Plan Review Details - Permit 13090807
Plan Review Stops For Permit 13090807
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 10:49 Rev Time 0.00
Received By rmcdouga Date 2013-12-10 Time 15:00 Sent To  
Notes
2013-12-11 11:08:01PASSED WITH EXCEPTIONS SEE REDLINED NOTES ON THE PLANS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By rmcdouga Date 2013-10-28 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2013-10-28 Time 06:44 Sent To  
Notes
2013-10-28 08:20:152010 FBC
  
 DENIED BY BUILDING
  
 1) THE NUMBERING OF THE PLAN SHEETS INDICATE THAT
 SHEETS 1 AND 3 ARE MISSING. PLEASE SUBMIT MISSING
 SHEETS. CITY AMENDMENTS 107.2.1
  
 2) PROVIDE AREA CALCULATIONS ON THE PLANS. SPECIFY
 EXISTING CONDITIONED LIVING SPACE AND PROPOSED
 CONDITIONED LIVING SPACE. CITY AMENDMENTS 107.2.1.3
  
 3) PROVIDE AN EXTERIOR OPENING IN-FILL STRUCTURAL
 DETAIL. CITY AMENDMENTS 107.2.1
  
 4) THE ULTIMATE WIND SPEED OF 160 MPH LISTED ON SHEET 4
 IS INCORRECT. THE CITY OF WEST PALM BEACH HAS AN
 ULTIMATE WIND SPEED OF 170 MPH. FBC FIGURE R301.2(4)
  
 5) SUBMIT TWO COPIES OF ENERGY CALCULATIONS FOR THE
 ADDED LIVING SPACE AS REQUIRED BY FBC ENERGY
 CONSERVATION SECTION 101.4.3.
  
 6) SHOW COMPLIANCE WITH FBC R314.3.1 FOR SMOKE ALARMS
 IN THE DWELLING UNIT.
  
 7) SHOW COMPLIANCE WITH FBC R318 FOR PROTECTION AGAINST
 TERMITES.
  
 8) SHOW COMPLIANCE WITH FBC R806 FOR REQUIRED ROOF
 VENTILATION.
  
 9) SHOW COMPLIANCE WITH FBC R807 FOR REQUIRED ATTIC
 ACCESS.
  
 10) THE SECOND FLOOR GUARDRAIL HEIGHT IS SPECIFIED AS
 3'-6" ON SHEET 5 AND 36" ON SHEET 7. PLEASE CLARIFY.
 FBC R312.2 AND CITY AMENDMENTS 107.2.1
  
 11) SPECIFY THE CONNECTORS THAT WILL BE USED TO ANCHOR
 THE GIRDER TRUSS THAT WILL CARRY THE NEW BALCONY FLOOR
 TRUSSES SHOWN ON SHEET 7. FBC R802.1.6.5
  
 12) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE NEW BALCONY FLOOR TRUSSES TO THE 2 X 12 WALL LEDGER
 SHOWN ON SHEET 7. FBC R802.1.6.5
  
 13) THE CROSS SECTION ON SHEET 7 APPEARS TO CONFLICT
 WITH THE ROOF FRAMING PLAN FOR THE ORIENTATION OF THE
 ROOF TRUSSES. PLEASE CLARIFY. CITY AMENDMENTS 107.2.1
  
 14) THE DETAIL FOR THE GABLE END FRAMING ON SHEET 7
 SHOWS 2 X 12 RAFTERS WITH A 2 X 12 BEAM BELOW IT
 SUPPORTED BY A 4 X 4 POST. THIS CONDITION DOES NOT
 APPEAR ON THE PLANS. PLEASE CLARIFY.
  
 15) PROVIDE A FRAMING DETAIL OR RAKE BEAM DETAIL FOR
 THE GABLE END AT THE RIGHT ELEVATION. FBC R601.2
  
 16) SUBMIT TWO COPIES OF A SURVEY / SITE PLAN THAT
 INDICATES THE SEPARATION DISTANCE FROM THE PROPERTY
 LINES. FBC R302.1
  
 17) SUBMIT A SURFACE DRAINAGE PLAN THAT SHOWS
 COMPLIANCE WITH FBC R401.3.
  
