Plan Review Details - Permit 13090923
Plan Review Stops For Permit 13090923
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By jwitmer Date 2013-10-28 Time 10:13 Rev Time 0.00
Received By jwitmer Date 2013-10-28 Time 09:30 Sent To  
Notes
2013-10-28 10:16:56ELECTRICAL ROOM # 1
 PROVISO:
 SHEET A1.1:
 1) STEEL COLUMN TO BE PAINTED WITH 2 HOUR INTUMESCENT
 PAINT, SUBMIT MANUFACTURERS CUT SHEETS.
 2) JOINT SYSTEMS BETWEEN STEEL AND BLOCK WORK, 2 HOUR
 JOINT SYSTEM PLEASE PROVIDE MANUFACTURERS CUT SHEETS.
  
 11/14/2013 OUR ELECTRICAL PLAN REVIEWER DOUG HARVEY DID
 NOT BELIEVE THE FIRE RATINGS OF THIS ROOM SHOULD BE
 DECREASE AT THIS TIME SINCE THE VOLTAGES WERE NOT
 PROVIDED ON THE PLANS.
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-11-08 Cont ID  
Sent By albarran Date 2013-11-08 Time 16:19 Rev Time 0.00
Received By albarran Date 2013-11-08 Time 14:56 Sent To  
Notes
2013-11-08 16:22:33AS THIS IS A PHASED PROJECT, THE ELECTRICAL SCOPE OF
 THIS PERMIT IS LIMITED ONLY TO THE ELECTRICAL
 INSTALLATION OF THE LIGHTING AND RECEPTACLES WITHIN THE
 BLDG. ALL LIGHTING CONTROLS AND SOURCES OF POWER TO THE
 APPARATUS HEREIN INSTALLED IS BEYOND THE SCOPE OF THIS
 PERMIT

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2013-11-13 Cont ID  
Sent By wjolin Date 2013-11-13 Time 09:43 Rev Time 0.00
Received By wjolin Date 2013-11-13 Time 09:31 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2013-11-23 Time   Rev Time 0.00
Received By rregueir Date 2013-10-02 Time 15:07 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2013-11-23 Cont ID  
Sent By rregueir Date 2013-11-23 Time 12:41 Rev Time 0.00
Received By rregueir Date 2013-11-23 Time 12:41 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2013-10-23 Cont ID  
Sent By lwagner Date 2013-10-23 Time 10:04 Rev Time 0.00
Received By lwagner Date 2013-10-23 Time 09:54 Sent To  
Notes
***NONE***

Review Stop SIGNATURE ELECTRONIC SIGNATURE SHEET
Rev No 1 Status P Date 2013-12-18 Cont ID  
Sent By rregueir Date 2013-12-18 Time 15:23 Rev Time 0.00
Received By rregueir Date 2013-12-06 Time 15:23 Sent To  
Notes
***NONE***