Plan Review Details - Permit 13090863
Plan Review Stops For Permit 13090863
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-10-03 Cont ID  
Sent By jwitmer Date 2013-10-03 Time 06:54 Rev Time 0.00
Received By jwitmer Date 2013-10-03 Time 06:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-09-27 Cont ID  
Sent By jwitmer Date 2013-09-27 Time 12:32 Rev Time 0.00
Received By jwitmer Date 2013-09-27 Time 12:10 Sent To  
Notes
2013-09-27 12:22:44BUILDING PLAN REVIEW
 PERMIT: 13090863
 ADD: 525 S FLAGLER SUITE 14-B
 CONT: CAMBRIDGE CONSTRUCTION
 TEL: (561) 784-3722
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SEPT 27/2013
 ACTION: DENIED
  
 1) WEST PALM BEACHAMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION,
 107.3.5.1.1. A FLOOR PLAN OF WHERE WORK WILL BE
 COMPLETED UNDER THIS PERMIT.
  
 2) 2010 FBC-EXISTING BUILDING CODE, CHAPTER 4,
 CLASSIFICATION OF WORK PLEASE PROVIDE WHAT LEVEL OF
 ALTERATION IS TO BE COMPLETED UNDER THIS PERMIT.
  
 3) SCOPE OF WORK TO INDICATE ON THE FLOOR PLAN WHERE
 THE NEW MARBLE FLOORS ARE TO BE INSTALLED. 107.2.1.3.
 ADDITIONAL INFORMATION IS REQUIRED.
  
 4) IS THERE ANY WALLS, SOFFITS OR DROPPED CEILINGS
 BEING MODIFIED, IF SO PLEASE SHOW ON THE FLOOR PLAN?
 107.2.1.3 ADDITIONAL INFORMATION IS REQUIRED.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-10-16 Cont ID  
Sent By dharvey Date 2013-10-16 Time 14:48 Rev Time 0.00
Received By dharvey Date 2013-10-16 Time 14:16 Sent To I
Notes
2013-10-16 14:43:45AS PER FBCR, LEVEL 1 ALTERATIONS ARE LIMITED TO THE
 REMOVE AND REPLACEMENT OF SAME FOR SAME FOR PURPOSES OF
 REPAIRS BASICALLY, BUT FBCR 314 REQUIRES COMPLIANCE
 WITH SMOKE DETECTORS WHENEVER INTERIOR REPAIRS ARE
 MADE, THEREFORE IF SMOKE DETECTORS ARE NOT ALREADY IN
 PLACE, THEY SHALL BE INSTALLED ACCORDING TO FBCR
 REQUIREMENTS FOR INSPECTIONS.
 FURTHERMORE, THE REPLACEMENT OF THE CABINETRY MAY
 INCLUDE THE INSTALLATION OF BACK SPLASH THAT WAS NOT
 ORIGINALLY THERE AS WELL AS MODIFICATION OF THE LAYOUT.
 IN SUCH A CASE, COMPLIANCE WITH NEC 314.20 & 210.52
 MUST BE CONSIDERED.
  
 SENT TO SH BY: MA
  
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-09-27 Cont ID  
Sent By dharvey Date 2013-09-27 Time 08:20 Rev Time 0.00
Received By dharvey Date 2013-09-27 Time 08:17 Sent To  
Notes
2013-09-27 08:20:21PROVIDE FLOOR PLAN INDICATING AREA OF WORK PER FBC-EB.
 DEFINE LEVEL OF ALTERATION PER FBC-EB FOR EVALUATION
 SHOW ELECTRICAL OUTLET LOCATIONS AND IF EXISTING OR NEW
 PROVIDE DETAILS OF HI- HATS AND OTHER LIGHTING WITH
 LABELING INFORMATION
 PROVIDE WIRINING METHOD TO BE USED FOR CODE COMPLIANCE
 ADDITIONAL INFORMATION MAY BE REQUIRED BASED ON
 RESPONSE

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status N Date 2013-09-27 Cont ID  
Sent By wjolin Date 2013-09-27 Time 13:16 Rev Time 0.00
Received By wjolin Date 2013-09-27 Time 13:16 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-10-16 Cont ID  
Sent By dharvey Date 2013-10-16 Time 14:51 Rev Time 0.00
Received By dharvey Date 2013-10-02 Time 18:14 Sent To  
Notes
2013-10-16 14:51:34SENT TO SH DESK BY MA
2013-10-02 18:16:01INCOMING SENT TO B-35 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-02 Cont ID  
Sent By jwitmer Date 2013-09-27 Time 18:14 Rev Time 0.00
Received By jwitmer Date 2013-09-27 Time 18:13 Sent To  
Notes
2013-10-02 14:54:49SENT TO J WITMER

Review Stop P PLUMBING
Rev No 2 Status P Date 2013-10-10 Cont ID  
Sent By lwagner Date 2013-10-10 Time 09:12 Rev Time 0.00
Received By lwagner Date 2013-10-10 Time 08:53 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2013-09-27 Cont ID  
Sent By lwagner Date 2013-09-27 Time 12:43 Rev Time 0.00
Received By lwagner Date 2013-09-27 Time 12:43 Sent To FIRE
Notes
2013-09-27 12:47:54FBC 2010 PLUMBING REVIEW #1
 DENIED:
  
 1) WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION,
 107.3.5.1.1. A FLOOR PLAN OF WHERE WORK WILL BE
 COMPLETED UNDER THIS PERMIT.
  
 2) IF REPLACING PLUMBING FIXTURES ONLY, NO PLUMBING
 RISER DIAGRAM WILL BE REQUIRED.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  