 18) SUBMIT TWO COPIES OF CURRENT PRODUCT APPROVALS FOR
 THE METAL ROOF FL# 11175.1, THE POLYGLASS SELF ADHESIVE
 UNDERLAYMENT, THE CASEMENT WINDOWS FL# 245.2, THE
 SLIDING GLASS DOOR FL# 251.6, THE CERTAINTEED MODIFIED
 ROOFING FL# 2533.1, THE 8" LINTELS AND THE SIMPSON
 CONNECTORS. MARK THE SPECIFIC ASSEMBLY AND ITS DESIGN
 PRESSURES FOR THE ITEM YOU WILL USE IN THE PRODUCT
 APPROVAL AND MAKE SURE THAT THE DESIGN PRESSURES YOU
 SELECT ARE GREATER THAN THE REQUIRED PRESSURES
 SPECIFIED ON THE PLANS. DCA RULE 9N-3
  
 19) CITY AMENDMENT 107.3.4.1 REQUIRES THE DESIGNER OF
 RECORD OF THE PROJECT TO REVIEW AND APPROVE THE PRODUCT
 APPROVALS IN WRITING. SPECIFICATION OF THE PRODUCT
 APPROVALS ON THE SIGNED AND SEALED PLANS MEETS THIS
 REQUIREMENT.
  
 20) THE SYSTEM NUMBERS SPECIFIED IN THE PRODUCT
 APPROVAL AFFIDAVIT ON SHEET 4 (ALSO ON SHEET 7) FOR THE
 CERTAINTEED ROOFING FL 2533.1 HAS THE WRONG SYSTEM
 NUMBERS LISTED. W-39 IS A SELF ADHERING SYSTEM AND W-42
 AND W-44 ARE HYBIRD SYSTEMS WITH DIFFERENT BASE SHEETS.
 ALSO THE SPECIFIED DESIGN PRESSURES LISTED DO NOT
 CORRESPOND TO THESE SYSTEMS. PLEASE CORRECT.
  
 21) PROVIDE WINDOW AND DOOR BUCK ATTACHMENT DETAILS ON
 THE PLANS. FBC R612.10.2
  
 NOTE: PLEASE SUBMIT A RESPONSE LETTER INDICATING HOW
 THE REVIEW COMMENTS HAVE BEEN ADDRESSED. THIS WILL HELP
 TO EXPEDITE YOUR NEXT REVIEW.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2013-12-10 Cont ID  
Sent By albarran Date 2013-12-10 Time 20:07 Rev Time 0.00
Received By albarran Date 2013-12-10 Time 19:38 Sent To B
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2013-10-16 Cont ID  
Sent By dharvey Date 2013-10-16 Time 09:47 Rev Time 0.00
Received By dharvey Date 2013-10-16 Time 08:51 Sent To  
Notes
2013-10-16 09:56:24THE FOLLOWING ITEMS NEED TO BE ADDRESS FOR A
 SATISFACTORY ELECTRICAL REVIEW:
 1. MUST PROVIDE A SERVICE RISER DIAGRAM TO INCLUDE ANY
 SUB PANELS IF ANY. RISER DIAGRAM SHALL INDICATE WIRE
 SIZE AND PROPER GROUNDING.
 2. MUST INDICATE THE LOCATION OF THE EXISTING PANEL
 BEFORE THE REMODEL.
 3. ELECTRICAL NOTES ADDRESS NEW A/C UNITS. THE
 ELECTRICAL CONNECTIONS TO IT SHALL BE INDICATED ON
 PLANS.
 4. PROVIDE THE REQUIRED ILLUMINATION FOR THE RELOCATED
 SPIRAL STAIRS TO COMPLY W/FBC 2010
 5. NEW OPENINGS TO THE POOL AREA SHALL BE PROPERLY
 PROTECTED WITH POOL ALARMS AS REQUIRED.
 6. SHOW DISTANCE FROM RESIDENCE TO THE POOL WATER EDGE.
 SENT BACK TO BIN BY: MA

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2013-12-11 Cont ID  
Sent By dkittred Date 2013-12-11 Time 11:07 Rev Time 0.00
Received By rmcdouga Date 2013-11-26 Time 13:44 Sent To Z
Notes
2013-11-26 13:45:08INCOMING SENT TO R-01 BOX. JW

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2013-10-28 Cont ID  
Sent By rmcdouga Date 2013-10-28 Time 11:18 Rev Time 0.00
Received By rmcdouga Date 2013-09-25 Time 07:44 Sent To  
Notes
2013-09-26 07:49:34RO9

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 2 Status N Date 2013-12-11 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 11:02 Rev Time 0.00
Received By rmcdouga Date 2013-12-11 Time 11:02 Sent To  
Notes
2013-12-11 11:05:31NOT ADDING ANY ADDITIONAL LIVING SPACE. CALLED MICHELLE
 AT COUNTY IMPACT FEE OFFICE AND AFTER CHECKING THE
 PROPERTY APPRAISERS WEB SITE WAS TOLD THAT NO IMPACT
 FEES WERE OWED AND THAT NO REVIEW WAS REQUIRED.

