| 2013-09-26 07:21:47 | BUILDING PLAN REVIEW |
| | PERMIT: 13090815 |
| | ADD: 1865 OKEECHOBEE RD |
| | CONT: MCCARTNEY & CO. |
| | TEL: (407)843-1553 |
| | |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SEPT 26/ 2013 |
| | ACTION: DENIED |
| | |
| | BUILDING SHELL BUILT UNDER PERMIT # 02111908 (FILE NET) |
| | |
| | 1) 2010 FBC-B F] 910.2.2 HIGH-PILED COMBUSTIBLE |
| | STORAGE. BUILDINGS AND PORTIONS THEREOF CONTAINING |
| | HIGH-PILED COMBUSTIBLE STOCK OR RACK STORAGE IN ANY |
| | OCCUPANCY GROUP IN ACCORDANCE WITH SECTION 413 AND THE |
| | FLORIDA FIRE PREVENTION CODE. |
| | |
| | 413.1 GENERAL. |
| | HIGH-PILED STOCK OR RACK STORAGE IN ANY OCCUPANCY GROUP |
| | SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE. |
| | |
| | 2) 2010 FBC-B [F] 910.3 DESIGN AND INSTALLATION. THE |
| | DESIGN AND INSTALLATION OF SMOKE AND HEAT VENTS AND |
| | DRAFT CURTAINS SHALL BE AS SPECIFIED IN SECTIONS |
| | 910.3.1 THROUGH 910.3.5.2 AND TABLE 910.3. HIGH PILED |
| | STORAGE WITH STORAGE HEIGHT OF < 20' , DEPTH OF DRAFT |
| | CURTAIN 6' AND MAXIMUM AREA FORMED BY DRAFT |
| | CURTAIN10,000 SQ FT.2A) |
| | |
| | F] 910.3 DESIGN AND INSTALLATION. THE DESIGN AND |
| | INSTALLATION OF SMOKE AND HEAT VENTS AND DRAFT CURTAINS |
| | SHALL BE AS SPECIFIED IN SECTIONS 910.3.1 THROUGH |
| | 910.3.5.2 AND TABLE 910.3. |
| | |
| | [F] 910.3.1 DESIGN. |
| | SMOKE AND HEAT VENTS SHALL BE LISTED AND LABELED TO |
| | INDICATE COMPLIANCE WITH UL 793. |
| | |
| | [F] 910.3.2 VENT OPERATION. |
| | SMOKE AND HEAT VENTS SHALL BE CAPABLE OF BEING OPERATED |
| | BY APPROVED AUTOMATIC AND MANUAL MEANS. AUTOMATIC |
| | OPERATION OF SMOKE AND HEAT VENTS SHALL CONFORM TO THE |
| | PROVISIONS OF SECTIONS 910.3.2.1 THROUGH 910.3.2.3. |
| | |
| | [F] 910.3.2.1 GRAVITY-OPERATED DROP-OUT VENTS. |
| | AUTOMATIC SMOKE AND HEAT VENTS CONTAINING |
| | HEAT-SENSITIVE GLAZING DESIGNED TO SHRINK AND DROP OUT |
| | OF THE VENT OPENING WHEN EXPOSED TO FIRE SHALL FULLY |
| | OPEN WITHIN 5 MINUTES AFTER THE VENT CAVITY IS EXPOSED |
| | TO A SIMULATED FIRE, REPRESENTED BY A TIME-TEMPERATURE |
| | GRADIENT THAT REACHES AN AIR TEMPERATURE OF 500?F |
| | (260?C) WITHIN 5 MINUTES. |
| | |
| | [F] 910.3.2.2 SPRINKLERED BUILDINGS. |
| | WHERE INSTALLED IN BUILDINGS PROVIDED WITH AN APPROVED |
| | AUTOMATIC SPRINKLER SYSTEM, SMOKE AND HEAT VENTS SHALL |
| | BE DESIGNED TO OPERATE AUTOMATICALLY. |
| | |
| | [F] 910.3.2.3 NONSPRINKLERED BUILDINGS. |
| | WHERE INSTALLED IN BUILDINGS NOT PROVIDED WITH AN |
| | APPROVED AUTOMATIC SPRINKLER SYSTEM, SMOKE AND HEAT |
| | VENTS SHALL OPERATE AUTOMATICALLY BY ACTUATION OF A |
| | HEAT-RESPONSIVE DEVICE RATED AT BETWEEN 100?F (38?C) |
| | AND 220?F (104?C) ABOVE AMBIENT. |
| | |
| | EXCEPTION: GRAVITY-OPERATED DROP-OUT VENTS COMPLYING |
| | WITH SECTION 910.3.2.1. |
| | |
| | [F] 910.3.3 VENT DIMENSIONS. |
| | THE EFFECTIVE VENTING AREA SHALL NOT BE LESS THAN 16 |
| | SQUARE FEET (1.5 M2) WITH NO DIMENSION LESS THAN 4 FEET |
| | (1219 MM), EXCLUDING RIBS OR GUTTERS HAVING A TOTAL |
| | WIDTH NOT EXCEEDING 6 INCHES (152 MM). |
| | |
| | [F] 910.3.4 VENT LOCATIONS. |
| | SMOKE AND HEAT VENTS SHALL BE LOCATED 20 FEET (6096 MM) |
| | OR MORE FROM ADJACENT LOT LINES AND FIRE WALLS AND 10 |
| | FEET (3048 MM) OR MORE FROM FIRE BARRIERS. VENTS SHALL |
| | BE UNIFORMLY LOCATED WITHIN THE ROOF IN THE AREAS OF |
| | THE BUILDING WHERE THE VENTS ARE REQUIRED TO BE |
| | INSTALLED BY SECTION 910.2 WITH CONSIDERATION GIVEN TO |
| | ROOF PITCH, DRAFT CURTAIN LOCATION, SPRINKLER LOCATION |
| | AND STRUCTURAL MEMBERS. |
| | |
| | [F] 910.3.5 DRAFT CURTAINS. |
| | WHERE REQUIRED BY TABLE 910.3, DRAFT CURTAINS SHALL BE |
| | INSTALLED ON THE UNDERSIDE OF THE ROOF IN ACCORDANCE |
| | WITH THIS SECTION. |
| | |
| | EXCEPTION: WHERE AREAS OF BUILDINGS ARE EQUIPPED WITH |
| | ESFR SPRINKLERS, DRAFT CURTAINS SHALL NOT BE PROVIDED |
| | WITHIN THESE AREAS. DRAFT CURTAINS SHALL ONLY BE |
| | PROVIDED AT THE SEPARATION BETWEEN THE ESFR SPRINKLERS |
| | AND THE NON-ESFR SPRINKLERS. |
| | |
| | [F] 910.3.5.1 CONSTRUCTION. |
| | DRAFT CURTAINS SHALL BE CONSTRUCTED OF SHEET METAL, |
| | LATH AND PLASTER, GYPSUM BOARD OR OTHER APPROVED |
| | MATERIALS WHICH PROVIDE EQUIVALENT PERFORMANCE TO |
| | RESIST THE PASSAGE OF SMOKE. JOINTS AND CONNECTIONS |
| | SHALL BE SMOKE TIGHT. |
| | |
| | [F] 910.3.5.2 LOCATION AND DEPTH. |
| | THE LOCATION AND MINIMUM DEPTH OF DRAFT CURTAINS SHALL |
| | BE IN ACCORDANCE WITH TABLE 910.3. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |