Plan Review Details - Permit 13090912
Plan Review Stops For Permit 13090912
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-12 Cont ID  
Sent By rmcdouga Date 2013-12-12 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2013-12-12 Time 06:45 Sent To Z
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-29 Cont ID  
Sent By rmcdouga Date 2013-10-29 Time 10:59 Rev Time 0.00
Received By rmcdouga Date 2013-10-29 Time 05:43 Sent To  
Notes
2013-10-29 07:44:122010 FBC
  
 DENIED BY BUILDING
  
 1) THE EXPOSURE CATEGORY "B" SPECIFIED ON SHEET S-1 IS
 INCORRECT. THE STRUCTURE IS LOCATED WITHIN 100 FEET OF
 A OPEN AREA OF SURFACE ROUGHNESS C-TYPE TERRAIN THAT
 EXTENDS MORE THAN 600 FEET AND IS WIDER THAN 150 FEET.
 THEREFORE, IT IS EXPOSURE "C". FBC R301.2.1.4.2 AND
 R301.2.1.3
  
 2) THE DESIGN PRESSURES IN THE SCHEDULE ON SHEET S-1
 ARE HIGHER THAN IS REQUIRED FOR WALL ZONES 4 AND 5 OF A
 DWELLING WITH A 15 FT OR LESS MEAN ROOF HEIGHT LOCATED
 IN EXPOSURE C WITH A WIND SPEED OF 170 MPH VULT / 132
 MPH VASD. WALL ZONE 5 PRESSURES FOR 10 SQFT ARE + 38
 PSF, - 51 PSF. SEE FBC TABLES R301.2(2) AND R301.2(3).
  
 3) PROVIDE A STRUCTURAL DETAIL FOR THE OPENING IN-FILL
 FRAMING. SPECIFY THE ANCHORS AND CONNECTORS. FBC R601.2
  
 4) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF
 VENTILATION.
  
 5) SHOW COMPLIANCE WITH FBC R314.3.1 FOR REQUIRED SMOKE
 ALARMS. ALTERATIONS, REPAIRS AND ADDITIONS.
 WHEN ALTERATIONS, REPAIRS OR ADDITIONS REQUIRING A
 PERMIT OCCUR, OR WHEN ONE OR MORE SLEEPING ROOMS ARE
 ADDED OR CREATED IN EXISTING DWELLINGS, THE INDIVIDUAL
 DWELLING UNIT SHALL BE EQUIPPED WITH SMOKE ALARMS
 LOCATED AS REQUIRED FOR NEW DWELLINGS.
  
 6) THE PROPOSED FLOOR PLAN ON SHEET A-1 SPECIFIES A
 FIXED WINDOW AT THE NEW BATHROOM AND THE PROPOSED
 WINDOW TYPE IS NOT SPECIFIED FOR THE WINDOW IN THE
 STUDY. PRODUCT APPROVALS WERE SUBMITTED FOR A
 HORIZONTAL SLIDING WINDOW AND A SINGLE HUNG WINDOW.
 PLEASE CLARIFY THE LOCATIONS AND TYPES OF WINDOWS. CITY
 AMENDMENTS 107.2.1
  
 7) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE SIMPSON
 CONNECTORS SPECIFIED ON THE PLANS. DCA RULE 9N-3
  
 8) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGN PROFESSIONAL PER
 CITY AMENDMENTS 107.3.4.1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-29 Cont ID  
Sent By rmcdouga Date 2013-10-29 Time 11:23 Rev Time 0.00
Received By rmcdouga Date 2013-10-29 Time 05:47 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-12 Cont ID  
Sent By rmcdouga Date 2013-12-12 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2013-12-02 Time 16:13 Sent To  
Notes
2013-12-02 16:13:23SENT TO R MCDOUGAL

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-29 Cont ID  
Sent By rmcdouga Date 2013-10-29 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2013-09-27 Time 05:51 Sent To  
Notes
2013-09-28 05:53:42R02

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status P Date 2013-12-17 Cont ID  
Sent By rmcdouga Date 2013-12-17 Time 10:32 Rev Time 0.00
Received By rmcdouga Date 2013-12-17 Time 10:32 Sent To  
Notes
2013-12-17 10:33:24MU 2013-26145