Review Stop IMPACT COUNTY IMPACT FEES
Rev No 1 Status F Date 2013-10-28 Cont ID  
Sent By rmcdouga Date 2013-10-28 Time 07:03 Rev Time 0.00
Received By rmcdouga Date 2013-10-28 Time 07:03 Sent To  
Notes
2013-10-28 07:08:01WHEN THE PLANS HAVE BEEN APPROVED, ONE SET WILL NEED TO
 BE SIGNED OUT AND TAKEN TO PALM BEACH COUNTY FOR AN
 IMPACT REVIEW FEE. THE PLANS WITH THE IMPACT FEE REVIEW
 STAMP AND A COPY OF THE PAID RECIEPT SHALL BE RETURNED
 TO THE CITY BUILDING DEPARTMENT BEFORE THE PERMIT CAN
 BE ISSUED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2013-10-28 Cont ID  
Sent By rmcdouga Date 2013-10-28 Time 07:08 Rev Time 0.00
Received By rmcdouga Date 2013-10-28 Time 06:44 Sent To  
Notes
2013-10-28 07:09:43NO MECHANICAL PLANS WERE SUBMITTED AND NO MECHANICAL
 PERMIT WAS APPLIED FOR AT THIS TIME. A SEPARATE PERMIT,
 APPLICATION AND REVIEW WILL BE REQUIRED.

Review Stop R ROOF PLAN REVIEW
Rev No 1 Status P Date 2014-05-01 Cont ID  
Sent By rmcdouga Date 2014-05-01 Time 10:35 Rev Time 0.00
Received By rmcdouga Date 2014-05-01 Time 10:35 Sent To  
Notes
2014-05-01 10:42:33ROOFING PRODUCT APPROVALS
  
 1) FLAT : CERTAINTEED MODIFIED BITUMEN - FL 2533-R9
  
 2) SLOPE : SOUTHEASTERN METALS 5V CRIMP - FL 11175-R1
 WITH POLY GLASS UNDERLAYMENT FL#5259.1

Review Stop Z ZONING
Rev No 2 Status P Date 2013-11-27 Cont ID  
Sent By rmcdouga Date 2013-12-11 Time 11:07 Rev Time 0.00
Received By dkittred Date 2013-11-27 Time 12:39 Sent To  
Notes
2016-09-15 13:18:28EAST BELCONY IS A GRANDFATHERED PART OF THE BUILDING.
  
 PLEASE CONTACT
 NATHAN WIRA
 [email protected]
 (561)822-1442
  
2013-11-27 12:39:58CONSTRUCTING IS OCCURING WITHIN EXISTING BUILDING
 FOOTPRINT. -DK

Review Stop Z ZONING
Rev No 1 Status F Date 2013-10-10 Cont ID  
Sent By dkittred Date 2013-10-10 Time 08:57 Rev Time 0.00
Received By dkittred Date 2013-10-10 Time 08:49 Sent To  
Notes
2013-10-10 08:56:59PLANNING & ZONING COMMENTS: ***FAILED***
  
 1. APPEARS ALL CONSTRUCTION MAY BE WITHIN THE EXISTING
 BUILDNG FOOTPRINT. PLEASE CLARIFY THIS BY PROVIDING A
 SITE PLAN INDICATING WHERE THE PROPOSED CHANGES ARE
 TAKING PLACE AND THE SETBACKS FOR THE PRINCPAL
 STRUCTURE BEING MODFIED..
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT:
  
 DANIELLE J. KITTREDGE, AICP
 SENIOR PLANNER
 PLANNING & ZONING DIVISION
 PHONE: (561)-822-1443
 EMAIL: [email protected]
  
2013-10-09 13:40:2710/9/13