRES
 TAMPER-RESISTANT RECEPTACLES.
 CORRECT THE ELECTRICAL DRAWINGS TO MEET THE
 REQUIREMENTS AND RESUBMIT, WHILE AT IT, RELOCATE THE
 LIGHT SWITCH AT THE ENTRY FROM BEHIND THE DOOR SWING.
  
 SENT TO SH DESK

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-10-07 Cont ID  
Sent By scaldero Date 2013-10-07 Time 15:29 Rev Time 0.00
Received By scaldero Date 2013-10-07 Time 15:18 Sent To  
Notes
2013-10-07 15:26:16PERMIT #13090924
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION AND
 DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS OF
 NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE
 REMOVED FROM THE SITE DAILY. SMOKING SHALL BE
 PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL
 OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO
 SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE
 RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED.
  
  
 SUE ELLEN CALDERON
 FIRE INVESTIGATOR & INSPECTOR
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4751
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-11-14 Cont ID  
Sent By shill Date 2013-11-14 Time 11:04 Rev Time 0.00
Received By shill Date 2013-11-12 Time 18:47 Sent To  
Notes
2013-11-13 18:47:58SENT TO ELECTRICAL BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-25 Cont ID  
Sent By shill Date 2013-10-25 Time 08:59 Rev Time 0.00
Received By shill Date 2013-09-27 Time 06:07 Sent To  
Notes
2013-09-28 06:07:17B10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-10-23 Cont ID  
Sent By rregueir Date 2013-10-23 Time 13:11 Rev Time 0.00
Received By rregueir Date 2013-10-23 Time 13:11 Sent To  
Notes
2013-10-23 13:12:00MECHANICAL SCOPE ADDED TO DESCRIPTION ON APPLICATION.
 NO PLAN REVIEW REQUIRED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-17 Cont ID  
Sent By hmoser Date 2013-10-17 Time 12:20 Rev Time 0.00
Received By hmoser Date 2013-10-17 Time 12:08 Sent To  
Notes
2013-10-17 12:20:52PLANS DENIED
 NO MECHANICAL PLAN SUBMITTED.
 REVIEW BY HAROLD MOSER
 [email protected]
 OFFICE 561-805-6732
 FAX 561-805-6676

Review Stop P PLUMBING
Rev No 1 Status P Date 2013-09-30 Cont ID  
Sent By lwagner Date 2013-09-30 Time 14:43 Rev Time 0.00
Received By lwagner Date 2013-09-30 Time 14:31 Sent To  
Notes
***NONE***