| Plan Review Stops For Permit 13090912 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-12 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-12 |
Time |
06:45 |
Sent To |
Z |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2013-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-10-29 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-10-29 |
Time |
05:43 |
Sent To |
|
|
| Notes |
| 2013-10-29 07:44:12 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THE EXPOSURE CATEGORY "B" SPECIFIED ON SHEET S-1 IS | | | INCORRECT. THE STRUCTURE IS LOCATED WITHIN 100 FEET OF | | | A OPEN AREA OF SURFACE ROUGHNESS C-TYPE TERRAIN THAT | | | EXTENDS MORE THAN 600 FEET AND IS WIDER THAN 150 FEET. | | | THEREFORE, IT IS EXPOSURE "C". FBC R301.2.1.4.2 AND | | | R301.2.1.3 | | | | | | 2) THE DESIGN PRESSURES IN THE SCHEDULE ON SHEET S-1 | | | ARE HIGHER THAN IS REQUIRED FOR WALL ZONES 4 AND 5 OF A | | | DWELLING WITH A 15 FT OR LESS MEAN ROOF HEIGHT LOCATED | | | IN EXPOSURE C WITH A WIND SPEED OF 170 MPH VULT / 132 | | | MPH VASD. WALL ZONE 5 PRESSURES FOR 10 SQFT ARE + 38 | | | PSF, - 51 PSF. SEE FBC TABLES R301.2(2) AND R301.2(3). | | | | | | 3) PROVIDE A STRUCTURAL DETAIL FOR THE OPENING IN-FILL | | | FRAMING. SPECIFY THE ANCHORS AND CONNECTORS. FBC R601.2 | | | | | | 4) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF | | | VENTILATION. | | | | | | 5) SHOW COMPLIANCE WITH FBC R314.3.1 FOR REQUIRED SMOKE | | | ALARMS. ALTERATIONS, REPAIRS AND ADDITIONS. | | | WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A | | | PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE | | | ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL | | | DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS | | | LOCATED AS REQUIRED FOR NEW DWELLINGS. | | | | | | 6) THE PROPOSED FLOOR PLAN ON SHEET A-1 SPECIFIES A | | | FIXED WINDOW AT THE NEW BATHROOM AND THE PROPOSED | | | WINDOW TYPE IS NOT SPECIFIED FOR THE WINDOW IN THE | | | STUDY. PRODUCT APPROVALS WERE SUBMITTED FOR A | | | HORIZONTAL SLIDING WINDOW AND A SINGLE HUNG WINDOW. | | | PLEASE CLARIFY THE LOCATIONS AND TYPES OF WINDOWS. CITY | | | AMENDMENTS 107.2.1 | | | | | | 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SIMPSON | | | CONNECTORS SPECIFIED ON THE PLANS. DCA RULE 9N-3 | | | | | | 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGN PROFESSIONAL PER | | | CITY AMENDMENTS 107.3.4.1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
P |
Date |
2013-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-10-29 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-10-29 |
Time |
05:47 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2013-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-12 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-02 |
Time |
16:13 |
Sent To |
|
|
| Notes |
| 2013-12-02 16:13:23 | SENT TO R MCDOUGAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2013-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-10-29 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-09-27 |
Time |
05:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
2 |
Status |
P |
Date |
2013-12-17 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-17 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-17 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2013-12-17 10:33:24 | MU 2013-26145 |
|
|
| Review Stop |
IMPACT |
COUNTY IMPACT FEES |
| Rev No |
1 |
Status |
F |
Date |
2013-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-10-29 |
Time |
05:44 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-10-29 |
Time |
05:44 |
Sent To |
|
|
| Notes |
| 2013-10-29 05:47:25 | ONE SET OF APPROVED PLANS WILL BE REQUIRED TO BE SIGNED | | | OUT AND TAKEN TO PALM BEACH COUNTY FOR AN IMPACT FEE | | | REVIEW. THE STAMPED PLANS AND A COPY OF THE PAID IMPACT | | | FEE RECIEPT SHALL BE RETURNED TO THE WPB BUILDING | | | DEPARTMENT BEFORE THE PERMIT IS ISSUED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2013-12-16 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-16 |
Time |
10:43 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-16 |
Time |
10:36 |
Sent To |
|
|
| Notes |
| 2013-12-16 10:43:47 | 2010 FBC | | | | | | HVAC LOAD CALCULATIONS WERE SUBMITTED AND APPROVED. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-12 |
Time |
09:17 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-12 |
Time |
06:45 |
Sent To |
|
|
| Notes |
| 2013-12-12 11:40:12 | APPROVED WITH EXCEPTION. REVISION REQUIRED. | | | | | | SUBMIT (2) SETS OF HEATING AND COOLING LOAD | | | CALCULATIONS FOR REVIEW THAT MATCH THE SPECIFIED | | | EQUIPMENT. FBCR M1401.3 ACCA MANUAL J OR OTHER APPROVED | | | HEATING AND COOLING CALCULATION METHODOLOGIES. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2013-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-10-29 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-10-29 |
Time |
05:44 |
Sent To |
|
|
| Notes |
| 2013-10-29 08:41:43 | 2010 FBC | | | | | | DENIED BY MECHANICAL | | | | | | 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS | | | FOR THE ADDITION AS REQUIRED BY FBC M1401.3. | | | | | | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S | | | SPECIFICATIONS AND LISTING INFORMATION FOR THE | | | MINI-SPLIT SYSTEM. FBC M1401.1 AND M1302.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-12-12 |
Time |
06:59 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-12-12 |
Time |
06:45 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2013-10-29 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2013-10-29 |
Time |
06:42 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2013-10-29 |
Time |
05:44 |
Sent To |
|
|
| Notes |
| 2013-10-29 06:41:48 | 2010 FBC | | | | | | DENIED BY PLUMBING | | | | | | 1) P3005.1.1 HORIZONTAL TO VERTICAL (MULTIPLE | | | CONNECTION FITTINGS).DOUBLE SANITARY TEE PATTERNS SHALL | | | NOT RECEIVE THE DISCHARGE OF BACK-TO-BACK WATER CLOSETS | | | AND FIXTURES OR APPLIANCES WITH PUMPING ACTION | | | DISCHARGE. SEE WASHER AND LAVATORY CONNECTION ON SHEET | | | A-1. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2013-12-12 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2013-12-12 |
Time |
16:51 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2013-12-12 |
Time |
13:54 |
Sent To |
|
|
| Notes |
| 2013-12-12 16:51:28 | 12/12/13 | | | PLANS REVISED FROM INITIAL REVIEW AND RESUBMITTED TO | | | ZONING FOR REVIEW AND SIGN-OFF. -DK | | 2013-12-12 13:55:28 | 12/12/13 - ZONING RECEIVED. SENT TO DK FOR REVIEW. LL |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2013-09-30 |
|
|
Cont ID |
|
| Sent By |
dkittred |
Date |
2013-09-30 |
Time |
15:57 |
Rev Time |
0.00 |
| Received By |
dkittred |
Date |
2013-09-30 |
Time |
11:44 |
Sent To |
|
|
| Notes |
| 2013-09-30 10:59:23 | 9/30/13 |
|
|