Plan Review Details - Permit 13090810
Plan Review Stops For Permit 13090810
Review Stop E ELECTRICAL
Rev No 3 Status P Date 2014-07-14 Cont ID  
Sent By dhayes Date 2014-07-14 Time 13:21 Rev Time 0.00
Received By dhayes Date 2014-07-14 Time 13:21 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2014-04-28 Cont ID  
Sent By dhayes Date 2014-04-28 Time 11:51 Rev Time 0.00
Received By dhayes Date 2014-04-28 Time 11:51 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2013-10-28 Cont ID  
Sent By albarran Date 2013-10-28 Time 15:52 Rev Time 0.00
Received By albarran Date 2013-10-28 Time 15:19 Sent To I
Notes
2013-10-28 15:54:01SENT TO SH DESK

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2014-04-25 Cont ID  
Sent By pleduc Date 2014-04-25 Time 13:25 Rev Time 0.00
Received By pleduc Date 2014-04-25 Time 13:13 Sent To E
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2013-10-22 Cont ID  
Sent By lphilmor Date 2013-10-22 Time 14:14 Rev Time 0.00
Received By lphilmor Date 2013-10-22 Time 14:02 Sent To E
Notes
2013-10-22 14:14:391101 N CONGRESS AVE
 PERMIT #13090810
 REVIEW COMMENTS - FIRE DEPARTMENT
  
  
 THE ADDRESS PROVIDED ON THE PLANS DOES NOT MATCH THE
 ADDRESS PROVIDED ON THE PERMIT APPLICATION.
 PROVIDE EQUIPMENT DETAIL FOR THE GENERATOR BEING
 INSTALLED.
  
  
  
  
 LAUREN PHILMORE
 FIRE INSPECTOR II / INVESTIGATOR I
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
 [email protected]
 (561) 804-4783
  
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2014-07-14 Cont ID  
Sent By shill Date 2014-07-14 Time 13:21 Rev Time 0.00
Received By dhayes Date 2014-06-26 Time 12:21 Sent To  
Notes
2014-07-11 15:37:10TO DAH DESK
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2014-05-29 Cont ID  
Sent By dhayes Date 2014-04-28 Time 11:29 Rev Time 0.00
Received By dhayes Date 2014-04-04 Time 08:47 Sent To  
Notes
2014-04-08 08:47:50TO ZONING
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-28 Cont ID  
Sent By jlmitch Date 2013-10-28 Time 18:19 Rev Time 0.00
Received By jlmitch Date 2013-09-25 Time 12:31 Sent To  
Notes
2013-09-25 12:32:07ROUTED TO ZONING

Review Stop Z ZONING
Rev No 3 Status P Date 2014-07-10 Cont ID  
Sent By eschneid Date 2014-07-10 Time 11:01 Rev Time 0.50
Received By eschneid Date 2014-07-10 Time 11:01 Sent To PC
Notes
2014-07-10 11:42:46PASSED W/PROVISO
  
 THE GENERATOR IS SHOWN AT 8.25 FEET IN HEIGHT, NOT
 INCLUDING THE ENGINE EXHAUST WITH RAIN CAP. THE
 EXISTING HEDGE SHALL BE LET GROW TO SCREEN THE FULL
 HEIGHT OF THE GENERATOR, INCLUDING THE ENGINE EXHAUST
 WITH RAIN CAP.
  
  

Review Stop Z ZONING
Rev No 2 Status F Date 2014-04-23 Cont ID  
Sent By ESchneid Date 2014-04-23 Time 09:13 Rev Time 0.50
Received By eschneid Date 2014-04-23 Time 09:13 Sent To FIRE
Notes
2014-04-23 09:14:05FAILED
  
 1) REPEAT COMMENT: NO SURVEY WAS PROVIDED.
  
 2) REPEAT COMMENT: THE SITE PLAN IS INADEQUATE AS IT
 DOES NOT SHOW DIMENSIONS FROM THE PROPOSED GENERATOR
 AND PAD TO THE PROPERTY LINES AND EXISTING STRUCTURES.
 ADDITIONALLY, THE SITE PLAN DOES NOT DESIGNATE WHERE
 THE NEW GENERATOR PAD, AS REFERENCED ON SHEET E.4 IS
 LOCATED. ALL THAT IS REFERENCED IS AN AREA LABELED ?NEW
 ELECTRICAL STUB UP AREA?
  
 3) REPEAT COMMENT: THE GENERATOR IS SHOWN AT 8.25 FEET
 IN HEIGHT, NOT INCLUDING THE ENGINE EXHAUST WITH RAIN
 CAP. THE GENERATOR SHALL BE SCREENED FOR ITS FULL
 HEIGHT BY AN OPAQUE WALL/FENCE WITH GATE AND LANDSCAPE.
 NO PLANS WERE SUBMITTED TO SHOW EITHER EXISTING OR
 PROPOSED SCREENING. PLEASE NOTE THAT IF THE EXISTING
 FENCE AND LANDSCAPE MEET THIS STANDARD, THEN NO
 ADDITIONAL SCREENING IS REQUIRED. GOOGLE STREET VIEW
 DOES NOT PROVIDE VERIFICATION THAT THE EXISTING IS
 ADEQUATELY SCREENED.
  
 4) MORE COMMENTS MAY BE GENERATED WHEN COMPLETE PLANS
 ARE SUBMITTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
  
2014-04-09 11:52:184/9/14 RESUB ZONING, SENT TO ES.SG

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-15 Cont ID  
Sent By eschneid Date 2013-10-15 Time 15:32 Rev Time 0.50
Received By eschneid Date 2013-09-30 Time 10:10 Sent To FIRE
Notes
2013-10-15 15:49:28FAILED
  
 1) NO SURVEY WAS PROVIDED.
  
 2) THE SITE PLAN IS INADEQUATE AS IT DOES NOT SHOW
 DIMENSIONS FROM THE PROPOSED GENERATOR AND PAD TO THE
 TO THE PROPERTY LINES AND EXISTING STRUCTURES.
  
 3) NO DETAILS OF THE GENERATOR SIZE, TO INCLUDE THE
 HEIGHT WER PROVIDED.
  
 4) THE GENERATOR SHALL BE SCREENED FOR IT'S FULL HEIGHT
 BY AN OPAQUE WALL/FENCE WITH GATE AND LANDSCAPE. NO
 SCREENING IS SHOWN.
  
 5) MORE COMMENTS MAY BE GENERATED WHEN COMPLETE PLANS
 ARE SUBMITTED.
  
 CONTACT ERIC SCHNEIDER @ (561) 822-1446.
2013-09-30 10:11:04ZONING RECEIVED. SENT TO ES FOR REVIEW.