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-10-29 Cont ID  
Sent By rmcdouga Date 2013-10-29 Time 05:44 Rev Time 0.00
Received By rmcdouga Date 2013-10-29 Time 05:44 Sent To  
Notes
2013-10-29 05:47:25ONE SET OF APPROVED PLANS WILL BE REQUIRED TO BE SIGNED
 OUT AND TAKEN TO PALM BEACH COUNTY FOR AN IMPACT FEE
 REVIEW. THE STAMPED PLANS AND A COPY OF THE PAID IMPACT
 FEE RECIEPT SHALL BE RETURNED TO THE WPB BUILDING
 DEPARTMENT BEFORE THE PERMIT IS ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2013-12-16 Cont ID  
Sent By rmcdouga Date 2013-12-16 Time 10:43 Rev Time 0.00
Received By rmcdouga Date 2013-12-16 Time 10:36 Sent To  
Notes
2013-12-16 10:43:472010 FBC
  
 HVAC LOAD CALCULATIONS WERE SUBMITTED AND APPROVED.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2013-12-12 Cont ID  
Sent By rmcdouga Date 2013-12-12 Time 09:17 Rev Time 0.00
Received By rmcdouga Date 2013-12-12 Time 06:45 Sent To  
Notes
2013-12-12 11:40:12APPROVED WITH EXCEPTION. REVISION REQUIRED.
  
 SUBMIT (2) SETS OF HEATING AND COOLING LOAD
 CALCULATIONS FOR REVIEW THAT MATCH THE SPECIFIED
 EQUIPMENT. FBCR M1401.3 ACCA MANUAL J OR OTHER APPROVED
 HEATING AND COOLING CALCULATION METHODOLOGIES.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2013-10-29 Cont ID  
Sent By rmcdouga Date 2013-10-29 Time 08:47 Rev Time 0.00
Received By rmcdouga Date 2013-10-29 Time 05:44 Sent To  
Notes
2013-10-29 08:41:432010 FBC
  
 DENIED BY MECHANICAL
  
 1) SUBMIT TWO COPIES OF EQUIPMENT SIZING CALCULATIONS
 FOR THE ADDITION AS REQUIRED BY FBC M1401.3.
  
 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS AND LISTING INFORMATION FOR THE
 MINI-SPLIT SYSTEM. FBC M1401.1 AND M1302.1
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-12-12 Cont ID  
Sent By rmcdouga Date 2013-12-12 Time 06:59 Rev Time 0.00
Received By rmcdouga Date 2013-12-12 Time 06:45 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-10-29 Cont ID  
Sent By rmcdouga Date 2013-10-29 Time 06:42 Rev Time 0.00
Received By rmcdouga Date 2013-10-29 Time 05:44 Sent To  
Notes
2013-10-29 06:41:482010 FBC
  
 DENIED BY PLUMBING
  
 1) P3005.1.1 HORIZONTAL TO VERTICAL (MULTIPLE
 CONNECTION FITTINGS).DOUBLE SANITARY TEE PATTERNS SHALL
 NOT RECEIVE THE DISCHARGE OF BACK-TO-BACK WATER CLOSETS
 AND FIXTURES OR APPLIANCES WITH PUMPING ACTION
 DISCHARGE. SEE WASHER AND LAVATORY CONNECTION ON SHEET
 A-1.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2013-12-12 Cont ID  
Sent By dkittred Date 2013-12-12 Time 16:51 Rev Time 0.00
Received By dkittred Date 2013-12-12 Time 13:54 Sent To  
Notes
2013-12-12 16:51:2812/12/13
 PLANS REVISED FROM INITIAL REVIEW AND RESUBMITTED TO
 ZONING FOR REVIEW AND SIGN-OFF. -DK
2013-12-12 13:55:2812/12/13 - ZONING RECEIVED. SENT TO DK FOR REVIEW. LL

Review Stop Z ZONING
Rev No 1 Status P Date 2013-09-30 Cont ID  
Sent By dkittred Date 2013-09-30 Time 15:57 Rev Time 0.00
Received By dkittred Date 2013-09-30 Time 11:44 Sent To  
Notes
2013-09-30 10:59:239/30/13